KNX
Area /Line Coupler
Ref.-no..: 2142 REG
4
4
Function of diagnosis LED („DIAG“) red
LED off: Telegrams are filtered or blocked (both directions)
LED on: Telegrams are retransmitted without being filtered (at least one
direction)
Function of operation LED („RUN“) green
LED off: device off, no voltage on superordinate line
LED on: device on, voltage on both lines
LED flashing: no voltage on subordinate line
4. Installation
The device is snap-fastened on the DIN rail until the latch is heard to
engage, with the connecting terminals pointing downwards.
5. Connection
The superordinate line is connected with the left-hand terminal (FIG.
A
,
(8), terminal „HL“). This terminal supplies power to the device electronics
so that it is possible to report a bus voltage failure of the subordinate via
the superordinate line. The subordinate line is connected to the right-
hand terminal (FIG.
A
, (7), terminal „UL“).
Removal info
: Do not lever out the connecting termianal from below.
Risk of shorting the bus voltage which is not available during the short-
circuit.
Allocation of the physical address
Press the programming button (2)
→
the programming LED (1) lights up.
The LED goes out on taking over of the physical address.
6. Technical data
Supply
KNX/EIB:
21
– 30 V DC
from superordinate line
Current consumption
superordinate line:
approx. 6 mA
subordinate line:
approx. 8 mA
Connection :
KNX/EIB terminal for superordinate
and subordinate line
Fitting:
snap-fastening on DIN rail
Ambient temperature:
-5 °C ... +45 °C
Storage temperature.:
-25 °C ... + 70 °C
Type of protection:
IP 20 in acc. with EN 60529
Safety class:
III in acc. with EN 61140
Installation width:
36 mm (2 modules)
Weight: approx.
90 g
Technical specifications subject to change.