Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Lock-out time
0 s – 60 s
F
Set the length of time that the active power must remain below the
lock-out power level before control is deactivated.
4
1
2
3
4
Downtime
0-10000 [ms]
If the voltage switches from a characteristic curve section with Q=0 to a
characteristic curve section with Q≠0 under active control, then the re-
active power setting process is delayed by the set dead time. Once the
dead time has expired, the control circuit is no longer subject to a delay
and the set transient time determines the transient behaviour.
4
1
2
3
4
Rise Outg. grad. & Fall.
Outg. grad.
increasing | decreas-
ing
1 %-60000 %/min
F
Maximum change in the reactive power %S
lim
/min in the event of a
change to over-excited mode.
1 %-60000 %/min
F
Maximum change in the reactive power %S
lim
/min in the event of a
change to under-excited mode.
4
1
2
3
4
Min. cos-phi Q1 - Min.
cos-phi Q4
NOTE: In the event of a significant voltage deviation, the maximum re-
active power adjustment range can be limited by a minimum cos φ in
order to prevent an excessive reactive power supply and, as a result, a
significant reduction in the maximum active power that can be fed in.
F
Enter the minimum cos ϕ factor for quadrants 1 and 4.
4
1
2
3
4
Priority mode
Q priority | P priority
F
Set priority for reactive power – Q or active power – P.
NOTE: When it comes to P priority, the reactive power adjustment
range is limited subject to the active power that is currently available
and fed in.
4
1
2
3
4
Active curve
1 - 4
F
Select active curve.
NOTE: Up to 4 characteristic curves can be configured independently
and one of them can be activated for regulation each time.
4
1
2
3
4
Reset the curve
F
Reset active curve to the default setting.
4
1
2
3
4
Number of nodes
2 - 10
NOTE: The maximum number of configurable nodes depends on the
selected grid type.
F
Specify the number of nodes for the Q(U) characteristic curve.
4
1
2
3
Exten. standalone grid
NOTE: Grid operators require shutdown of the device with standalone
grid detection.
F
Further parameterisation is possible via the web interface.
BE CH-NS
CY DE-NS
DK JP-50HZ
JP-60HZ
LU-NS TW
UD
4
1
2
3
Line error
NOTE: Display of grid faults.
F
To show the last 5 grid fault messages, press the
Show button.
4
1
2
3
Advanced features
F
Further parameterisation is possible via the web interface
4
1
2
3
4
Information
Open the menu: Press the right arrow button or the OK button.
4
1
2
3
Inv. type
Displays the type designation of the device. If feed-in power is actively
limited: display maximum power in kW.
4
1
2
3
SW version
Displays the installed software version.
4
1
2
3
Serial number
Displays the serial number of the device.
4
1
2
3
Select country
Displays the selected country setting. Optional: Displays the grid type if
a grid type has been selected.
Powador 30.0-72.0 TL3
Page 46
EN