Power loss 

5 W 

Connected load at 25 °C see reference list (figure 5)(figure 6) 

Power specifications including transformer power dissipation. 

Operate inductive transformers with at least 85% nominal load. 

For ohmic-inductive mixed load, maximum 50% proportion of ohmic load. Otherwise 
incorrect calibration of the dimmer may result. 

capacitive-inductive 

not permitted 

Minimum connected load 

200 W/VA 

Power reduction 
per 5°C in excess of 45°C 

-15 % 

Connection 
single stranded 

max. 4 mm² 

finely stranded with conductor sleeve 

0.5 ... 2.5 mm² 

finely stranded without conductor sleeve 

0.75 ... 4 mm² 

Number of power boosters 

see reference list 

Total length power cable 

max. 100 m 

Fitting width 

36 mm / 2 modules 

Figure 5: Reference list of conventional and radio dimmers 

5/7 

82557263 
J:0082557263 

27.02.2013 

Light Management  

Universal amplifier for rail mounting 200-500 W 

Содержание ULZ 1215 REG

Страница 1: ...re hazard For operation with inductive transformers each transformer must be fused on the primary side in accordance with the manufacturer s instructions Only safety transformers according to EN 61558 2 6 may be used A minimum power of 10 kVA is required for operation on isolating transformer networks Otherwise it is not ensured that the dimmer will correctly recognise the dimming principle suitab...

Страница 2: ... represent any defect in the device i Brightness differences between the lighting on a dimmer without powerpower booster and a dimmer with power booster are possible 4 Information for electrically skilled persons 4 1 Fitting and electrical connection DANGER Electrical shock when live parts are touched Electrical shocks can be fatal Before carrying out work on the device or load disengage all the c...

Страница 3: ...Figure 2 Connection diagram with RMD dimmer Figure 3 Connection diagram with FM dimmer 3 7 82557263 J 0082557263 27 02 2013 Light Management Universal amplifier for rail mounting 200 500 W ...

Страница 4: ...r boosters figure 4 o If multiple circuit breakers supply dangerous voltages to the device or load couple the circuit breakers to ensure tripping Calculation example for the number of power boosters required PL Load to be dimmed e g 2200 W PD Max dimmer load e g 500 W PLZ Max universal power extension load e g B 500 W PLZG Power that the power boosters have to provide n Number of power boosters re...

Страница 5: ...esult capacitive inductive not permitted Minimum connected load 200 W VA Power reduction per 5 C in excess of 45 C 15 Connection single stranded max 4 mm finely stranded with conductor sleeve 0 5 2 5 mm finely stranded without conductor sleeve 0 75 4 mm Number of power boosters see reference list Total length power cable max 100 m Fitting width 36 mm 2 modules Figure 5 Reference list of convention...

Страница 6: ...om mains switch off circuit breakers Let system cool down for approx 15 minutes Check the installation situation Reduce the connected load Switch circuit breakers and system on again i Load is initially distributed to the remaining devices The further behaviour of the system depends on the dimmer used and the number utilisation and installation situation of the devices 5 3 Warranty We reserve the ...

Страница 7: ...chalksmühle Telefon 49 23 55 8 06 0 Telefax 49 23 55 8 06 2 04 kundencenter jung de www jung de Service Center Kupferstr 17 19 44532 Lünen Germany 7 7 82557263 J 0082557263 27 02 2013 Light Management Universal amplifier for rail mounting 200 500 W ...