8.10.2 Setting the nominal pressure change via timing program
Note the setting sequence:
➤ First, set the timing program.
➤ Then select the operating mode.
Overview
■ Deleting an existing timing program
■ Entering the weekday for the first switching point
■ Enter the time of the first switching point.
■ Set the nominal pressure for the first switching point
pA or pB
■ Set up any further switching points.
■ Select the operating mode
pA/pB Clock : see chapter 8.10.3.3.
User-defined timer program
No.:
Day
Time
Nominal pressure
01
02
03
04
05
06
07
08
09
10
Tab. 67 User-defined timing program for nominal pressure change
When setting a clock programme for the first time, note first the switching times on the "User-
defined clock program" table for example.
In addition to individual weekdays, the controller has the following cycles:
■ Mon-Thu
■ Mon-Fri
■ Mon-Sat
■ Mon-Sun
■ Sat-Thu
Example
■ Base load period: Weekdays from 06:30AM–05:00PM, Fridays 06:30AM–03:00PM
■ Low load period: Midday from 12:00PM–01:00PM and remaining time
The timing program is established with the following switching points (maximum 10 switching
points available):
8
Initial Start-up
8.10 Setting the machine for local mode
No.: 9_9450 12 E
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.0.X