background image

4

KWH150-ECO-LC/20210130

Kair Ventilation Ltd | 9-11 High Street | Sidcup | DA14 6EN | www.Kair.co.uk

KWH150-ECO-LC

Installation Manual

5.0 SMOKE / CARBON MONOXIDE ALARM 

AUTOMATIC SHUT DOWN

If the unit is required to switch off in the event of smoke/CO detection, 
alarms are available with separate relay bases from companies such as:

Kidde – www.kiddesafetyeurope.co.uk 
Aico Ltd – www.aico.co.uk

This is a mandatory requirement for all units installed in a 3 Storey 
property.

In the event of conducted RF interference between 80 to 127 MHz 
or transient radiated interference between 80 to 87 MHz, the LED 
display may go blank and fan stop temporarily, then go into reset 
mode (LED flashing with the number of the speed setting) and run 
at high speed. The unit will return to normal after 2 minutes after 
the RF interference has stopped.

POWER 
SUPPLY

FAN 

UNIT

Mains power Smoke/CO  detector

with NO/NC contacts

NO

NC

N

L

N

L

C

230V

Supply

230V

24V

For information only, 
refer to manufacturer’s  
specific  instructions.

Alarm Wiring

6.0 CONTROLS

6.1 Speed Settings

The unit has 6 air flow rate (speed) settings, 1-6. Switches to control 
the speed settings and the display are located on the rear of the fan 
unit. The following table shows the flow rates and their corresponding 
speed settings.

As an example a one bedroom bungalow should be set to speed 1, and 
a large 5 bedroom detached property would require speed 6.

Speed Setting

Airflow Rate (l/s)

0

Standby (0)

1

10

2

20

3

30

4

40

5

50

6

60

6.2 Speed Selection

When power to the unit is switched on the display will show the 
temperature control option for 2 minutes. Once the start-up pattern 
has completed you may now press the “up” or “down” switch to choose 
the flow rate appropriate to the property you are installing the unit in.

KWH150-ECO-LC Control

UP

DOWN

6.3 Temperature Control Selection

When delivered, the unit is set to temperature setting 1 as a default. 
To change this setting, switch the power to the unit on. The display on 
the rear of the fan unit will show the temperature control option for 
2 minutes and the unit will being running at speed 6. In this time you 
can change the temperature setting by pressing and holding the “up” 
button. The display will show a flashing value of 1 and will increase 
every 4 seconds. Once you have reached the temperature setting you 
require press and release the “down” button to store the setting. The 
fan will now enter into its normal speed setting mode and a speed can 
be selected at this point. 

Temperature  

Control  

Setting

Temperature Control Description

(Default)

At loft temperatures below 19°C the unit will operate on  

“Normal Operation Mode”.

  

At loft temperatures above 18°C but less than 24°C, the 
unit will switch automatically to 

“Intelligent Heat  

Recovery Mode”

At loft temperatures above 23°C the unit will switch itself 
automatically to 

“Standby Mode”.

2

At loft temperatures below 19°C the unit will operate on  

“Normal Operation Mode”

.

At loft temperatures above 18°C but less than 31°C, the 
unit will switch automatically to 

“Intelligent Heat  

Recovery Mode”

At loft temperatures above 30°C the unit will switch itself 
automatically to 

“Standby Mode”

.

3

This option removes the temperature sensing function out 
of the unit.  
The unit will operate continuously in 

“Normal Operation 

Mode” 

depending on the volume control setting selected.

4

At loft temperatures below 16°C the unit will operate on  

“Normal Operation Mode”

.

At loft temperatures above 15°C but less than 28°C, the 
unit will switch automatically to 

“Intelligent Heat  

Recovery Mode”

.

At loft temperatures above 27°C the unit will switch itself 
automatically to 

“Standby Mode”

.

5

At loft temperatures below 19°C the unit will operate on  

“Normal Operation Mode”

At loft temperatures above 27°C or below 5°C the unit will 
switch itself automatically to 

“Standby Mode”.

Notes: 

Speed Setting 1 is not available for Temperature 

Control Option 5. On selecting Temperature Control Option 
5, Speed Setting 1, the unit will operate as Speed Setting 2.

Содержание KWH150-ECO-LC

Страница 1: ...y a person responsible for their safety Children shall not play with the appliance Cleaning and user maintenance shall not be carried out by children 1 1 Hazard Symbols REFER TO INSTRUCTION MANUAL Rea...

Страница 2: ...loft has adequate ventilation There may be occasions where a loft is so well sealed that additional ventilation may have to be provided by the owner occupier Ensure that all water tanks are covered a...

Страница 3: ...plied 1 amp Mains 230V 50Hz 230V AC 6 KWH150 ECO LC Wiring 2 Filter Installation 3 4 Fan Unit Installation 3 4 1 Joist Hung Standard Mounting The standard method of installation is to suspend from a c...

Страница 4: ...1 as a default To change this setting switch the power to the unit on The display on the rear of the fan unit will show the temperature control option for 2 minutes and the unit will being running at...

Страница 5: ...l good practice The product warranty applies to the UK mainland only and in accordance with our Conditions of Sale Where a floor room is more than 4 5m tall the fan unit must be fitted with a 3 storey...

Страница 6: ...6 KWH150 ECO LC 20210130 Kair Ventilation Ltd 9 11 High Street Sidcup DA14 6EN www Kair co uk KWH150 ECO LC Installation Manual NOTES...

Страница 7: ...7 KWH150 ECO LC 20210130 Kair Ventilation Ltd 9 11 High Street Sidcup DA14 6EN www Kair co uk KWH150 ECO LC Installation Manual NOTES...

Страница 8: ...8 KWH150 ECO LC 20210130 Kair Ventilation Ltd 9 11 High Street Sidcup DA14 6EN www Kair co uk KWH150 ECO LC Installation Manual NOTES...

Отзывы: