K SYSTEMS CORPORATION TANK INVENTORY SYSTEM
The third column displays the alarm status of each tank, (HI-MID-LO). When the product amount is below
the low setpoint the status display will be LO, and a 115 VAC low alarm output will be generated. When the
amount is above LO and below MID, the display will be blank and no alarm output will be generated. When
the middle setpoint is exceeded, MID will be displayed and the middle alarm output will come on. When the
amount exceeds the high setpoint, HI will be displayed and both medium and high alarm outputs will be
generated. The level setpoint values may be changed as outlined in the User Programming Section.
The fourth column displays product specific gravity. The operator sets these values to the specific gravity of
the product in each tank (See USER PROGRAMMING Section). If no value has been set, the control will
default to 1.000.
CAUTION
: Product name has no bearing on the calculation of content. When product
name is changed be sure to check that the specific gravity has the correct value for the new product name.
(See note under specific gravity in user programming section).
The last column displays level percentage. The number shown is the product level percentage of maximum
level. The bar graph displays this percentage graphically.
NOTE
: The following parimeters may be changed in the field by authorized personel -
TIME OF DAY
DISPLAY UNITS
LEVEL ALARM SET POINTS
SPECIFIC GRAVITIES
PRODUCT NAMES
_______________________________________________________________________________________
K Systems