10 Technical data
10.7 General characteristic data
Circuit options
- Three-phase economy circuit in master slave operation
Operating mode:
- Burst-firing operation for resistive or transformer load
Special features
- Dual energy management
- Soft start with pulse groups
Cascade control
U² control as standard
Can be switched over to U, I, I², P control depending on device type
Electrical connection
For type 709062/8 -0X-020...
Control and load leads are connected via screw terminals.
From type 709062/8 -0X-032...
Control leads are connected via screw terminals and load leads via cable
lugs DIN 46235 and DIN 46234 or tubular cable lugs.
Operating conditions
The power controller is designed as a panel-mounting device as per: EN 50
178,
pollution degree 2, overvoltage category Ü III
Electromagnetic
compatibility
as per DIN 61326-1
Emitted interference: class B
Interference resistance: industrial requirements
Protection type
all device types IP20 as per EN 60 529
Protection rating
Protection rating I, with isolated control circuitry for connection to SELV cir-
cuits
Permissible
ambient temperature range
35°C with forced air cooling (250A controller)
0 … 45°C with natural air cooling (extended temperature range, class 3K3
as per EN 60 721-3-3)
For higher temperatures, use with reduced type current is possible.
(from 45°C with type current -2%/°C)
v
Chapter 2.1.3 „Permissible load current depending on the ambient tem-
perature“
Permissible storage
temperature range
-30 … +70°C (1K5 as per EN 60 721-3-1)
Cooling
- Natural convection up to a load current of 200A
- For a load current of 250A, forced convection with built-in ventilator
Environmental performance
Rel. humidity £ 85 % annual average, no condensation 3K3 as per EN 60
721
Installation position
vertical
Test voltage
as per EN 50178
Creepage distances
8 mm between supply current circuit and SELV circuits
for type 709062/8 -0X-020...
12.7 mm between supply current circuit and SELV circuits
from type 709062/8 -0X-032...
SELV = Separate Extra Low Voltage (safe low voltage)
Case
Plastic, flammability class UL94 V0, color: cobalt blue RAL 5013
Power dissipation
The power dissipation can be calculated using the following empirical for-
mula:
Pv = 20W + 1.3V x ILoad A
Maximum temperature of the
cooling body
110°C
Содержание TYA 202
Страница 8: ...6 2011 07 01 00561073 Thyristor Leistungssteller TYA202 Content...
Страница 16: ...1 Introduction 14 2011 07 01 00561073 SCR Power Controller TYA202...
Страница 21: ...2011 07 02 00561073 SCR Power Controller TYA202 19 2 Installation TYA202 100A TYA202 150 200A...
Страница 22: ...2 Installation 20 2011 07 02 00561073 SCR Power Controller TYA202 TYA202 250A...
Страница 30: ...2 Installation 28 2011 07 01 00561073 SCR Power Controller TYA202...
Страница 40: ...3 Electrical Connection 38 2011 07 01 00561073 SCR Power Controller TYA202...
Страница 66: ...5 Configuration 64 2011 07 01 00561073 SCR Power Controller TYA202...
Страница 84: ...6 Special device functions 82 2011 07 01 00561073 SCR Power Controller TYA202...
Страница 100: ...8 Fault messages and alarms 98 2011 07 01 00561073 SCR Power Controller TYA202...
Страница 107: ......