Operating hours

0...65535
Basic setting: Current value

The time is counted during
which the load is physically
switched on (relay contact
closed).
This parameter can be reset to
"0", for example after
exchanging the load.
The Reset button is used to
reset the meter to "0". The
device must be programmed
to apply the change.

Extended channel settings

Parameters

Setting options, Basic
setting

Explanations

Operating mode

Switching operation
Push-button operation
Flashing
Continuous on
Continuous off
Basic setting: Switching
operation

See Device and channels.

Manual commissioning

On, Off
Basic setting: On

Blocks manual commissioning
for the device channel. In the
"Off" setting, the device
cannot be reset to the factory
setting.

Local Operation

On, Off
Basic setting: On

Blocks the output for operation
using the 

Prog

 button.

Behaviour on voltage return

 On
 Off
Last value
Configured brightness
Basic setting: Off

Defines the behaviour of the
output after voltage return.

Timer behaviour, voltage
return

 Off
Restart
Basic setting: Off

Specifies whether the timers
for switch-on delay, switch-off
delay and run-on time remain
off after voltage return or
whether they restart. Directly
connected to the parameters
"Switch-on delay", "Switch-off
delay" and "Run-on time".

Behaviour after the end of the
disabling function

 On
 Off
no change
Last value
Basic setting: No change

Behaviour of the output when
a block is removed.

Manual saving of the scene
values

On, Off
Basic setting: On

Disables the saving of the
current actuator state (On/Off)
as scene value in an actuator
for a command via a
transmitter.

9/12

82581723
J0082581723

23.03.2017

eNet radio switch/push-button actuator 1-gang, for rail mounting

Содержание FMAS16REG

Страница 1: ...port dangerous voltages to the device and or load Danger of electric shock During installation and cable routing comply with the regulations and standards which apply for SELV circuits Danger of elect...

Страница 2: ...Fully encrypted radio transmission AES CCM from eNet Server software version 2 0 Update of the device software Reading of error memory Behaviour in case of bus voltage failure and return If the bus v...

Страница 3: ...k grey Power supply DC RD red Power supply Bus WH white Data cable Bus YE yellow Data cable As bus line use e g J Y St Y 2x2x0 8 o Connect the device with bus line figure 2 to the RMD reception module...

Страница 4: ...eter set with eNet server M Push button operation K Switching operation If the operating mode switch is turned from the position PC to another operating mode the parameters are set to the default sett...

Страница 5: ...place i Scene buttons must be connected separately Disconnecting connection to a radio transmitter o Carry out the same steps as when connecting see Connecting actuator to radio transmitters The statu...

Страница 6: ...out conductor sleeve 0 75 4 mm Finely stranded with conductor sleeve 0 5 2 5 mm Fitting width 36 mm 2 modules Bus line Rated voltage DC 12 V SELV Current consumption max 20 mA Connection Bus device co...

Страница 7: ...frequency can be changed using parameters The parameter Switch off delay is used for the pulse time and the parameter Switch on delay for the pause time Continuous on The output switches to continuous...

Страница 8: ...s parameter Comment The set times apply to operation using radio transmitters The relay is switched immediately when the Prog button is pressed Run on time 0 s 24 h Basic setting 0 s As soon as a run...

Страница 9: ...ff Basic setting On Blocks the output for operation using the Prog button Behaviour on voltage return On Off Last value Configured brightness Basic setting Off Defines the behaviour of the output afte...

Страница 10: ...switching state On Off Basic setting On Defines the behaviour of the output on activating the forced operation Deactivate forced operation switching state On Off Basic setting Off Defines the behaviou...

Страница 11: ...is not yet active as a light controller has not yet been implemented Switch on brightness undershoot On Off Basic setting Off Allows automatic switch on according to the brightness If the parameter is...

Страница 12: ...ungen 6 3 Accessories Power supply 12 V for rail mounting Art No NT1220REGVDC eNet master receiver for rail mounting Art No FMFK32REG eNet server for rail mounting Art No ENET SERVER 6 4 Warranty The...

Отзывы: