Figure 3
o
Mount radio receiver (1) on DIN rail.
o
Connect radio receiver according to connection diagram (figure 3).
o
Connect radio receiver with the RMD radio actuators via the connection socket (3) using a
bus cable (6).
o
Connect option external antenna (see Connecting an external antenna).
i
The total length of the bus cables between the RMD devices may not exceed 3 m.
i
The polarity of the bus cables must not be reversed.
i
For the bus cable, use a shielded cable with twisted conductors and a conductor diameter
of 0.8 mm that is designed for a test voltage of 2.5 kV AC. Examples of permissible bus
cables are YCM 2×2×0.8 or J-Y(St)Y 2×2×0.8.
o
Switch on mains voltage.
Connecting an external antenna
Figure 4
A
Routing outside the distributor
B
Routing inside the distributor
o
Insert the antenna connector (7) into the SMB socket (2) of the radio receiver (1) (figure 4).
3/4
32549823
J0032549823
24.10.2016
Radio Management