
3 Mounting
10
3.3
Capillary / temperature probe/ pocket
3.3.1
General
A
Cutting through or kinking the capillary will result in the permanent failure of
the instrument!
The minimum permissible bending radius of the capillary is 5 mm.
The temperature probe must be installed in JUMO pockets. If this is not the
case, the approval of the thermostat becomes void.
H
The temperature probe must be completely immersed in the medium.
Fitting several probes into a common pocket is permitted only with 2 or 3 plain
probes 6 mm dia. and pockets 15 x 0.75 mm.
When fitting 2 probes, the spring clip supplied by the factory must be fitted in
the pocket.
For use in air, Form A (without pocket) has to be used.