Engineering of insulation
Installation
105
9. Engineering of insulation
9.1 Insulation of refrigerant pipe
9.1.1 Operational procedure of refrigerant pipe insulation
Cut the suitable pipe
→ insulation (except joint section) → flare the pipe → piping layout and connection→
vacuum drying
→ insulate the joint parts
9.1.2 Purpose of refrigerant pipe insulation
During operation, temperature of gas pipe and liquid pipe shall be over-heating or over-cooling
extremely. Therefore, it is necessary to carry out insulation; otherwise it shall debase the performance
of unit and burn compressor.
Gas pipe temperature is very low during cooling. If insulation is not enough, it shall form dew and cause
leakage.
Temperature of gas pipe is very high (generally 50-100
℃
) during heating. Insulation work must be
carried out to prevent hurt by carelessness touching.
9.1.3 Insulation material selection for refrigerant pipe
The burning performance should over 120
℃
According to the local law to choose insulation materials
The thickness of insulation layer shall be above 10mm.If in hot or wet environment place, the layer of
insulation should be thicker accordingly.
9.1.4 Installation highlights of insulation construction
Gas pipe and liquid pipe shall be insulated separately, if the gas pipe and liquid pipe were insulated
together; it will decrease the performance of air conditioner.
Liquid pipe
Insulation meterial
Gas pipe
The insulation material at the joint pipe shall be 5~10cm longer than the gap of the insulation material.
The insulation material at the joint pipe shall be inserted into the gap of the insulation material.
The insulation material at the joint pipe shall be banded to the gap pipe and liquid pipe tightly.
The linking part should be use glue to paste together
Be sure not bind the insulation material over-tight, it may extrude out the air in the material to cause bad
insulation and cause easy aging of the material.
9.2 Insulation of drainage pipe
9.2.1 Operational procedure of refrigerant pipe insulation
Select the suitable pipe
→ insulation (except joint section) → piping layout and connection→ drainage test→
insulate the joint parts
9.2.2 Purpose of drainage pipe insulation
The temperature of condensate drainage water is very low. If insulation is not enough, it shall form dew and
Содержание KCD-18HRFN1-QRC4
Страница 1: ...Contents i Energy Related Products SUPER DC INVERTER SERIES Service Manual 2013 LFIS B 1309...
Страница 2: ......
Страница 4: ......
Страница 17: ...Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 23: ...Field Wiring Indoor Units 19 9 Field Wiring...
Страница 31: ...Wiring Diagrams Indoor Units 27 KTB 24HWDN1 QRC4...
Страница 42: ...Service Space 38 Indoor Units 3 Service Space...
Страница 44: ...Wiring Diagrams 40 Indoor Units KUE 36HRFN1 QRC8 A...
Страница 47: ...Indoor Units 43 9 Field Wiring...
Страница 50: ...Dimensions 46 Indoor Units 2 Dimensions...
Страница 51: ...Service Space Indoor Units 47 3 Service Space...
Страница 52: ...Wiring Diagrams 48 Indoor Units 4 Wiring Diagrams KCA2U 12HRFN1 QRC8 KCA2 18HRFN1 QRC8...
Страница 56: ...52 Indoor Units 10 Field Wiring KCA2U 12HRFN1 QRC8 KCA2 18HRFN1 QRC8...
Страница 58: ......
Страница 61: ...Dimensions Console Type 57 2 Dimensions KFAU 12HRFN1 QRC8 KFA 16HRFN1 QRC8...
Страница 62: ...Service Space 58 Console Type 3 Service Space...
Страница 63: ...Wiring Diagrams Console Type 59 4 Wiring Diagrams KFAU 12HRFN1 QRC8 KFA 16HRFN1 QRC8...
Страница 68: ...Field Wiring 64 Console Type 10 Field Wiring KFAU 12HRFN1 QRC8 KFA 16HRFN1 QRC8...
Страница 74: ...Wiring Diagrams 70 Outdoor Units 4 Wiring Diagrams KOU 12HFN1 QRC8...
Страница 76: ...Wiring Diagrams 72 Outdoor Units KOU 36HFN1 RRC4 KOU 36HFN1 RRC8 520 KOU 36HFN1 QRC8 5A0...
Страница 77: ...Wiring Diagrams Outdoor Units 73 KOU 36HFN1 RRC8 5A0...
Страница 102: ...Refrigerant pipe installation 98 Installation...
Страница 110: ...Engineering of insulation 106 Installation cause leakage to damage the house decoration...