Read and understand these instructions before installing fixture.

This fixture is intended for installation in accordance with the National Electrical Code and local regulations. To 

assure full compliance with local codes and regulations, check with your local electrical inspector before installation. 

To prevent electrical shock, turn off electricity at main circuit breaker panel before proceeding.

SAVE THESE INSTRUCTIONS

Current Limiting End Feed/In-Line 

Feed Connector TCLF11 and 

TCLF21 for use with Trac-Master 

Single-Circuit Trac only. Current 

Limiter will limit the wattage on 

a circuit and can be used as a 
standard ON/OFF switch.

Current limiting feed can be fed using a 

4” octagon junction box, fed directly using 

flexible or rigid conduit with 3/8” or 1/2” 

electrical connector from standard ceilings 

or grid ceiling runner systems, or fed using 

Trac Pendant Mounting Kits.

1300 South Wolf Road • Des Plaines, IL 60018 • Phone 800-323-5068 • www.junolightinggroup.com

© 2009 Juno Lighting LLC    Printed in USA    Rev 5/09    P2434    pg 1 of 2

Trac-Master Single-Circuit Current Limiting End Feed/In-Line Feed Connector 

NOTE:

1.   Turn off power at breaker box before    

 

installing electrical connector and trac.

2.   If feeding with electrical connectors do  

 

not use feed connector as a conduit    

 

support. Independent conduit supports  

 

must be used to attach the conduit to the  

 

building structure.

3.   Observe polarity; white neutral wire must  

 

be connected to the terminal marked “N” in  

 

the feed connector.

4.   Use 12 gauge or 14 gauge solid wire in  

 

feed connector only. Feed connector rating  

 

120V, 20Amp max., 60Hz.

5.   Use the proper rated Juno current limiting  

 

circuit breaker (TCL Series) to limit the  

 

load on the circuit (current limiting circuit  

 

breaker sold separately).

6.   Feed connector is polarized and will only  

 

install into one end of the trac. Align  

 

polarity arrow on feed connector toward  

 

trac polarity line for proper installation.  

 

See Figure 1.

7.   Do not position luminaire such that it    

 

touches the feed connector.

Note: This Current Limiting Trac Feed 

Connector conforms to ASHRAE 90.1  

Section 9.1.4(c) and is certified to California 

Energy Commission T24-2008, Section  

119(L) of the California Energy Code.

INSTALLING CURRENT LIMITING 
FEED CONNECTOR ON A J-BOX

The centerline of the trac must be on the 

center of the J-Box and the mounting holes 

for the J-Box must be at a 45º angle to the 

centerline of the trac. 

1.  Remove the COVER and retain.

2.  Remove the RECTANGULAR KNOCK  

 

OUT from the PLATE. Do not remove any  

 

other knock outs.

3.  Push CURRENT LIMITING CIRCUIT   

 

BREAKER(S) into PLATE. 

4.  Fasten PLATE to J-Box passing supply  

 

wires through RECTANGULAR HOLE.  

 

Secure PLATE by passing (2) Mounting  

 

screws (not supplied) through PLATE and  

 

into J-BOX.

5.  Attach wires per WIRING INSTRUCTIONS 

 

on page 2.

6.  Slide TRAC onto FEED CONNECTOR;  

 

ensure (2) CONTACT BLADES

   insert into the gap of the trac BUS BARS. 

7.   Tighten FEED CONNECTOR ONE-WAY 

LOCKING SCREW(S) for permanent 

mounting to the trac (in accordance with 

CEC-T24-2008.)

8.   Apply VA label provided loose with circuit 

breaker packaging onto the mounting 

plate according to each trac VA rating (in 

accordance with CEC-T24-2008.) 

9.  Fasten COVER taking caution to avoid  

 

pinching any wires. 

See OPERATING INSTRUCTIONS on page 2.

INSTALLING CURRENT LIMITING 

FEED CONNECTOR USING 

FLEXIBLE OR RIGID CONDUIT

1.  Remove the COVER and retain.

2.  Mark centerline of PLATE on ceiling to  

 

determine the mounting location of the  

 

FEED CONNECTOR.

3.  Make a hole in the ceiling for the electrical  

 

connector in the position that coincides  

 

with one of the ROUND KNOCK OUTS. 

4.  Remove one ROUND KNOCK OUT    

 

where the power is to be passed through.  

 

Do not remove any other knock outs.

5.  Push CURRENT LIMITING CIRCUIT   

 

BREAKER(S) into PLATE. 

6.  Attach electrical connector (by others) to  

 

PLATE in round hole. 

7.  Pass supply wires through hole in ceiling  

 

and through electrical connector.

8.  Mount PLATE to ceiling using (2) of the  

 

PLATE MOUNTING HOLES that are not  

 

located on a knock out. Mounting  

 

 

hardware not supplied.

9.  Attach wires per WIRING    

 

 

INSTRUCTIONS on page 2.

10.  Slide TRAC onto FEED CONNECTOR;  

 

ensure (2) CONTACT BLADES insert

    into the gap of the trac BUS BARS.

11.  Tighten FEED CONNECTOR LOCKING  

 

SCREW(S).

12. Fasten COVER taking caution to avoid  

 

pinching any wires.

See OPERATING INSTRUCTIONS on page 2.

Figure 1

INSTALLATION INSTRUCTIONS

For TCLF11 and TCLF21