12 Configuration

80

Control direction

Is set to inverse (1) per default for heating mode.

Manual mode

 

Enabled

Manual mode possible on the device

Disabled

Manual mode disabled

Y in manual mode

Defines the output level (%) that the controller should 
adopt after switching to manual mode.

Y manual mode

The value set below for Y manual mode is adopted.

Current value

The current controller output level before switching to 
manual mode is adopted.

Average value

The average value calculated using the set time below 
is adopted.

Y with error

Defines the output level (in %) that the controller should 
display, if one of the analog values relevant for the con-
troller is invalid (incorrect actual value, setpoint value, 
output level feedback, etc).

Y replacement value

The Y replacement value set below is adopted.

Current value

The current output level before deviation above or below 
the measuring range is adopted.

Average value

The average value calculated using the set time below 
is adopted.

Y manual mode 0 to 100 %
Y replacement 
value

0 to 100 %

Time for
manual aver-
age value

1 to 3600 min

Time for averaging of values when average value is set 
for "Y in manual mode"

Time for 
replacement 
average value

1 to 3600 min

Time for averaging of values when average value is set 
for "Y with error"

Start of cascade 
standardization

0 to 100 %

The output level can be standardized here (only for cas-
cade controllers). 

End of cascade 
standardization

0 to 100 %

Deadband
(neutral zone)

 

0.00 to 100 %

Output level movements within the deadband are sup-
pressed, for example in the case of noisy signals. The 
deadband is only effective for controller structures with 
an I-component.

Additional functions Not selected (empty)
(setup only)

(

) Extension 1

Reserved functions for service

(

) Extension 2

(

) Extension 3

(

) Extension 4

1

Bold: default setting

Parameter

Selection/settings

1

Description

Содержание DICON touch

Страница 1: ...JUMO DICON touch Two Four Channel Process and Program Controller with Paperless Recorder and 8 9 cm 3 5 Touch screen Operating Manual 70357100T90Z004K000 V2 00 EN 00603327 2020 03 10...

Страница 2: ......

Страница 3: ...ng 19 3 2 Dimensions 20 3 3 Close mounting 21 3 4 Installation in panel cut out 21 3 5 Care and treatment of the front cover 21 4 Electrical connection 23 4 1 Installation notes 23 4 1 1 Lines shieldi...

Страница 4: ...values to the user level 47 8 Program administration 49 8 1 Entering program profiles 49 8 1 1 On the device 49 8 1 2 About the setup program 50 8 1 3 Section run time 51 8 1 4 Setpoint value 1 to 4...

Страница 5: ...ms 78 12 6 Controller 1 to 4 79 12 6 1 Controller configuration 79 12 6 2 Controller inputs 82 12 6 3 Controller self optimization 84 12 6 4 Starting autotuning SO on the device 89 12 6 5 Control loop...

Страница 6: ...am 131 12 13 Timer or week time switch 132 12 14 Digital controller signals 135 12 14 1Alarms 137 12 15 Math logic 138 12 16 Flags service 140 12 16 1Flags 140 12 16 2Service 141 12 17 External digita...

Страница 7: ...170 14 Special functions 171 14 1 Calibrating the touchscreen 171 15 Online parameters 173 15 1 Fine adjustment 173 15 2 Ethernet option 175 15 3 Date and time 176 15 4 Screenshot 176 15 5 Deleting th...

Страница 8: ...Table of contents 8 18 2 DIN 193 19 China RoHS 195...

Страница 9: ...dicates that personal injury may occur if the respective precautionary measures are not carried out CAUTION This symbol in connection with the signal word indicates that damage to assets or data loss...

Страница 10: ...ON Active input The device has no keys and is operated using a finger or a pen The following manual will therefore make references to touching and the images displayed will show a hand operating the d...

Страница 11: ...evel systems interfaces such as Modbus master slave PROFIBUS PROFINET RT or Ethernet with web server can be used To ensure secure process operation the device has password protected user administratio...

Страница 12: ...ay output OUT2 changeover contact Digital analog outputs OUT4 OUT3 Digital analog outputs OUT6 OUT5 Digital analog outputs OUT8 OUT7 Digital analog outputs OUT10 OUT9 Digital analog outputs OUT12 OUT1...

Страница 13: ...changeover contact 12 2 relays normally open 13 1 solid state relay 230 V 1 A 14 1 logic output 0 22 V max 30 mA 15 2 logic outputs 0 12 V 20 mA 16 1 analog output 17 2 PhotoMOS relays1 20 2 solid sta...

Страница 14: ...ut 0 22 V max 30 mA 15 2 logic outputs 0 12 V 20 mA 16 1 analog output 17 2 PhotoMOS relays1 10 Outputs OUT11 12 00 None 11 1 relay changeover contact 12 2 relays normally open 13 1 solid state relay...

Страница 15: ...to 16 223 Program controller 879 AMS2750 CQI 92 1 PhotoMOS is a registered trademark of the Panasonic Corporation 2 For the calibration certificate the channels to be checked must be stated along wit...

Страница 16: ...V max 30 mA 00581165 Two logic outputs DC 0 12 V max 20 mA 00581168 One solid state relay AC 230 V 1 A 00581164 Two solid state relays AC 230 V 1 A for motor actuator 00621574 Two PhotoMOS relays1 DC...

Страница 17: ...on be tween the customer and the sales department Fabrication number F Nr Among other things the fabrication number contains the date of production year week Example F Nr 0202520101220120001 The chara...

Страница 18: ...ins information about optional modules provided per default as in the following example of the Ethernet interface digit 08 703571 8 01 00 00 00 00 00 00 00 25 08 see order code Further information on...

Страница 19: ...and with end sleeve Electrical safety According to DIN EN 61010 1 Overvoltage category III pollution degree 2 Electromagnetic compatibility Interference emission Interference immunity According to DIN...

Страница 20: ...Max 5 mm Mounting depth Max 130 mm Fastening 4 mounting elements Operating position including the viewing angle of the TFT color screen Any Horizontal 65 vertical 40 to 65 Protection type Front IP66...

Страница 21: ...p Activity 1 Affix delivered panel seal 1 on the device from the rear 2 Insert the device into the panel cut out from the front and ensure the panel seal is correctly positioned so that no water or po...

Страница 22: ...rated using commer cially available pens with a rounded plastic tip CAUTION Sharp tools will cause scratches and may damage the cover The front plate is not resistant to corrosive acids or lyes abrasi...

Страница 23: ...ctive ground is required 4 1 2 Electrical safety The primary fuse protection for the voltage supply should not exceed a value of 20 A slow blow and should not be less than 2 A In order to prevent the...

Страница 24: ...isuse The controller is intended for installation in the industrial sector WARNING The controller is not suitable for installation in potentially explosive areas Explosion hazard The device must only...

Страница 25: ...C 0 22 V max 30 mA short circuit proof ogic output 2 logic outputs DC 0 12 V max 20 mA short circuit proof Digital input potential free contact 7 DC 50 V AC 30 V DC 50 V AC 30 V DC 50 V AC 30 V AC 360...

Страница 26: ...ed personnel 1 Analog input IN8 2 Analog input IN9 3 Expansion slot for analog input IN10 4 Expansion slot for analog input IN11 5 Voltage supply AC 240 V 10 15 48 to 63 Hz AC DC 24 V 30 25 48 to 63 H...

Страница 27: ...ection ele ment Input Symbol and terminal designation Thermocouple 1 IN8 2 IN9 3 IN10 4 IN11 3 4 RTD temperature probe Two wire circuit 2 4 RTD temperature probe Three wire circuit 2 3 4 Voltage DC 0...

Страница 28: ...4 000 2 x Pt100 170 700 C 500 verschiebbare Klemmverschraubung G1 2 902006 55 228 2003 1 15 710 254 000 710 902006 55 228 2003 1 15 1000 254 000 1000 Thermoelemente Typenblatt 90 1006 901006 65 547 20...

