Kaisai GEO KGE-12GRGI Скачать руководство пользователя страница 5

Safety 

Precautions

 Page 4

• 

Do not

 clean the air conditioner with combustible cleaning agents. Combustible cleaning agents 

can cause fire or deformation.

CLEANING AND MAINTENANCE WARNINGS

• 

Turn off the device and disconnect the power before cleaning. Failure to do so can cause 

electrical shock.

• 

Do not

 clean the air conditioner with excessive amounts of water.

 CAUTION

• 

Turn off the air conditioner and disconnect the power if you are not going to use it for a long time.

• 

Turn off and unplug the unit during storms.

• 

Make sure that water condensation can drain unhindered from the unit.

• 

Do not

 operate the air conditioner with wet hands. This may cause electric shock.

• 

Do not

 use device for any other purpose than its intended use.

• 

Do not

 climb onto or place objects on top of the outdoor unit. 

• 

Do not

 allow the air conditioner to operate for long periods of time with doors or windows open, 

or if the humidity is very high.

ELECTRICAL WARNINGS

• 

Only use the specified power cord. If the power cord is damaged, it must be replaced by the 

manufacturer

, its service agent or similarly qualified persons in order to avoid a hazard. 

• 

Keep power plug clean. Remove any dust or grime that accumulates on or around the plug. Dirty 

plugs can cause fire or electric shock.

• 

• 
• 

• 

• 

• 

• 

Do not

 pull power cord to unplug unit. Hold the plug firmly and pull it from the outlet. Pulling 

directly on the cord can damage it, which can lead to fire or electric shock.

Do not

modify the length of the power supply cord or use an extension cord to power the unit.  

Do not

share the electrical outlet with other appliances. Improper or insufficient power supply 

can cause fire or electrical shock.

If connecting power to fixed wiring, an all-pole disconnection device which has at least 3mm
clearances in all poles, and have a leakage current that may exceed 10mA, the residual current
device(RCD) having a rated residual operating current not exceeding 30mA, and disconnection
must be incorporated in the fixed wiring in accordance with the wiring rules.

For all electrical work, follow all local and national wiring standards, regulations, and the 

Installation Manual.  Connect cables tightly, and clamp them securely to prevent external forces 
from damaging the terminal. Improper electrical connections can overheat and cause fire, and may 
also cause shock. All electrical connections must be made according to the Electrical Connection 

Diagram located on the panels of the indoor and outdoor units. 
All wiring must be properly arranged to ensure that the control board cover can close properly. If 
the control board cover is not closed properly, it can lead to corrosion and cause the connection
points on the terminal to heat up, catch fire, or cause electrical shock. 

The product must be properly grounded at the time of installation, or electrical shock may occur. 

TAKE NOTE OF FUSE SPECIFICATIONS

The air conditioner’s circuit board (PCB) is designed with a fuse to provide overcurrent protection. 
The specifications of the fuse are printed on the circuit board ,such as : 

T3.15AL/250VAC, T5AL/250VAC, T3.15A/250VAC, T5A/250VAC, T20A/250VAC, T30A/250VAC,etc.

NOTE: 

For the units using R32 or R290 refrigerant , only the blast-proof ceramic fuse can be used.

Содержание GEO KGE-12GRGI

Страница 1: ...before installing or operating your new air conditioning unit Make sure to save this manual for future reference Please check the applicable models technical data F GAS if any and manufacturer informa...

Страница 2: ...Owner s Manual Table of Contents Safety Precautions 03 Care and Maintenance 12 Troubleshooting 14 1 Indoor unit display 07 2 Operating temperature 09 3 Other features 10 4 Setting angle of airflow 11...

Страница 3: ...Mount indoor unit 25 Outdoor Unit Installation 26 1 Select installation location 26 2 Install drain joint 27 3 Anchor outdoor unit 27 4 Connect signal and power cables 29 Refrigerant Piping Connectio...

Страница 4: ...g smell immediately turn off the unit and disconnect the power Call your dealer for instructions to avoid electric shock fire or injury Do not insert fingers rods or other objects into the air inlet o...

Страница 5: ...rd to power the unit Do not share the electrical outlet with other appliances Improper or insufficient power supply can cause fire or electrical shock If connecting power to fixed wiring an all pole d...

Страница 6: ...install the appliance to its support please read the information for details in indoor unit installation and outdoor unit installation sections For units that have an auxiliary electric heater do not...

Страница 7: ...cal equipment should not be mixed with general household waste 2 2 2 2 2 2 When flammable refrigerant are employed appliance shall be stored in a well ventilated area where the room size corresponds t...

Страница 8: ...e unit is OFF remains on when TIMER ON is set FRESH SWING TURBO SILENCE or SOLAR PV ECO feature is turned on for 3 seconds when TIMER OFF is set FRESH SWING TURBO SILENCE or SOLAR PV ECO feature is tu...

Страница 9: ...OFF is set FRESH SWING TURBO or SILENCE features is turned off when defrosting for cooling heating units when unit is self cleaning some units when fresh feature is turned on some units when ECO feat...

Страница 10: ...2 F 15 C 30 C 5 F 86 F 0 C 50 C 32 F 122 F 0 C 52 C 32 F 126 F For special tropical models 0 C 52 C 32 F 126 F For special tropical models 15 C 50 C 5 F 122 F For models with low temp cooling systems...

Страница 11: ...settings to stay comfortable This function can only be activated via remote control And the Sleep function is not available in FAN or DRY mode Press the SLEEP button when you are ready to go to sleep...

Страница 12: ...ers in or near the blower and suction side of the unit The high speed fan inside the unit may cause injury Fig B Fig A Setting Angle of Air Flow Setting horizontal angle of air flow To operate your un...

Страница 13: ...be bad for your health Make sure to clean the filter once every two weeks 1 Lift the front panel of the indoor unit 2 Grip the tab on the end of the filter lift it up then pull it towards yourself 3...

Страница 14: ...If you plan not to use your air conditioner for an extended period of time do the following Clean all filters Turn on FAN function until unit dries out completely Turn off the unit and disconnect the...

Страница 15: ...Troubleshooting Troubleshooting The unit changes from COOL HEAT mode to FAN mode The indoor unit makes noises A rushing air sound may occur when the louver resets its position A squeaking sound may o...

Страница 16: ...customer service center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting Troubleshooting When troubles occur please check the following po...

Страница 17: ...oor heating performance The outdoor temperature is extremely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use...

Страница 18: ...Shape Quantity PC Need to be installed on the back of main air filter by the authorized technician while installing the machine Mounting plate fixing screw Remote controller Fixing screw for remote co...

Страница 19: ...g Plate Determine Wall Hole Position 1 2 3 Drill Wall Hole 4 12cm 4 75in 2 3m 90 55in 12cm 4 75in 15cm 5 9in Mount Indoor Unit STEP 8 Wrap Piping and Cable not applicable for some locations in North A...

Страница 20: ...requirement of local and national standards The installation may be slightly different in different areas Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Controller...

Страница 21: ...irect sunlight NOTE ABOUT WALL HOLE If there is no fixed refrigerant piping While choosing a location be aware that you should leave ample room for a wall hole see Drill wall hole for connective pipin...

Страница 22: ...e sure to avoid wires plumbing and other sensitive components Type A Type B 101mm 4in 179mm 7 05in 136mm 5 35in 37mm 1 45in 290mm 11 4in 49mm 1 95in Right rear wall hole 65mm 2 5in Indoor unit outline...

Страница 23: ...side Right hand side Left rear Right rear Knock out Panel CAUTION Be extremely careful not to dent or damage the piping while bending them away from the unit Any dents in the piping will affect the u...

Страница 24: ...the compressor or any moving parts within the unit If the unit has an auxiliary electric heater it must be installed at least 1 meter 40in away from any combustible materials To avoid getting an elect...

Страница 25: ...on the back DRAIN HOSE MUST BE ON BOTTOM Make sure that the drain hose is at the bottom of the bundle Putting the drain hose at the top of the bundle can cause the drain pan to overflow which can lea...

Страница 26: ...pressure to the left and right hand sides of the unit The unit should not jiggle or shift 6 Using even pressure push down on the bottom half of the unit Keep pushing down until the unit snaps onto th...

Страница 27: ...wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong wind If the unit is frequently exposed to heavy rain or sn...

Страница 28: ...bber seal see Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain j...

Страница 29: ...Remove the nuts from expansion bolts and place outdoor unit on bolts 6 Put washer on each expansion bolt then replace the nuts 7 Using a wrench tighten each nut until snug WARNING WHEN DRILLING INTO C...

Страница 30: ...amp down tightly 1 Remove the wire cover from the unit by loosening the 3 screws 2 Dismount caps on the conduit panel 3 Temperarily mount the conduit tubes not included on the conduit panel 4 Properly...

Страница 31: ...et substances or gases other than the specified refrigerant enter the unit The presence of other gases or substances will lower the unit s capacity and can cause abnormally high pressure in the refrig...

Страница 32: ...alling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down Step 3 Flare pipe ends Proper flaring is essential to achieve an airtig...

Страница 33: ...0 76 0 78 23 2 23 7 0 91 0 93 18 20 180 200kgf cm 32 39 320 390kgf cm 49 59 490 590kgf cm 57 71 570 710kgf cm 67 101 670 1010kgf cm 9 52 0 375 12 7 0 5 16 0 63 19 0 75 1 Unscrew the cover from the pa...

Страница 34: ...for at least 15 minutes or until the Compound Meter reads 76cmHG 10 Pa 2 3 4 5 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that...

Страница 35: ...0Btu h and 24000Btu h ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Method Additional Refrigerant Standard pipe length Vacuum Pump N A Standard pipe length Vacuum Pump Li...

Страница 36: ...Water Method Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak Leak Detector Method If...

Страница 37: ...ressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double check that all refrigerant pipe conn...

Страница 38: ...ty for system impedance information This appliance MST2ABF 30CR QB9W can be connected only to a supply with system impedance no more than 0 085 In case necessary please consult your supply authority f...

Страница 39: ......

Страница 40: ...cations are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website p...

Отзывы: