Reactive power control
Reactive power can be used in electrical energy supply networks to bolster the level of voltage. As such, feed-in inverters
can contribute to statistical voltage stability. Reactive power brings about a voltage drop at the inductive and capacitive
components of the equipment which can either bolster or reduce the level of voltage. If the generating plant draws induc-
tive reactive power while active power is being fed in, part of the voltage swing caused by the active power feed can be
compensated for by the supply of reactive power.
This reactive power mode and the respective control process are specified by the grid operator. If no control process has
been specified, then the plant should be operated using a reactive power specification of 0%.
10.1.1
Operating power range depending on grid voltage
The device can be operated within the respective fixed voltage range provided. The maximum apparent power is stated in
the following table. In the event of undervoltage determined by the maximum continuous current subject to the grid volt-
age.
The following figures show the reactive power operating range subject to active power and the apparent power operating
range subject to the grid voltage for various devices.
KACO
blue-
planet
87.0 TL3
M1 WM
OD IIF0 /
KACO
blue-
planet
87.0 TL3
M1 WM
OD IIFX
Voltage
U
N:
380V
KACO
blue-
planet
92.0 TL3
M1 WM
OD IIG0 /
KACO
blue-
planet
92.0 TL3
M1 WM
OD IIGX
Voltage
U
N:
400V
KACO
blue-
planet
105TL3
M1 WM
OD IIG0 /
KACO
blue-
planet
105TL3
M1 WM
OD IIGX
Voltage
U
N:
400V
KACO
blue-
planet
110 TL3
M1 WM
OD IIK0 /
KACO
blue-
planet
110 TL3
M1 WM
OD IIKX
Voltage
U
N:
270V /
480V
KACO
blue-
planet
125 TL3
M1 WM
OD IIP0 /
KACO
blue-
planet
125 TL3
M1 WM
OD IIPX
Voltage
U
N:
600V
KACO
blue-
planet
125TL3
M1 WM
OD IIK0 /
KACO
blue-
planet
125TL3
M1 WM
OD IIKX
Voltage
U
N:
480V
KACO
blue-
planet
137 TL3
M1 WM
OD IIP0 /
KACO
blue-
planet
137 TL3
M1 WM
OD IIPX
Voltage
U
N:
600V
KACO
blue-
planet
150 TL3
M1 WM
OD IIQ0 /
KACO
blue-
planet
150 TL3
M1 WM
OD IIQX
Voltage
U
N:
660V
KACO
blue-
planet
155TL3
M1 WM
OD IIP0 /
KACO
blue-
planet
155TL3
M1 WM
OD IIPX
Voltage
U
N:
590V
KACO
blue-
planet
165TL3
M1 WM
OD IIQ0 /
KACO
blue-
planet
165TL3
M1 WM
OD IIQX
Voltage
U
N:
630V
Maximum
apparent
power [p.u.]
-
-
-
-
≥ 600
≥ 475
-
-
-
-
1,10
≥ 380
≥ 400
≥ 380
≥ 480
545
475
≥ 600
≥ 660
≥ 590
≥ 630
1,00
361
380
361
456
520
450
570
622
560
595
0,95
342
360
342
432
492
430
540
590
530
564
0,90
Tab. 8:
Maximum continuous apparent power depending on grid voltage
1
P [p.u.]
Q [P.u]
0,6
0,4
0,2
0
1
0,8
1,2
0,6
0,6
1
0,0
U
N
660V
above 630V
at 595V
at 565V
Fig. 63:
P-Q operating range for bp 165TL3 (Qmax=Smax)
760
S [p.u. S
nom
]
U [V]
0,6
0,4
0,2
0
1
0,8
1,2
560
680
520
480
600
640
720
Nominal capability
U
V
R
T
Under voltage
derating
O
V
R
T
Fig. 64:
Apparent power subject to the grid voltage for
bp165TL3