Страница 29: ...thermometer Typenblatt 90 2006 902006 53 505 2003 1 12 190 815 000 90D239 F03 2 x Pt100 40 400 C 190 902006 53 507 2003 1 12 100 815 000 90 239 F02 2 x Pt100 im Schutzrohr untereinander angeordnet 40...

Страница 30: ...hangeover contacts as a standard feature Connection Connection ele ment Input Symbol and terminal designation 1 analog output DC 0 2 to 10 V or DC 0 4 to 20 mA configurable 8 OUT3 4 9 OUT5 6 10 OUT7 8...

Страница 31: ...DC 0 22 V max 30 mA short circuit proof 1 2 2 logic outputs DC 0 12 V max 20 mA short circuit proof not galvanically isolated from each other 1 2 3 4 2 PhotoMOS relays2 max DC 45 V 200 mA max AC 30 V...

Страница 32: ...300 DC 24V 3 0 5 7ms A 250 000 operations at nominal load One solid state relay Switching capacity Protection circuitry 1 A at AC 230 V resistive load Varistor Two solid state relay for motor actuator...

Страница 33: ...33 4 Electrical connection Connection Connection ele ment Symbol and terminal designation Protection conductor Neutral conductor Line conductor PE N L L1 L PE N L1...

Страница 34: ...nd COM1 interfaces as a standard feature Connection Connection element Symbol and terminal designation USB device interface 21 USB host 20 COM1 serial interface RS485 galvanically isolated 13 1 TxD Rx...

Страница 35: ...e RS422 galvanically isolated 1 RxD 2 RxD 3 TxD 4 TxD Received data Received data Transmission data Transmission data Serial interface RS485 galvanically isolated 3 TxD RxD 4 TxD RxD Transmission rece...

Страница 36: ...4 Electrical connection 36...

Страница 37: ...ure Commercially available pens with plastic tips can also be used 2 Controller overview images Factory setting switched off 4 Process images Factory setting switched off 2 Recording images Data recor...

Страница 38: ...re set per default to Operating level and Home back to main view and are configurable Operating manual Chapter 12 10 1 General configuration Page 112 The History H and Channel changeover Ch buttons en...

Страница 39: ...ogram Chapter 12 10 6 Colors designations in controller screen 1 to 4 Page 116 Default setting Fixed setpoint controller and Controller 1 are set up In order to function properly the controller requir...

Страница 40: ...Operating manual Chapter 12 6 3 Controller self optimization Page 84 Step Activity 1 Touch the hand symbol pencil appears at output level display 2 Touch the pencil enter the manual output level and c...

Страница 41: ...center Touching the black rectangle stops the program and the statuses prior to the program starting are adopted again Pause Pauses the time base of a program that is running whereby the current setpo...

Страница 42: ...il the dialog for en tering setpoint values 1 and 2 opens After pressing the OK button these setpoint values are used for the control Autotuning Operating manual Chapter 12 6 3 Controller self optimiz...

Страница 43: ...button If the channels to be displayed have been configured the screen must be activated for the display in the operating loop Operating manual Chapter 12 11 Recording 1 2 Page 120 5 5 5 Process scre...

Страница 44: ...5 Operation 44...

Страница 45: ...5 different users in the user list using the setup program On entering the password each user is entitled to use the rights available If permitted the rights and passwords can also be changed on the...

Страница 46: ...n as you are logged in the Log Out button is no longer grayed out and touching it will enable you to log out Your user rights will be limited again thereafter 6 3 Changing the password You can change...

Страница 47: ...to op erating personnel ONLY SETUP USER LEVEL Setup dialog box 7 1 Example 4 Transferring controller setpoint values to the user level The 4 switchable controller setpoint values are to be transferred...

Страница 48: ...7 User level Log In 48 Setup dialog box Device display Once the setup data has been transferred to the device the setpoint values can be entered on the device...

