Start-up
W
V
CAUTION!
The heating system will malfunction
if the controls are incorrectly set.
This can damage the heating system.
Only a technician may adjust the settings
of the heating system.
Set the heating mode when starting the controller.
■
Press
M
in the default display.
MENU briefly appears in the function display (8).
A help text as a marquee appears at the bottom
edge of the display.
■
Press the
+
/
-
buttons until INSTALLER
SETTINGS appears.
■ Select INSTALLER SETTINGS with
O
.
CODE is displayed, and code number 0 flashes.
■ Select code 7 with
+
/
-
, confirm with
O
.
H1 and the marquee text HEATING TYPE are
displayed.
■
Press
O
.
ROOM
is the default. When switching the heating
mode, all the user and installer settings are reset to
the default.
■
Press
+
/
-
to set the desired heating mode
and confirm with
O
.
The heating mode is set.
Additional settings are available under "Installer
settings".
Installer settings
Overview 3
A marquee at the bottom of the display shows
information for an individual menu items identified
with H1 to H11.
W
W
Some menu items are not available under the
control modes set under H1.
The abbreviations for the relevant control mode for
each menu item are indicated in the table.
The abbreviations have the following meaning:
R
= Room temperature controller
F
= Floor temperature controller
L
= Room temperature controller with a limiting
function
(The menu displays and set all values are in
UPPERCASE, and the
presettings are bold
)
H1 HEATING TYPE
R F L
Selection of the control method depending on the
heating mode:
–
ROOM
= Room temperature controller with
the setting of whether or not a remote sensor is
connected:
EXTERNAL SENSOR = YES/
NO
–
FLOOR = Floor temperature controller
–
LIMITER = Room temperature controller with
limiter
Select with
+
/
-
, confirm with
O
.
H2 CONTROL MODE
R F L
Select the control mode:
–
PWM
= Pulse width modulation with the cycle
time set in minutes:
10
, 15 ... 30.
W
W
For fast heating systems, select a short cycle
time, for slow heating systems, select a long
cycle time. The minimum on/off time is 10% of
the cycle time.
–
ON/OFF = Two-point control with setting option
of the hysteresis (
OFF
, 0.1 °C, 0.2 °C … 5.0 °C)
and the minimum switch-on/switch-off time of the
relay in minutes (1, 2 …
10
... 30).
W
W
If the hysteresis is not set, the relay switches
with the minimum on/off time even when the
temperature differences are very small.
Select with
+
/
-
, confirm with
O
.
H3 MIN/MAX FLOOR TEMP
L
Setting the upper and lower limit for the floor
temperature:
–
LOWER LIMIT FLOOR TEMP
: The floor should
not be colder than the temperature set here
(
OFF
, 10.0 °C, 10.5 °C … 35.0 °C).
–
UPPER LIMIT FLOOR TEMP
: The floor should
not be warmer than the temperature set here
(OFF, 10.0 °C, 10.5 °C …
35.0
°C
... 40.0 °C,
OFF).
Set the temperatures with
+
/
-
and confirm with
O
.
W
W
To deactivate the upper or lower limit, set the
lower temperature limit < 10°C, or the upper
temperature limit > 40°C with
+
/
-
. OFF is
displayed.
H4 HEATING OR COOLING
R
Switching the controller between heating and
cooling mode:
–
HEATING
– COOLING
W
W
Precondition for switching to cooling mode:
H2 - CONTROL = ON/OFF
W
W
H4 = Heating: If there is an error, heating takes
place for 30 % of the time.
H4 = Cooling: If there is an error, the relay
is off.
W
W
When switching to cooling mode, H6 - FROST
PROTECTION is automatically set to OFF,
and H7 - OPTIMUM START is set to NO.
W
W
The switching times and temperatures of
heating mode are used.
Select with
+
/
-
, confirm with
O
.
H5 VALVE PROTECTION
R
L
Protection of the valve from seizing after
long periods with no control. Every 24 hours,
calculated from the last switch-on of the voltage of
RESET (H11), the valve is opened for the time set
here in minutes: OFF, 1, 2,
3
… 10.
Set the opening time with
+
/
-
and confirm with
O
.
H6 FROST PROTECTION
R F L
Setting the frost protection temperature:
–
For H1 = ROOM or LIMITER:
OFF,
5.0 °C
, 5.5 °C … 30.0 °C
–
For H1 = FLOOR:
OFF,
10.0 °C
, 10.5 °C … 40.0 °C
Press
+
/
-
to set the temperature and confirm
with
O
.
