Light Management
Tronic Transformers
In TRONIC transformers without stress-relief, the cable must be
protected against pushing and pulling with a suitable clamp at the
TRONIC transformer.
For TRONIC transformers with prepared connecting cable, a suitable box
to connect the mains supply must be used.
For TRONIC transformers equipped with a stressrelieving device, use at
least a H 05 VV-F 2x1.5 mm² cable for the mains supply. Stripping length
for outer cable sheath and base insulation: see fig. (8).
Figure 8
Important: When TRONIC transformers with multipoint terminals on
the primary side for mains supply through-connection are used, the
maximum number of interconnected TRONIC transformers is limited
to 10.
4. Technical
data
10-40 W
Trafo
20-70 W
Trafo
20-70 W
Trafo
20-105 W
Trafo
20-150 W
Trafo
50-200 W
Trafo
Design /
Dimension (mm)
73 x 35,5 x
18
49 x 48 x 28
152 x 43,5x
17,5
175 x 42 x 18
176 x 42 x 38
212 x 48,5 x 46
Nominal rating
10-40 W T50
20-60 W T50
20-70 W T40
20-70 W T50
20-105 W T50
20-150 W T50
50-200 W T50
Supply voltage
AC 230 V ~
Mains frequency
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 / 60 Hz
50 Hz
Output voltage
11,7 V eff
~ 50 kHz
11,7 V eff
~ 40 kHz
11,7 V eff
~ 40 kHz
11,8 V eff
~ 40 kHz
11,7 V eff
~ 40 kHz
11,5 V eff
~ 40 kHz
Primary current
0,18 A
(40 W)
0,33 A
(60 W)
0,33 A
(70 W)
0,45 A
(105 W)
0,71 A
(150 W)
0,95 A
(200 W)
Max. ambient
temperature
50 °C
50 °C (60 W)
50 °C
50 °C
50 °C
45 °C
Max. housing
temperature
85 °C
75 °C
90 °C
80 °C
75 °C
65 °C
Max. length of
secondary line
2 m
2 m
2 m
2 m
2 m
2 m
Figure 9
5