Страница 49: ...names and icons 2 Enter first section If the program memory is empty the section will be highlighted in red Each section consists of setpoint values 1 and 2 section time operating contacts toler ance...

Страница 50: ...ep Activity 1 Start the setup program and click on Program editor Program administration in the menu 2 Enter sections in the table 3 The table is displayed as a graphic with the program simulation 4 S...

Страница 51: ...sections They are available in the digital selector and can switch relays for instance Setup program CONFIGURATION LEVEL DIGITAL OUTPUTS They can also be logically linked or can trigger internal devic...

Страница 52: ...Parameter block For each control channel parameter blocks 1 to 4 are available and can be switched over in sections The configured parameter block relates to all controllers Selecting a parameter blo...

Страница 53: ...n the device are displayed alongside the device name 9 1 1 Version motherboard Ethernet information Software version fabrication number and testing ID are displayed Displays the hardware on the mother...

Страница 54: ...9 Device info 54 9 3 Inputs outputs The switching statuses and measured values are displayed here 9 3 1 Digital and analog inputs digital and analog outputs external digital and external analog inputs...

Страница 55: ...55 9 Device info 9 4 Functions 9 4 1 Math logic signal limit value outputs 9 4 2 Timer signal digital control signals operating contacts controller analog flag digital flag...

Страница 56: ...9 Device info 56 9 5 Ethernet 9 6 PROFINET...

Страница 57: ...d diagnostic purposes Analog and binary values of the outputs can be controlled manually here This may be useful for instance for checking an individual piece of equipment in a plant For maintenance a...

Страница 58: ...10 Functional level 58...

Страница 59: ...ither using the setup program or on the DICON touch This area is for setting the parameters that relate directly to the process of adjusting the controller to suit the control process after the plant...

Страница 60: ...ontroller type configured certain parameters may be omitted or ineffective Parameters that appear in pairs such as Proportional band 1 and 2 refer to the first and second controller outputs for instan...

Страница 61: ...witched output the cycle time should be chosen so that the energy supply to the process is as con tinuous as possible and the switching elements are not overloaded Cycle time 2 Cy2 0 to 20 to 999 9 s...

Страница 62: ...nd Xp must be greater than 0 for the controller structure to take effect If Xp 0 the behavior corresponds to the function of limit value monitoring with switching dif ferential Xd1 working point Y0 0...

Страница 63: ...cture to take effect The three step controller is used for actuator drives with three switching statuses actuator open closed hold If output level feedback is available the active output is deactivate...

Страница 64: ...Page 97 For program controllers Chapter 8 1 Entering program profiles Page 49 11 4 1 Entering the values on the device The setpoint values are entered in the parameter level Type Signal 2 Bit 1 setpo...

Страница 65: ...65 11 Parameterization 11 4 2 Entering the values using the setup program The setpoint values are entered in the parameter level setup dialog...

Страница 66: ...11 Parameterization 66...

Страница 67: ...or Category Signal Type Description No function No signal selected Analog inputs Analog input IN8 Internal Measured values of analog inputs 1 to 4 Chapter 12 5 Analog inputs IN8 IN9 IN10 IN11 Page 75...

Страница 68: ...Flags service Page 140 Service Terminal temperature Internal Measured value internal Pt100 Sampling period Sampling rate Internal Measured value of sampling rate Category Signal Type Description Cate...

Страница 69: ...ignals Ramp end signal 1 Internal Logic level 0 function inactive Logic level 1 function active Chapter 12 6 8 Ramp function Page 99 Tolerance band signal 1 Ramp end signal 2 Tolerance band signal 2 P...

Страница 70: ...3 MaxAlarm Ext AI 3 MinAlarm Ext AI 4 MaxAlarm Ext AI 4 MinAlarm Ext AI 5 MaxAlarm Ext AI 5 MinAlarm Ext AI 6 MaxAlarm Ext AI 6 MinAlarm Ext AI 7 MaxAlarm Ext AI 7 MinAlarm Ext AI 8 MaxAlarm Ext AI 8...

