background image

Rows of series installation

 H

 1/2H

L

A

25 cm / 9.8” or more

1/2H < L 

 H

30 cm / 11.8” or more

>

 H

Can not be installed

               The relations between H, A and L 

are as follows.

Outdoor Unit Dimentsion (mm/inch) Mounting Dimentsion (mm/inch)

A

B

W

H

A

B

D

Outdoor unit C

L

H

300 cm / 118” or more

A

60 cm / 23.6” 

 or more

150 cm / 59” 

 or more

25 cm / 9.8” 

 or more

25 cm / 9.8” 

  or more

When connecting refrigerant piping, 

do not

 let substances or gases other than the specified 
refrigerant enter the unit. The presence of other 
gases or substances will lower the unit’s capacity,
and can cause abnormally high pressure in the 
refrigeration cycle. This can cause explosion 
and injury.

Refrigerant Piping 
Connection 

Oil traps

 CAUTION

 

If oil flows back into the outdoor unit’s 
compressor, this might cause liquid compression 
or deterioration of oil return. Oil traps in the 
rising gas piping can prevent this.
An oil trap should be installed every 6m(20ft) 
of vertical suction line riser.    

6m/20ft 

Indoor unit/

Outdoor unit 

Indoor unit/

Outdoor unit 

Please check the elevation difference  between 

the indoor unit and the outdoor unit, the length

of the refrigerant pipe, and the curved places 

(bend) of the pipe as following:

Elevation difference: no more than 10m/32.8ft 

Pipe length: no more than 20m/65.6ft

Bends: no more than 5 places

A  minimum pipe run of 3 metres is required to 

minimise vibration & excessive noise.

Note on Pipe Length

681x434x285 (26.8x 17.1x 11.2)

460 (18.1)

292 (11.5)

700x550x270 (27.5x 21.6x 10.6)

450 (17.7)

260 (10.2)

946x810x420 (37.2x 31.9x 16.5)

673 (26.5)

403 (15.9) 

946x810x410 (37.2x 31.9x 16.1)

673 (26.5)

403 (15.9) 

845x702x363 (33.3x 27.6x 14.3)

540 (21.3)

350 (13.8)

770x555x300 (30.3x 21.8x 11.8)

487 (19.2)

298 (11.7)

800x554x333 (31.5x 21.8x 13.1)

514 (20.2)

340 (13.4)

W x H x D

EN

31

Содержание KFS-48HRG32X

Страница 1: ...INSTRUKCJAOBSŁUGI OWNER S INSTALLATIONMANUAL BEDIENUNGSANLEITUNG KLIMATYZATOR KANAŁOWY SPLIT TYPE AIR CONDITIONER DECKENEINBAU KLIMAANLAGE PL EN KFS 48HRG32X KOE30U 48HFN32X ...

Страница 2: ......

Страница 3: ...EROWANIA 18 ZESTAW SMART AC 38 OWNER S INSTALLATIONMANUAL SPLIT TYPE AIR CONDITIONER 5 INSTALLATION INSTRUCTIONS 24 AIR CONDITIONER REMOTE CONTROLLER 49 SMART AC KIT 83 BEDIENUNGSANLEITUNG DECKENEINBAU KLIMAANLAGE 41 FERNBEDIENUNG 54 SMART AC 128 5 5 41 PL EN DE ...

Страница 4: ......

Страница 5: ...llation Manual Thank you for choosing our product For proper operation please read and keep this manual carefully If you have lost the Owner s Manual please contact the local agent or visit www kaisai com or sent email to handlowy kaisai pl for electronic version EN 5 ...

Страница 6: ... the indoor unit 26 5 Installing the rodent proof mesh 26 6 Piping and binding 27 7 Applying the sealant putty and installing the wall hole cover 27 8 Drill wall hole for connective piping 28 9 Connect drain hose 28 Outdoor Unit Installation 29 1 Select installation location 29 2 Install drain joint 30 3 Anchor outdoor unit 30 Refrigerant Piping Connection 31 A Note on Pipe Length 31 B Connection ...

Страница 7: ...acking Indoor unit 1 Put the indoor unit on the lower packaging foam 2 Put the packing bag on the indoor unit 2 Attach the upper packaging foam to the unit 3 Put the carton on the unit 4 Seal it with the tape 5 Using the packing belt if necessary Outdoor unit 1 Put the outdoor unit into the packing bag 2 Put the bottom foam into the box 3 Put the unit into the carton then put the upper packaging f...

Страница 8: ... immediately turn off the unit and disconnect the power Call your dealer for instructions to avoid electric shock fire or injury Do not insert fingers rods or other objects into the air inlet or outlet This may cause injury since the fan may be rotating at high speeds Do not use flammable sprays such as hair spray lacquer or paint near the unit This may cause fire or combustion Do not operate the ...

Страница 9: ...e unit Do not share the electrical outlet with other appliances Improper or insufficient power supply can cause fire or electrical shock If connecting power to fixed wiring an all pole disconnection device which has at least 3mm clearances in all poles and have a leakage current that may exceed 10mA the residual current device RCD having a rated residual operating current not exceeding 30mA and di...

Страница 10: ...liance to its support please read the information for details in indoor unit installation and outdoor unit installation sections For units that have an auxiliary electric heater do not install the unit within 1 meter 3 feet of any combustible materials Do not install the unit in a location that may be exposed to combustible gas leaks If combustible gas accumulates around the unit it may cause fire...

Страница 11: ...omply with ISO 14903 Amount of refrigerant to be charged kg maximum installation height m Minimum room area m 2 048 0 6m 35 2 048 3 0 0 6m 80 3 0 Model Btu h 30000 30000 48000 48000 0 6m 80 European Disposal Guidelines This appliance contains refrigerant and other potentially hazardous materials When disposing of this appliance the law requires special collection and treatment Do not dispose of th...

Страница 12: ...17 C 32 C 62 F 90 F 0 C 30 C 32 F 86 F 10 C 32 C 50 F 90 F Outdoor Temperature 0 C 50 C 32 F 122 F 15 C 24 C 5 F 75 F 0 C 50 C 32 F 122 F 0 C 52 C 32 F 126 F For special tropical models 0 C 52 C 32 F 126 F For special tropical models 15 C 50 C 5 F 122 F For models with low temp cooling systems FOR OUTDOOR UNITS WITH AUXILIARY ELECTRIC HEATER Inverter Type When outside temperature is below 0 C 32 F...

Страница 13: ... may form and drip into the machine To reset the louver press the manual button which will reset the horizontal louver settings To further optimize the performance of your unit do the following Keep doors and windows closed Limit energy usage by using TIMER ON and TIMER OFF functions Do not block air inlets or outlets Regularly inspect and clean air filters NOTE Room relative humidity less than 80...

Страница 14: ...to Automatically chooses the operation mode by sensing the difference between the actual ambient room temperature and the set temperature on the remote controller The fan speed is automatically controlled Cool Enables you to enjoy the cooling effect at you preferred setting temperature Temperature range 16 C 17 C 30 C 60 F 62 F 86 F or 20 C 28 C 68 F 82 F Dry Enables you to set the desired tempera...

Страница 15: ...lly moving the horizontal and vertical airflow direction louvers could damage the air conditioner 6 button 4 Fan button This button is used to select the desired fan speed Each time you push the button the fan speed is shifted in the following sequence LOW MED HIGH AUTO Fan speed display Select LOW fan speed and zones 1 2 will illuminate Select MED fan speed and zones 1 4 will illuminate Select HI...

Страница 16: ...ler seven times or more the Wireless module will enter into AP mode A long beep will be heard and the Wireless control indicator will flash quickly which means the user can do the next configuration Between wireless control network function and wire controller function you can only choose one When the air conditioner switches to heating mode the electrical heating feature is activated automaticall...

Страница 17: ...the cooling efficiency of your unit and can also be bad for your health Make sure to clean the filter once every two weeks WARNING DO NOT REMOVE OR CLEAN THE FILTER BY YOURSELF Removing and cleaning the filter can be dangerous Removal and maintenance must be performed by a certified technician Cleaning the dust filter located at the bottom of the unit Seize the left and right at the bottom of the ...

