CAUTION:
It is particularly important to provide a properly grounded and shielded
environment and to use electrical surge-suppression devices.
Table 29: Site Electrical Wiring Guidelines
Guideline
Site Wiring Factor
To ensure that signaling functions optimally:
•
Install wires correctly.
Improperly installed wires can emit radio interference.
•
Do not exceed the recommended distances or pass wires between buildings.
The potential for damage from lightning strikes increases if wires exceed recommended
distances or if wires pass between buildings.
•
Shield all conductors.
The electromagnetic pulse (EMP) caused by lightning can damage unshielded
conductors and destroy electronic devices.
Signaling limitations
To reduce or eliminate the emission of RFI from your site wiring:
•
Use twisted-pair cable with a good distribution of grounding conductors.
•
Use a high-quality twisted-pair cable with one ground conductor for each data signal
when applicable, if you must exceed the recommended distances.
Radio frequency
interference (RFI)
Provide a properly grounded and shielded environment and use electrical
surge-suppression devices.
Strong sources of electromagnetic interference (EMI) can cause the following damage:
•
Destruction of the signal drivers and receivers in the device.
•
Electrical hazards as a result of power surges conducted over the lines into the
equipment.
TIP:
If your site is susceptible to problems with EMC, particularly from lightning or radio
transmitters, you might want to seek expert advice.
Electromagnetic
compatibility (EMC)
95
Содержание MX10008
Страница 1: ...MX10008 Universal Routing Platform Hardware Guide Published 2019 11 11 ...
Страница 19: ......
Страница 89: ......
Страница 129: ......
Страница 170: ......
Страница 179: ...Figure 76 Removing Fan Tray JNP10008 FAN from an MX10008 FAN FTC SIB STATUS FAN FTC SIB STATUS 181 ...
Страница 183: ...Figure 79 Installing Fan Tray JNP10008 FAN in an MX10008 FAN FTC SIB STATUS FAN FTC SIB STATUS 185 ...
Страница 278: ...5 CHAPTER Troubleshooting Hardware Restoring Junos OS 283 Alarm Messages 287 ...
Страница 279: ......
Страница 287: ......
Страница 318: ...Restricted Access Warning 321 ...
Страница 333: ...Jewelry Removal Warning 336 ...
Страница 336: ...Operating Temperature Warning 339 ...
Страница 345: ...DC Power Disconnection Warning 348 ...
Страница 349: ...DC Power Wiring Sequence Warning 352 ...
Страница 352: ...DC Power Wiring Terminations Warning 355 ...
Страница 361: ...Translation The emitted sound pressure is below 92 dB A per GR63 CORE 364 ...