This topic describes these tasks:
1.
Calculating the Power Consumption of Your MX10008 Configuration | 101
2.
Calculating the Number of Power Supplies Required for Your MX10008 Configuration | 102
Calculating the Power Consumption of Your MX10008 Configuration
Use the following procedure to determine the maximum power you need to supply to the router. To
calculate maximum system power consumption, you first determine the combined maximum internal power
requirements of all the router components and then divide this result by the power supply output power.
To calculate maximum system power consumption:
1. Determine the maximum power consumption of the base chassis components (that is, the components
other than the line cards). Use
if your router is configured as either the standard
base or redundant configuration.
Table 31: Chassis Power Consumption for Standard Configurations
Redundant Configuration
Base Configuration
Chassis Component
1100 W
1100 W
Fan tray, JNP10008-FAN
1212 W
1212 W
Fan tray, JNP10008-FAN2
350 W/330 W
175 W/165 W
Routing and Control board (128G/64G) @40°
C
1200 W
1000 W
Switch fabric board (SFB)
2. Calculate the maximum internal power consumption of the entire router by adding in the power
requirements of each line card. See
for a chart of the power needed for line cards.
Table 32: Line Card Power Consumption
MX10K-LC2101 (400 Gigabit
Ethernet mode @104° F (40°
C))
MX10K-LC2101 (240 Gigabit
Ethernet mode @104° F (40°
C))
Number of Line Cards
1425 W
1175 W
1
2850 W
2350 W
2
4275 W
3525 W
3
101
Содержание MX10008
Страница 1: ...MX10008 Universal Routing Platform Hardware Guide Published 2019 11 11 ...
Страница 19: ......
Страница 89: ......
Страница 129: ......
Страница 170: ......
Страница 179: ...Figure 76 Removing Fan Tray JNP10008 FAN from an MX10008 FAN FTC SIB STATUS FAN FTC SIB STATUS 181 ...
Страница 183: ...Figure 79 Installing Fan Tray JNP10008 FAN in an MX10008 FAN FTC SIB STATUS FAN FTC SIB STATUS 185 ...
Страница 278: ...5 CHAPTER Troubleshooting Hardware Restoring Junos OS 283 Alarm Messages 287 ...
Страница 279: ......
Страница 287: ......
Страница 318: ...Restricted Access Warning 321 ...
Страница 333: ...Jewelry Removal Warning 336 ...
Страница 336: ...Operating Temperature Warning 339 ...
Страница 345: ...DC Power Disconnection Warning 348 ...
Страница 349: ...DC Power Wiring Sequence Warning 352 ...
Страница 352: ...DC Power Wiring Terminations Warning 355 ...
Страница 361: ...Translation The emitted sound pressure is below 92 dB A per GR63 CORE 364 ...