To ensure proper operation and to meet safety and electromagnetic interference (EMI) requirements, you
must connect an EX Series switch to earth ground before you connect power to the switch. You must use
the protective earthing terminal on the switch chassis to connect the switch to earth ground (see
).
You must install the EX Series switch in a restricted–access location and ensure that the chassis is always
properly grounded. EX Series switches have a two–hole protective grounding terminal provided on the
chassis. See
for the location of the earthing terminals on various EX Series switches.
We recommend that you use the protective grounding terminal as the preferred method for grounding
the chassis regardless of the power supply configuration. However, if additional grounding methods are
available, you can also use those methods. For example, you can use the grounding wire in the power cord
of an AC power supply or use the grounding terminal or lug on a DC power supply. This system was tested
to meet or exceed all applicable EMC regulatory requirements with the two-hole protective grounding
terminal connected correctly.
Ensure that a licensed electrician has attached an appropriate grounding lug to the grounding cable you
supply. Using a grounding cable with an incorrectly attached lug can damage the switch.
Parts and Tools Required for Connecting an EX Series Switch to Earth Ground
Before you begin connecting an EX Series switch to earth ground, ensure you have the parts and tools
required for your switch.
lists the earthing terminal location, grounding cable and lug specifications, and parts
needed for connecting an EX Series switch to earth ground.
Table 43: Parts Required for Connecting an EX Series Switch to Earth Ground
Additional
Information
Screws and
Washers
Grounding Lug
Specifications
Grounding
Cable
Requirements
Earthing
Terminal
Location
Switch
•
Two
10-32 x .25 in.
screws with
#10 split-lock
washer—
not provided
•
Two #10 flat
washers—not
provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 AWG (2 mm²),
minimum 90° C
wire, or as
permitted by the
local code
Rear panel of
the chassis
EX2200
122
Содержание EX4500 Series
Страница 1: ...EX4500 Switch Hardware Guide Published 2020 12 15...
Страница 19: ...1 CHAPTER Overview EX4500 System Overview 20 EX4500 Chassis 35 EX4500 Cooling System 54 EX4500 Power System 58...
Страница 42: ...Table 6 LCD Panel Menu Options in EX4500 Switches continued Description Menu MAINT Maintenance Menu 42...
Страница 164: ...Table 47 System Information continued Description Field Inventory details 164...
Страница 240: ...5 CHAPTER Troubleshooting Hardware Troubleshooting EX4500 Components 241...
Страница 273: ...273...
Страница 280: ...Restricted Access Warning 280...
Страница 284: ...284...
Страница 297: ...Jewelry Removal Warning 297...
Страница 300: ...Operating Temperature Warning 300...
Страница 310: ...DC Power Disconnection Warning 310...
Страница 314: ...DC Power Wiring Sequence Warning 314...
Страница 317: ...DC Power Wiring Terminations Warning 317...