General Informations

The device can be used in electrical panels, laboratories and test devices. With 
the assistance of a current transformer, it measures the AC current passing 
through the system in terms of  Amper unite. When the current exceeds the 
adjusted over current or goes below the adjusted under current values the 
device starts to count for the adjusted delay time and after that it changes 
Re1 or Re2  outputs contact possition. After energizing the device, “dA -c “ 
message appears on it's screen for 2 seconds and then it starts to show the 
current value.
■ The current transformer ratio can be adjusted between 5/5 and 10000/5 using 
the touch buttons on the front panel of the device.
■ Stores the maximum demand value and the peak value on its memory and 
keeps these values even if the energy supply  goes off.
■ When the measured value of the seconder current reaches 5,1 A, “ OvEr” 
message starts to flash on the screen to warn the user that the value of the 
current exceeded the limit values

Fast Buttons: 

While in measurement screen, pressing up button shows the peak value   

Pressing down button shows the maximum demand value                           

Main Menu :

Pressing on the set button leads to the main menu. The menu contains 

o-OP

u-OP

CLr

SEt

 and  

quIt

 in order.

► OP :

Shows the opening counter “ that occures when the adjusted over 
current values being exceeded

► CLr :

Peak and maximum demand values can be cleared in this menu. 
To enter this menu, set button must be pressed. 

cALL

c-OP

c-dp

 

and 

quIt

 submenus are included within this menu.

► cALL :

 

It is used to clear all peak, maximum demand and opening 
counter values by pressing the set button.

► c-OP :

 

It is used only to clear the opening counter value.

           

► c-dp :

  It is used only to clear the peak and the maximum 

demand values.

           

► quIt :

 

To exit the submenus and return back to the main menu.

► Set : 

The menu that parameters can be adjusted in. to enter this menu set 
button must be pressed.  

CtrF

o-SP

u-SP, hYS

od-t

ud-t

Sd-t

r-t

dd-t

o-CO

u-CO

LtCh

tP

, and 

quıt 

submenus are included 

          

within this menu. These parameters   will flash on the screen. In 
order to change any of them set button must be pressed, then the 
screen will stop flashing and using the direction buttons the new 

          

value can be applied. Pressing the set button again would store this 
value.

          

► ctrF :

 Current transformer ratio.

 It can be set between 5 and 

10000. In order to set the value, set button must be pressed then 
using the direction button the aimed value can be set. Pressing set 
again would store the new value.

          

► o-SP :

 Over current value set menu.

 It can be set between the 

maximum current allowed for the current transformer and %10 of 
the that value. For example for 500/5A transformer, it can be set 

          

between 50 and 500A.

          

► u-SP :

 Under current value set menu.

 It can be set between 

the maximum current allowed for the current transformer and %10 
of the that value.

          

► hYS :

 The percentage Hysteresis value.

 It can be adjusted 

between 0,03 and 0,50. When the current exceeds the adjusted 
over current value then an opening occures. Inorder to close the 

          

output contact again, the current must go below the adjusted over 
current value multiplied by the %hYS, otherwise it will keep the 
output open.

          

► od-t :

 Delay time for over current alarm.

 It can be adjusted 

between 1 and 30 seconds. The opening  of current exceeding 
adjusted current limit occures after this delay.

          

► ud-t :

 Delay time for under current alarm.

 It can be adjusted 

between 1 and 30 seconds. The opening of current exceeding 

I(A)

Re

Over

Re

Over

Re

Under

Re

Under

o-CO =0000

u-CO =0000

o-CO=0001

u-CO =0001

Sd-t 

od-t 

r-t 

ud-t 

r-t 

o-SP

u-SP

%hYS

%hYS

Technical Data

Operational Voltage (Un)

: 230Vac

Operating range

: (0,8-1,1) x Un

Frequency

: 50/60 Hz

Power Consumption

: < 4VA

Measurement Sensitivity   

: %1 +1 digit

Current Transformer Ratio

: 5/5..........10000/5 A

Display

: 4 Digits Led Display

Contact Current

: Max. 3A / 240Vac

Protection Class

: IP 20

Terminal Protection Class

: IP 00

Operating Temperature

: - 5 °C .... + 50 °C

Operating Humidity

: %15 ...... %95 

 

 (without condensation)

Installation 

: to the panel tap

Dimentions

: 72x72x80 mm

DAM – C - 

72

®

DIGITAL UNIVERSAL AMPERMETER  (True RMS)
► With Demand
► Over & Under Current Adjustment

adjusted current limit occures after this delay.

          

► Sd-t :

 Start delay time.

 It can be set btween 0 and 60 seconds. It is 

used to prevent any unwanted opening while current is starting from 
0 “ especially for motors that need high current for start up”. 

         

In this period opening wouldn't occure even if the current exceeds 
the adjusted over current value. If this value is set to “0000” the  
device will wait for the delay time d-t and then opens its output.

          

► r-t :

 Return time.

 The time required to turn back from an alarm 

situation. The device waits for that period after the current returns 
below the adjusted value. It can be set between 2 and 10 seconds.

          

► dd-t :

 Demand time.

 The tıme interval in which the demand 

                                     value is calculated. It can be adjusted between 10 to 60
                                     minutes

          

► o-CO :

 

The menu to adjust the over current output contact possition.

           

■ if the value is set to  0000 then the output in normal situation is 
closed contact and in over current alarm situation is open contact.

           

■ if the value is set to  0001 then the output in normal situation is 
open contact and in over current alarm situation is closed contact.

          

 

► u-CO :

 

The menu to adjust the under current output contact 

possition.

           

■ if the value is set to  0000 then the output in normal situation is 
closed contact and in under current alarm situation is open contact.

           

■ if the value is set to  0001 then the output in normal situation is 
open contact and in over current alarm situation is closed contact.

          

► LtCh :

 Latch function.

 The place to choose wether the device will 

go out of an alarm manually or automatically

           

■ if the value is set to 0000 then the latch function is off and the 
device will go out of the alarm automatically

           

■ if the value is set to  0001 then the latch function is on and the 
device wouldn't go out of the alarm unless the user presses the set 
button until the alarm led turns off. If pressed, then device then will 
go out of the alarm after the delay time r-t.

          

► tP :

 

Sudden opening function. If the current goes over %150 of the 

adjusted over current value the the device will open its output 
without any delay.

           

■ if 0000 then the function is disabled .

           

■ if 0001 then the function is enabled. ( not active while start delay 
time (Sd-t)).

           

► quıt :

 

Pressing set leads to the main menu.

► quıt :   

Pressing set leads to the measurement screen.

Button Functions :

To enter the menu set button must be pressed. Within the menu, the 
parameters can e reached using the direction buttons. To inter the desired 
menu set button must be pushed again. This parameters can be adjusted 
using the direction buttons, pressing the set button again stores the new 
parameters.