Страница 18: ...or unit This can destroy insulation and cause electrical shock Do not expose filter to direct sunlight when drying This can shrink the filter CAUTION Any maintenance and cleaning of outdoor unit should be performed by an authorized dealer or a licensed service provider Any unit repairs should be performed by an authorized dealer or a licensed service provider Maintenance Long Periods of Non Use If...

Страница 19: ... OFF or in COOL mode The noise is also heard when the drain pump optional is in operation A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the unit s plastic parts Both the indoor unit and outdoor unit make noises A low hissing sound may occur during operation This is normal and is caused by refrigerant gas flowing through both the indoor and outd...

Страница 20: ...iption of the unit malfunction as well as your model number Troubleshooting When troubles occur please check the following points before contacting a repair company Problem Possible Causes Solution Poor Cooling Performance Temperature setting may be higher than ambient room temperature Lower the temperature setting The heat exchanger on the indoor or outdoor unit is dirty Clean the affected heat e...

Страница 21: ...uxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use Low refrigerant due to leak or long term use Check for leaks re seal if necessary and top off refrigerant Indicator lamps continue flashing The unit may stop operation or continue to run safely If the indicator lamps continue to flash or error codes appear wait for abou...

Страница 22: ...The items are not included with the air conditioner must be purchased separately Name Shape Quantity PC Parts you must purchase separately Consult the dealer about the proper pipe size of the unit you purchased Connecting pipe assembly Liquid side Gas side Φ6 35 1 4i n Φ9 52 3 8in Φ12 7 1 2in Φ9 52 3 8in Φ12 7 1 2in Φ16 5 8in Φ19 3 4in Φ22 7 8in Remote controller Fixing screw for remote controller...

Страница 23: ...nit INSTALLATION ORDER Install the outdoor unit Evacuate the refrigeration system Connect the refrigerant pipes Perform a test run Installation Summary Indoor Unit 5 Connect Wiring not applicable for some locations in North America EN 23 ...

Страница 24: ...pe vent pipe Connection cable Connection pipe Refrigerant pipe port Air outlet Indoor unit Outdoor unit Outdoor unit A Outdoor unit B NOTE ON ILLUSTRATIONS Illustrations in this manual are for explanatory purposes The actual shape of your indoor unit may be slightly different The actual shape shall prevail 5 6 7 7 8 8 9 10 Unit Parts EN 24 ...

Страница 25: ...ge Noise from the unit will not disturb other people Firm and solid the location will not vibrate Strong enough to support the weight of the unit A location at least one meter from all other electrical devices e g TV radio computer DO NOT install unit in the following locations Near any source of heat steam or combustible gas Near flammable items such as curtains or clothing Near any obstacle that...

Страница 26: ...on the indoor unit has any fasteners holding it in place and tear off the notice sticker 2 Remove the fasteners from the roller according to the directions on the sticker 1 Measure the position of the holes for installation 2 Insert the M8 bolts into the unit while it is on the floor the amount of bolts used depends on the number of holes on the unit s chassis 3 Lift up the indoor unit so that the...

Страница 27: ...place 3 Arrange the piping so that the drainage hose is on the bottom the connecting piping is in the middle and the electrical wiring is at the top Step 6 Piping and binding drainage electrical wiring refrigerant pipe The electrical wiring drainage hose and refrigerant pipe must exit the binding in a suitable place All binding must be mutually connected evenly applied and aesthetically pleasing N...

Страница 28: ...rcefully as this could cause it to disconnect Indoor Drainpipe Installation 1 Make sure the drain pipe is connected to the outdoor side downward 2 The hard polyvinyl chloride PVC plastic pipe external diameter 26 mm 1 sold in the market is suitable for the attached soft drain pipe 3 Please connect the Soft Drain Pipe with the Drain Pipe then fix it with band if you have to connect the Drain Pipe i...

Страница 29: ...air outlet fan is at a 90 angle to the direction of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind If the unit is frequently exposed to heavy rain or snow Build a shelter above the unit to protect it from the rain or snow Be careful not to obstruct air flow around the unit If the unit is frequently exposed ...

