8.2.16 Setting the time server
If SIGMA CONTROL 2 is connected to the network, you can set the access to an SNTP server
available in the Internet or a local Intranet. SIGMA CONTROL 2 then automatically imports the
date and time settings and ensures continuous synchronisation of the internal clock with the exter‐
nal time server.
Precondition Access level 2 is activated.
IP configuration is set; see chapter 8.2.14.
The time server's IP address is known. Request the required information from your IT department.
1. Open the 5.1.2
<Configuration – General – Time server> menu.
2. Use «Up» or «Down» to select the
IP address line.
6 . 1 b a r
0 8 : 1 5 A M
8 0 ° C
Header
5.1.2 Time server
Menu
active:
☐
Activating/deactivating the time server function
IP address
192.053.103.103
Example address, time server
3. Press «Enter».
The first group of numbers of the
IP address flashes 192.053.103.103.
4. Use «Up» or «Down» to set the first group of numbers of the
IP address.
5. Press the «Right» key.
The second group of numbers of the
IP address flashes 192.053.103.103.
6. Use «Up» or «Down» to set the second, third and fourth group of numbers of the
IP address.
The
IP address is correctly set.
7. Press «Enter».
The setting is applied.
8. Use «Up» or «Down» to select the
active: line.
9. Press «Enter».
The check box
active: will flash.
10. Press the «Up» key.
The check box is activated.
6 . 1 b a r 0 8 : 1 5 A M 8 0 ° C
5.1.2 Time server
Menu
active: ☑
The time server function is activated.
IP address 192.053.103.103
Example address, time server
8
Initial Start-up
8.2
Setting the controller
No.: 9_9450 12 E
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X