Rack Requirements for ACX500 Indoor Routers
You can mount the indoor router on two-post racks or four-post racks.
Rack requirements consist of:
• Rack type
• Mounting bracket hole spacing
• Rack size and strength
• Rack connection to the building structure
provides the rack requirements and specifications for the router.
Table 26: Rack Requirements and Specifications for the ACX500 Indoor Router
Rack Requirement
Guidelines
Rack type
Use a two-post rack or a four-post rack. You can mount the router on any two-post or four-
post rack that provides bracket holes or hole patterns spaced at 1 U (1.75 in., or 4.45 cm)
increments and that meets the size and strength requirements to support the weight.
A U is the standard rack unit defined in
Cabinets, Racks, Panels, and Associated Equipment
(document number EIA-310–D) published by the Electronics Industry Association (
The rack must meet the strength requirements to support the weight of the chassis.
Mounting bracket
hole spacing
The holes in the mounting brackets are spaced at 1 U (1.75 in., or 4.45 cm) so that the
router can be mounted in any rack that provides holes spaced at that distance.
99