Страница 30: ...eal on the end of the drain joint that will connect to the outdoor unit 2 Insert the drain joint into the hole in the base pan of the unit 3 Rotate the drain joint 90 until it clicks in place facing the front of the unit 4 Connect a drain hose extension not included to the drain joint to redirect water from the unit during heating mode If the drain joint doesn t come with a rubber seal see Fig B d...

Страница 31: ...liquid compression or deterioration of oil return Oil traps in the rising gas piping can prevent this An oil trap should be installed every 6m 20ft of vertical suction line riser 6m 20ft Indoor unit Outdoor unit Indoor unit Outdoor unit Please check the elevation difference between the indoor unit and the outdoor unit the length of the refrigerant pipe and the curved places bend of the pipe as fol...

Страница 32: ...cally reduce the heating efficiency of the unit Step 2 Remove burrs Burrs can affect the air tight seal of refrigerant piping connection They must be completely removed 1 Hold the pipe at a downward angle to prevent burrs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down Step 3 Flare pipe ends Proper flaring is es...

Страница 33: ...ble with other wires While bundling these items together do not intertwine or cross the signal cable with any other wiring Check to make sure there is no refrigerant leak after completing the installation work If there is a refrigerant leak ventilate the area immediately and evacuate the system refer to the Air Evacuation section of this manual 7 Thread this pipeline through the wall and connect i...

Страница 34: ...If connecting power to fixed wiring a switch or circuit breaker that disconnects all poles and has a contact separation of at least 1 8in 3mm must be incorporated in the fixed wiring The qualified technician must use an approved circuit breaker or switch 7 Only connect the unit to an individual branch circuit outlet Do not connect another appliance to that outlet 8 Make sure to properly ground the...

Страница 35: ... actual shape shall prevail Indoor unit Outdoor unit Air switch purchased seperately Air switch purchased seperately purchased seperately Indoor unit power wires Indoor Outdoor connective wires Outdoor unit power wires Indoor unit Outdoor unit Air switch purchased seperately purchased seperately Indoor unit power wires Indoor Outdoor connective wires B C Not applicable for North America NOTE In No...

Страница 36: ...s corresponding terminal Refer to the Serial Number and Wiring Diagram located on the cover of the electric control box While connecting the wires please strictly follow the wiring diagram The refrigerant circuit can become very hot Keep the interconnection cable away from the copper tube 4 Clamp down the cable with the cable clamp The cable must not be loose or pull on the u lugs 5 Reattach the e...

Страница 37: ...m for at least 15 minutes or until the Compound Meter reads 76cmHG 10 Pa 2 3 4 5 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that there has been no change in system pressure 8 If there is a change in system pressure refer to Gas Leak Check section for information on how to check for leaks If there is no change in system pressur...

Страница 38: ...g 0 42oZ m ft φ6 35 1 4 φ9 52 3 8 φ12 7 1 2 R22 orifice tube in the indoor unit Total pipe length standard pipe length x 30g 0 32oZ m ft Total pipe length standard pipe length x 65g 0 69oZ m ft Total pipe length standard pipe length x 115g 1 23oZ m ft R22 orifice tube in the outdoor unit Total pipe length standard pipe length x15g 0 16oZ m ft Total pipe length standard pipe length x30 0 32oZ m ft ...

Страница 39: ...d correctly d Ensure the indicators on the remote control and the display panel on the indoor unit work properly e Ensure the manual buttons on the indoor unit works properly f Check to see that the drainage system is unimpeded and draining smoothly g Ensure there is no vibration or abnormal noise during operation 5 For the Outdoor Unit a Check to see if the refrigeration system is leaking b Make ...

Страница 40: ...EN 40 ...

Страница 41: ...ion and Owner s Manual Thank you for choosing our product For proper operation please read and keep this manual carefully If you have lost the Owner s Manual please contact the local agent or visit www kaisai com or sent email to handlowy fgpoland pl for electronic version EN 41 ...

Страница 42: ... the indoor unit does not have a particular function pressing that function s button on the remote control will have no effect When there are wide differentces between Remote controller Manual and USER S MANUAL on function description the description of USER S MANUAL shall prevail Table of Contents Remote Controller Specifications 02 Handling the Remote Controller 03 Buttons and Functions 04 Remot...

Страница 43: ...BGEFU1 RG10B1 F BGEF RG10B2 F BGCEF RG10B10 F BGEF RG10B H BGEF RG10B H1 BGEFU1 RG10B1 H BGEF RG10B2 H BGCEF RG10B10 H BGEF RG10B G BGEF RG10B G1 BGEFU1 RG10B1 G BGEF RG10B2 G BGCEF RG10B10 G BGEF RG10Y1 F BGEF RG10Y1 H BGEF RG10Y1 G BGEF Model Rated Voltage 8m 3 0V Dry batteries R03 LR03 2 Environment Signal Receiving Range 5 C 60 C 23 F 140 F AUTO LOW MED HIGH NOTE For model of RG10Y1 F H G BGEF...

Страница 44: ...the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide ...

Страница 45: ...s Max temperatur e is O O 30 C 86 F Set timer to turn unit on or off Saves energy during sleeping hours Selects fan speeds in the following order AUTO LOW MED HIGH NOTE Holding this button down for 2 seconds will activate Silence feature Enables unit to reach preset temperature in shortest possible time Used to restore the current settings or resume previous settings Starts and stops the horizonta...

Страница 46: ...fan speeds in the following order AUTO LOW MED HIGH NOTE Holding this button down for 2 seconds will activate Silence feature Enables unit to reach preset temperature in shortest possible time Starts and stops the horizontal louver movement Hold down for 2 seconds to initiate vertical louver auto swing feature some units TEMP SET Increases temperate in 1 C increments Max temperature is 30 C Decrea...

Страница 47: ... relative function signs are shown on the display window Remote Screen Indicators Displays when LOCK feature is activated LOW MED HIGH AUTO Lights up when remote sends signal to indoor unit Displays selected fan speed Displays the current including mode This fan speed can not be adjusted in AUTO or DRY mode Not available for this unit Not available for this unit Displays the set temperature by def...

Страница 48: ...tically select the COOL FAN or HEAT operation based on the set temperature 1 Press the MODE button to select AUTO 2 Set your desired temperature using the TEMP or TEMP button Set your desired temperature using the TEMP or TEMP button 3 Press the ON OFF button to start the unit Press the ON OFF button to start the unit NOTE FAN SPEED can t be set in AUTO mode COOL Mode Basic operation 1 Press the M...

Страница 49: ...OFF button to start the unit 1 Press the MODE button to select HEAT mode 2 3 Press FAN button to select the fan speed AUTO LOW MED or HIGH 4 4 1 3 2 1 3 2 DRY Mode dehumidifying NOTE FAN SPEED cannot be changed in DRY mode HEAT Mode NOTE As outdoor temperature drops the performance of your unit s HEAT function may be affected In such instances we recommend using this air conditioner in conjunction...

Страница 50: ...4 2 Cancel either function by setting its timer to 0 0h Point remote to unit and wait 1sec the TIMER ON will be activated Press TIMER button to initiate the OFF time sequence Point remote to unit and wait 1sec the TIMER OFF will be activated Current time 1PM 2 00PM 3 00PM 4PM 5PM 6PM Timer starts Unit turns ON Unit turns OFF 2 5 hours later 5 hours later 3 30PM Example If current timer is 1 00PM t...

Страница 51: ...s including operating mode setting temperature fan speed level and sleep feature if activated When you select Turbo feature in COOL mode the unit will blow cool air with strongest wind setting to jump start the cooling process When you select Turbo feature in HEAT mode for units with Electric heat elements the Electric HEATER will activate and jump start the heating process Clean Function Press CL...

Страница 52: ...will cancel silence function Silence function O LED LED Clean 5s 5s Turbo Press this button 2 times during one second under HEAT Mode and setting temperature of 17 C 62 F or 20 C for model of RG10B10 F H G BGEF The unit will operate at high fan speed while compressor on with temperature automatically set to 8 C 46 F Press this button 2 times during one second under HEAT Mode and setting temperatur...

Страница 53: ......

Страница 54: ......

Страница 55: ......

Страница 56: ...kaisai com ...

Отзывы: