Connecting Earth Ground to an EX Series Switch
To ensure proper operation and to meet safety and electromagnetic interference (EMI)
requirements, you must connect an EX Series switch to earth ground before you connect
power to the switch. You must use the protective earthing terminal on the switch chassis
to connect the switch to earth ground (see
).
NOTE:
A ground connection to the protective earthing terminal is not required
for an AC-powered switch. The AC power cords provide adequate grounding
when you connect the power supply in the switch to a grounded AC power
outlet by using the AC power cord appropriate for your geographical location.
WARNING:
The switch is installed in a restricted-access location.
CAUTION:
If external ground connection is required, ensure that a licensed
electrician has attached an appropriate grounding lug to the grounding cable
that you supply. Using a grounding cable with an incorrectly attached lug can
damage the switch.
•
Parts and Tools Required for Connecting an EX Series Switch to Earth
Ground on page 93
•
Special Instructions to Follow Before Connecting Earth Ground to a Switch on page 97
•
Connecting Earth Ground to an EX Series Switch on page 99
Parts and Tools Required for Connecting an EX Series Switch to Earth Ground
lists the earthing terminal location, grounding cable requirements,
grounding lug specifications, screws and washers required, and the screwdriver needed
for connecting a switch to earth ground. Before you begin connecting a switch to earth
ground, ensure you have the parts and tools required for your switch.
Table 33: Parts and Tools Required for Connecting an EX Series Switch to Earth Ground
Additional
Information
Screwdriver
Screws and
Washers
Grounding Lug
Specifications
Grounding Cable
Requirements
Earthing
Terminal
Location
Switch
Phillips (+)
number 2
•
Two 10-32
x .25 in. screws
with #10
split-lock
washer—
not provided
•
Two #10 flat
washers—not
provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 AWG (2 mm²),
minimum 90° C wire,
or as permitted by the
local code
Rear panel
of the
chassis
EX2200
93
Copyright © 2018, Juniper Networks, Inc.
Chapter 3: Initial Installation and Configuration
Содержание EX2200 Series
Страница 1: ...EX2200 and EX2200 C Switches Hardware Guide Modified 2018 12 18 Copyright 2018 Juniper Networks Inc...
Страница 8: ...Copyright 2018 Juniper Networks Inc viii EX2200 and EX2200 C Switches Hardware Guide...
Страница 12: ...Copyright 2018 Juniper Networks Inc xii EX2200 and EX2200 C Switches Hardware Guide...
Страница 20: ...Copyright 2018 Juniper Networks Inc xx EX2200 and EX2200 C Switches Hardware Guide...
Страница 40: ...Copyright 2018 Juniper Networks Inc 40 EX2200 and EX2200 C Switches Hardware Guide...
Страница 66: ...Copyright 2018 Juniper Networks Inc 66 EX2200 and EX2200 C Switches Hardware Guide...
Страница 150: ...Copyright 2018 Juniper Networks Inc 150 EX2200 and EX2200 C Switches Hardware Guide...
Страница 168: ...Copyright 2018 Juniper Networks Inc 168 EX2200 and EX2200 C Switches Hardware Guide...
Страница 174: ...Copyright 2018 Juniper Networks Inc 174 EX2200 and EX2200 C Switches Hardware Guide...
Страница 214: ...Copyright 2018 Juniper Networks Inc 214 EX2200 and EX2200 C Switches Hardware Guide...