Jung 2142 REG Скачать руководство пользователя страница 4

 

KNX 

Area /Line Coupler 

 

Ref.-no..: 2142 REG 

 

 

Function of diagnosis LED („DIAG“) red 

LED off: Telegrams are filtered or blocked (both directions) 

LED on: Telegrams are retransmitted without being filtered (at least one 
direction) 

Function of operation LED („RUN“) green 

LED off: device off, no voltage on superordinate line 

LED on: device on, voltage on both lines 

LED flashing: no voltage on subordinate line 

4.  Installation 

The device is snap-fastened on the DIN rail until the latch is heard to 
engage, with the connecting terminals pointing downwards. 

5.  Connection 

The superordinate line is connected with the left-hand terminal (FIG. 

A

(8), terminal „HL“). This terminal supplies power to the device electronics 
so that it is possible to report a bus voltage failure of the subordinate via 
the superordinate line. The subordinate line is connected to the right-
hand terminal (FIG. 

A

, (7), terminal „UL“). 

Removal info

: Do not lever out the connecting termianal from below. 

Risk of shorting the bus voltage which is not available during the short-
circuit. 

Allocation of the physical address 

Press the programming button (2) 

→ 

the programming LED (1) lights up. 

The LED goes out on taking over of the physical address. 

6.  Technical data 

Supply 

KNX/EIB:  

21 

– 30 V DC 

 

 

from superordinate line 

Current consumption 

 

superordinate line:  

approx. 6 mA 

 

subordinate line:  

approx. 8 mA 

Connection : 

KNX/EIB terminal for superordinate 
and subordinate line 

Fitting:  

snap-fastening on DIN rail 

Ambient temperature:  

-5 °C ... +45 °C 

Storage temperature.:  

-25 °C ... + 70 °C 

Type of protection:  

IP 20 in acc. with EN 60529 

Safety class:  

III in acc. with EN 61140 

Installation width:  

36 mm (2 modules) 

Weight: approx.  

90 g 

Technical specifications subject to change. 