MX2010 Rack Requirements
IN THIS SECTION
Spacing of Mounting Bracket and Flange Holes | 137
Connection to the Building Structure | 138
Rack Size and Strength
The MX2010 router is designed for installation in a rack that complies with either of the following standards:
•
A 19-in. rack as defined in Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310-D)
published by the Electronics Components Industry Association (
).
•
A 600-mm rack as defined in the four-part Equipment Engineering (EE); European telecommunications
standard for equipment practice (document numbers ETS 300 119-1 through 119-4) published by the
European Telecommunications Standards Institute (ETSI). The horizontal spacing between the rails in a
rack that complies with this standard is usually wider than the mounting brackets, which measure
19.2 in. (48.8 cm) from the outer edge to outer edge. Use approved wing devices to narrow the opening
between the rails as required.
•
A 23-in. rack using appropriate 23-in. to 19-in. rack adapters and an appropriate installation shelf that
supports the chassis at the correct vertical position to properly line up the rack mount holes. Juniper
Networks does not supply this hardware, but consideration for the size and weight of the chassis is
important for a safe installation.
The rack rails must be spaced widely enough to accommodate the chassis’s external dimensions:
59.50 in. (151.1 cm) high, 36.20 in. (91.95 cm) deep, and 19 in. (48.3 cm) wide. The outer edges of the
front-mounting flanges extend the width to 19.2 in. (48.8 cm), The spacing of rails and adjacent racks must
also allow for the clearances around the chassis and rack that are specified in
for Airflow and Hardware Maintenance for the MX2010 Router” on page 147
. The cable manager and EMI
135
Содержание MX2010
Страница 1: ...MX2010 Universal Routing Platform Hardware Guide Published 2019 12 03...
Страница 28: ......
Страница 30: ...MX2010 Power System Description 95 MX2010 Cooling System Description 45 4...
Страница 54: ...MX2010 Router Overview 3 MX Series Router Interface Names MX2010 Port and Interface Numbering 90 28...
Страница 144: ...MX2010 DC Power 48 V System Electrical Specifications 201 122...
Страница 146: ......
Страница 233: ......
Страница 258: ...Figure 85 Removing an AC Power Distribution Module Before Installing the MX2010 Router D g007439 241...
Страница 259: ...Figure 86 Removing a DC Power Distribution Module 48 V Before Installing the MX2010 Router D g007431 242...
Страница 273: ...Figure 98 Loading the MX2010 Router into the Rack g007436 256...
Страница 294: ...Figure 113 Reinstalling an AC Power Distribution Module g007440 D 277...
Страница 295: ...Figure 114 Reinstalling a DC Power Distribution Module 48 V D g007432 278...
Страница 373: ...4 PART Installing and Replacing Components Installing Components 359 Replacing Components 429...
Страница 374: ......
Страница 620: ......
Страница 715: ...6 PART Troubleshooting Hardware Troubleshooting Components 703...
Страница 716: ......
Страница 744: ......
Страница 767: ...Remove the shipping brackets and hardware and set them aside Guide the router in the shipping crate 754...
Страница 772: ......
Страница 775: ...763...
Страница 783: ...772...
Страница 796: ...Jewelry Removal Warning 787...
Страница 799: ...Operating Temperature Warning 790...
Страница 808: ...DC Power Disconnection Warning 799...
Страница 812: ...DC Power Wiring Sequence Warning 803...
Страница 815: ...DC Power Wiring Terminations Warning 806...