If the temperature falls below the set frost protection
temperature, heating is turned on.
W
W
To deactivate the frost protection with a button
-W
select the OFF setting under the lowest
temperature.
W
W
Frost protection mode is only possible when
the control is shut off; see user settings:
G4 - OFF HEATING PERMANENT = YES
H7 ECO SETTING
R F L
Presetting of the ECO temperature:
–
For H1 = ROOM or LIMITER:
OFF, 5.0 °C, 5.5 °C …
18.0 °C
… 30.0 °C
–
For H1 = FLOOR:
OFF, 10.0 °C, 10.5 °C …
18.0 °C
… 40.0 °C
Press
+
/
-
to set the temperature and confirm
with
O
.
W
W
The temperature set here is only used when
the ECO input is activated (see ...).
H8 VALVES NORMALLY OPEN
R
L
Reverse of the relay switching behaviour for using
actuators that are normally open:
–
YES =
activated
–
NO
= deactivated
Select YES/NO with
+
/
-
, confirm with
O
.
H9 ENERGY COUNTER RESET
R F L
Reset to zero the energy cost meter set under
G8/G9 (see user settings).
–
YES =
reset
–
NO
Select YES/NO with
+
/
-
, confirm with
O
.
H10 FLOOR TEMPERATURE DISPLAY
L
Display of the current floor temperature for service
purposes.
H11 RESET ALL
R F L
Reset to the defaults all of the settings made in the
menus for the installer and user.
–
YES =
reset
–
NO
Select YES/NO with
+
/
-
, confirm with
O
.
Overview 3: Installer settings
Open the settings menu and make settings
The display shows the menu code H1 in the display
(8) and, beneath that, the marquee HEATING TYPE.
■
Press
+
/
-
to select the desired menu.
The menu ID and a help text appear at the
bottom edge of the display (7) and (11).
■ Confirm with
O
.
The first settable value flashes in the display.
■
Set the desired value by pressing
+
/
-
.
■ Confirm with
O
.
The second settable value flashes.
■
Repeat the aforementioned steps until all the
values are set.
The display returns to higher-level and displays
the menu ID.
Appendix
Do not dispose of this product in household
waste. Dispose of the device in a facility
designated for electronics waste.
Consult the local recycling authorities.
C
This symbol confirms that the product is in
conformance with the relevant guidelines.
Technical data
Operating voltage:
AC 230 V ~
Rated frequency:
50 Hz
Output:
N/O contact relay, non-floating
Switching current
- as a room temperature controller
or room temperature controller with limiter:
10 mA ... 10 (4) A, 230 V~
- as a floor temperature controller:
10 mA ... 16 (4) A, 230 V~
Power consumption:
~ 1.2 W
Degree of protection:
IP 30
Protection class: II (with corresponding installation)
Pollution category:
2
Ambient temperature:
- Operation:
0°C to 40 °C (without thawing)
- Storage:
-20°C to 70°C (without thawing)
Temperature setting range (in increments of 0.5 °C):
- As a room temperature controller:
5°C ... 30 °C
- as a floor temperature controller:
10°C ... 40 °C
Temperature display:
In increments of 0.1°C
Output signal:
Pulse width modulation (PWM)
or two-point control ( on/off)
PWM cycle time:
Adjustable (10 ... 30 min)
Hysteresis:
Adjustable (with two-point control)
Minimum switching time:
Adjustable (1 ... 30 min)
Rated impulse voltage:
4 kV
Temperature for the ball thrust test:
75 ± 2°C
Voltage and current for the EMC
emitted interference test:
230 V, 0.1 A
Software class:
A
Accuracy:
< 4 min/year
Reserve power:
~ 10 years (lithium cell)
Help in case of problems
Overviews 4 and 5 describe a few error messages
and problems as well as probable causes and
solutions.
Error message/problem
Possible cause
– Suggestions for troubleshooting
Display of device errors
Errors in the hardware configuration can be shown
on the display. In this case, ERR and an error type
are displayed as marquee text.
ERR CONFIGURATION
The controls and insert do not match.
– Only use matching components.
–
Turn the power off and on.
ERR COMMUNICATION
Communication problem between the controls and
insert.
– Remove the controls and put them back on.
–
Turn the power off and on.
ERR EXT SENSOR
External remote sensor broken/shorted/missing.
–
Check whether the remote sensor is connected.
The limits of the display range are exceeded.
– Determine the cause and eliminate it.
Overview 4: Display of device faults
Other problems and operating errors
The room is heating up too slowly.
The floor temperature is limited by the maximum
limiter.
– Adjust the upper limit (H3).
The room temperature is too hot.
The floor temperature is limited by the minimum
limiter.
–
Adjust the lower limit (H3).
No entries can be made.
Access protection is enabled.
– Disable access protection (G6).
The desired temperature cannot be set.
The temperature limitation prevents the desired
setting.
– Adjust the temperature limitation (G7).
The temperature display does not change.
The target temperature display is activated.
– Activate the display of the room temperature (G10).
Overview 5: Other problems and operating errors
Accessories
Remote sensor (not included in the delivery)
Type:
FF 7.8
Length:
4 m (can be extended up to 50 m)
Wire:
Flexible, finely stranded
Stripped end:
8 mm
Fig. 7: External remote sensor
Resistance/temperature table for remote sensor
FF 7.8
Temperature [°C]
Resistance [k
W
]
10
66.8
20
41.3
25
33
30
26.3
40
17.0
50
11.3
Table 1: Resistance/temperature table for
remote sensor FF 7.8
Warranty
We reserve the right to modify technical and formal
characteristics of the product insofar as this supports
technical progress.
Our products are under guarantee within the scope
of the statutory provisions.
Please return the device with a description of the
problem to our Central Service Centre:
ALBRECHT JUNG GMBH & CO. KG
Service Centre
Kupferstr. 17-19
44532 Lünen
Germany
W
W
Only install the temperature controller in non-
conductive plastic flush-mounted boxes with
a diameter of 60 mm!
■
Align the insert (7) in the appliance box (22).
■ Fix the insert with fastening screws (23).
Install the insert so that the plastic tongue (21)
functions as insulation against the fastening
screw (Fig. 5).
(7)
(5)
(1)
Fig. 6: Mounting the controls
■
Mount the design frame (5) and secure by
attaching the controls (1).
Connecting the remote sensor
A remote sensor can be used instead of the internal
sensor to measure the room temperature. The menu
item H1 can be used to select whether the remote
sensor is to be used.
An external remote sensor is necessary for
the modes "Floor temperature controller" and
"Room temperature controller with limiter".
The remote sensor line carries mains voltage and
can be extended to 50 m with appropriate lines.
In order to prevent signal faults, do not run the
remote sensor line together with power lines. It is
recommendable to run the remote sensor in ducting.
■
Connect the remote sensor according to the
connection diagram (Fig. 4, item (20)).
■ When inserting and removing the connecting
line using an appropriate tool, press the release
buttons (Fig. 4/7, item (24)).
Connecting an external switch to the ECO input
To control the temperature to a preset value
automatically, it is necessary to connect an external
switch, e.g. a timer.
■
Connect the connecting line of the external
switch according to the connection diagram.
■ When inserting and removing the connecting
line using an appropriate tool, press the release
button (Fig. 4, item (25)).
Information for electrically
skilled persons
Installation and electrical connection
W
V
DANGER!
Electric shock from touching live parts.
Electric shock can be fatal.
Before working on the device,
disconnect the connecting lines and
cover surrounding live parts!
Installation site
The controller should be installed at a location in the
room which is easily accessible for use.
When using the internal temperature sensor,
the chosen installation site should:
– Enable free circulation of air
–
Not be in a draft (such as an open window or doors)
– Not be located behind curtains, cabinets, shelves,
etc.
– Not be exposed to direct sunlight
–
Not be directly influenced by sources of heat
–
Not be adjacent to external walls
–
Be 1.5 m above the floor
Connecting and installing the controller
(7)
(1)
Fig. 3: Remove the controls from the insert
■
Remove the controls (1) from the insert (7).
■
Remove a maximum of 8 mm of the insulation
from the connecting lines.
Sensor
N
N
L
TRD..231..
AC 230V ~ 50Hz
10(4)A / -R,-L
T40
16(4)A / -F
RTR mit Display
Made in Germany
ECO
L
N 230 V~, 50 Hz
(17)
(18)
(25)
(24)
(20)
Fig. 4: Connection diagram
The connection terminals (18) for mains and
switching current are designed for solid or flexible
conductors with cross-sections of 1 to 2.5 mm
2
.
■
Connect the controller according to the
connection diagram (Fig. 4).
■
If necessary, connect an external remote sensor
(20) (see "Connecting the external remote
sensor").
(7)
(22)
(23)
(21)
Fig. 5: Installation