Parts and Tools Required for Connecting an EX Series Switch to Earth Ground
Before you begin connecting an EX Series switch to earth ground, ensure you have the parts and tools
required for your switch.
lists the earthing terminal location, grounding cable and lug specifications, and
parts needed for connecting an EX Series switch to earth ground.
Table 33: Parts Required for Connecting an EX Series Switch to Earth Ground
Switch
Earthing
Terminal
Location
Grounding
Cable
Requirements
Grounding Lug
Specifications
Screws and
Washers
Additional
Information
EX2200
Rear panel of
the chassis
14 AWG
(2 mm²),
minimum 90° C
wire, or as
permitted by
the local code
Panduit
LCC10-14BWL or
equivalent—
not provided
•
Two
10-32 x .25 i
n. screws
with #10
split-lock
washer—
not provided
•
Two #10 flat
washers—
not provided
EX2300-C
Rear panel of
the chassis
14 AWG
(2 mm²),
minimum 90° C
wire, or as
permitted by
the local code
Panduit
LCC10-14AW-L or
equivalent—
not provided
•
Two
10-32 x .25 i
n. screws
with #10
split-lock
washer—
not provided
•
Two #10 flat
washers—
not provided
83