Four-Post Installation Procedure for QFX5220-128C
To mount the QFX5220-128C on a four-post rack using the provided rack mount kit:
1. Attach the ESD grounding strap to your bare wrist and to a site ESD point.
2. Decide whether the field replaceable unit (FRU) end of the switch or the port end is to be placed at
the front of the rack. Position the device in such a manner that the AIR IN labels on components are
next to the cold aisle and AIR OUT labels on components are next to the hot aisle.
3. Align the holes in the flange with the holes closest to the port panel. See
.
Figure 31: Attaching the Flange to the QFX5220-128C Chassis
QFX5220-128C
g051182
4. Use the Phillips number 2 screwdriver to attach the flange to the chassis using two M4 x 6 mm flathead
screws in the top and bottom holes. Tighten the screws.
5. Repeat Step
and Step
and attach the second flange to the opposite side of the chassis.
6. Align the holes in the left mounting rail with the holes on the side of the chassis and in the flange. See
to see the proper alignment for the QFX5220-128C.
NOTE:
There is a left mounting rail, stamped LEFT, and a right mounting rail, stamped RIGHT.
The mounting rails are not interchangable.
118
Содержание QFX5220
Страница 1: ...QFX5220 Switch Hardware Guide Published 2019 11 07 ...
Страница 18: ......
Страница 77: ......
Страница 107: ......
Страница 148: ......
Страница 172: ...5 CHAPTER Troubleshooting Hardware Troubleshooting the QFX5220 179 ...
Страница 173: ......
Страница 182: ......
Страница 206: ...Restricted Access Warning 213 ...
Страница 221: ...Jewelry Removal Warning 228 ...
Страница 224: ...Operating Temperature Warning 231 ...
Страница 234: ...DC Power Disconnection Warning 241 ...
Страница 238: ...DC Power Wiring Sequence Warning 245 ...
Страница 241: ...DC Power Wiring Terminations Warning 248 ...