background image

Figure 3

o

Mount radio receiver (1) on DIN rail.

o

Connect radio receiver according to connection diagram (figure 3).

o

Connect radio receiver with the RMD radio actuators via the connection socket (3) using a
bus cable (6).

o

Connect option external antenna (see Connecting an external antenna).

i

The total length of the bus cables between the RMD devices may not exceed 3 m.

i

The polarity of the bus cables must not be reversed.

i

For the bus cable, use a shielded cable with twisted conductors and a conductor diameter
of 0.8 mm that is designed for a test voltage of 2.5 kV AC. Examples of permissible bus
cables are YCM 2×2×0.8 or J-Y(St)Y 2×2×0.8.

o

Switch on mains voltage.

Connecting an external antenna

Figure 4

A

Routing outside the distributor

B

Routing inside the distributor

o

Insert the antenna connector (7) into the SMB socket (2) of the radio receiver (1) (figure 4).

3/4

32549823
J0032549823

24.10.2016

Radio Management 

Master receiver for rail mounting

Отзывы: