6 Appendix
Disposal
Please consider your local regulation for disposal and electronic waste recycling.
6.1 Technical data
KNX medium
TP
Commissioning mode
S-mode
Rated voltage KNX
DC 21 ... 30 V SELV
Current consumption KNX
max. 12.5 mA
Connection, Bus
device connection terminal
Ambient temperature
23 ... 113 °F
(23 ... 113 °C)
Storage/transport temperature
-13 ... +149 °F
(-25 ... +65 °C)
Relative humidity
5 ... 93 % (No moisture condensation)
Protection class
III
Motion detection
Detection angle
360 °
Range at installation height 9.8 ft (3 m)
Ø approx. 65.6 ft (20 m)
Brightness sensor
Measuring range
0 ... 186 fc
(0 ... 2000 lx)
Detection field
Ø approx. 6.6 ft (2 m)
Purpose of control
Sensing Control
Construction of control
Independently Mounted Control for Surface
Mounting
Pollution Degree
PD 2
Impulse Voltage
330 V
6.2 Troubleshooting
Light does not switch on despite motion detection and low lighting
Cause 1: Wrong function block active.
Change function block switchover.
Cause 2: Brightness threshold set is too low.
Increase the brightness threshold with the remote control or parameter setting.
Light switches on despite sufficient ambient lighting
Cause 1: Signal function is active and the device therefore operates independently of the bright
ness.
Check programming.
Cause 2: Device operates independently of the brightness.
Adjust the brightness threshold with the remote control.
Correct parameter setting for brightness threshold.
Light switches off briefly and then on again immediately
Cause 1: Luminaires in the detection area.
Set the configuration barrier parameter so that cooling luminaires are not detected.
Cause 2: The brightness threshold set is not reached after switching off. Device switches on
again immediately during motion detection.
Increase brightness threshold.
Light switches off early despite motion detection and low lighting
Cause 1: The set time is too short.
Increase the time with the remote control or parameter setting.
11/12
Presence detector
82585625
J0082585625
04.12.2017