Operating hours
0...65535
Basic setting: Current value
The time is counted during
which the load is physically
switched on (relay contact
closed).
This parameter can be reset to
"0", for example after
exchanging the load.
The Reset button is used to
reset the meter to "0". The
device must be programmed
to apply the change.
Extended channel settings
Parameters
Setting options, Basic
setting
Explanations
Operating mode
Switching operation
Push-button operation
Flashing
Continuous on
Continuous off
Basic setting: Switching
operation
See Device and channels.
Manual commissioning
On, Off
Basic setting: On
Blocks manual commissioning
for the device channel. In the
"Off" setting, the device
cannot be reset to the factory
setting.
Local Operation
On, Off
Basic setting: On
Blocks the output for operation
using the
Prog
button.
Behaviour on voltage return
On
Off
Last value
Configured brightness
Basic setting: Off
Defines the behaviour of the
output after voltage return.
Timer behaviour, voltage
return
Off
Restart
Basic setting: Off
Specifies whether the timers
for switch-on delay, switch-off
delay and run-on time remain
off after voltage return or
whether they restart. Directly
connected to the parameters
"Switch-on delay", "Switch-off
delay" and "Run-on time".
Behaviour after the end of the
disabling function
On
Off
no change
Last value
Basic setting: No change
Behaviour of the output when
a block is removed.
Manual saving of the scene
values
On, Off
Basic setting: On
Disables the saving of the
current actuator state (On/Off)
as scene value in an actuator
for a command via a
transmitter.
9/12
82581723
J0082581723
23.03.2017
eNet radio switch/push-button actuator 1-gang, for rail mounting