Страница 71: ...ive starting with the collective alarm event to the end of the alarm as long as the red alarm line flashes Collective alarm acknowl edged Is active starting with the collective alarm event to the ackn...

Страница 72: ...cted empty no The device starts without language selec tion Selected yes The language selection appears Supply frequency 50 Hz 60 Hz Temp device Deg Celsius Temperature unit for displaying the tem per...

Страница 73: ...If the remaining 20 has been used up the oldest recorded data is overwritten and replaced with the new data In this case there will be a gap in the recording Setup quick info Any text may be transferr...

Страница 74: ...er Selection settings Description Channel description Digital input 01 15 characters of editable text that indicates for example what the signal will be used for Alarm type Off Alarm switched off Alar...

Страница 75: ...aracters of editable text Probe Selection of measuring probe for the relevant analog input No function No sensor selected Resistance 3 wire RTD temperature probe in three wire circuit Resistance 2 wir...

Страница 76: ...Copel Fe CuNi L GOST Cu CuNi T Fe CUNi J Cu CuNi U Fe CuNi L NICr Ni K Pt10Rh Pt S Pt13Rh Pt R Pt30Rh Pt6Rh B NiCrSi NiSi N NiCr CuNi E W5Re W26Re C W3Re W25Re D In40 Rh Pt10Rh Pt Customer spec 1 Cust...

Страница 77: ...cted and the linearization These limits only affect the recording If for example the scaling end for a Pt100 is reduced from 850 C to 400 C the recording only displays values up to 400 C Measuring val...

Страница 78: ...e in addition to the functions described in Chapter 12 9 Limit value monitoring function page 106 and is independent of these functions Setup dialog box Parameters Parameter Selection settings Descrip...

Страница 79: ...type Off Control channel switched off default setting for Controller 2 Two state controller Controller with a switched output default setting for Controller 1 Three state controller Controller with tw...

Страница 80: ...t output level before deviation above or below the measuring range is adopted Average value The average value calculated using the set time below is adopted Y manual mode 0 to 100 Y replacement value...

Страница 81: ...ode If the setting is set to disabled manual mode is no longer possible on the device The button for manual mode is grayed out Deadband Default is 0 i e no distance between heating and cooling contact...

Страница 82: ...2 Controller actual value IN8 analog input 1 Analog signal for actual value Analog selector Controller setpoint value Setpoint specification for Controller 1 Analog signal for setpoint value Analog s...

Страница 83: ...to IN10 analog input 3 Signal Manual Auto changeover No selection Digital selector This signal switches between manual mode and automatic mode Signal Manual mode lock ing This signal locks manual mod...

Страница 84: ...old default setting Description Method Oscillation Oscillation method Step response Step response method Locking Enabled Autotuning can be started on the device Disabled Autotuning is disabled Output...

Страница 85: ...ependently of the configured parameters Error handling If the actual value deviates above or below the measuring range during autotuning autotuning is aborted In this case the configured parameters ar...

Страница 86: ...xceed the setpoint value if possible In the case of a minor control deviation for example if the control loop is in a steady state dur ing operation oscillation is forced around the setpoint value Her...

Страница 87: ...ely well insulated furnace with low losses long oscillation period Actual value must not exceed the setpoint value If the output level is known for the corrected setpoint value overshooting is prevent...

Страница 88: ...sible incorrect settings and how to correct them Here the transient behavior of a 3rd order control process for a PID controller is recorded as an example The procedure for setting the controller para...

Страница 89: ...derivative time 0 the PI structure is used for the optimization Is the os cillation method appropriate for the case at hand or do you need to switch to the step re sponse method not possible with ever...

Страница 90: ...n controller parameter block 1 3 Enter program setpoint value for manual mode 4 Return to the controller screen by pressing OK 5 Click on the symbol at the bottom for the SO and start by pressing OK 6...

Страница 91: ...e digital selector and can be processed further at any time Setup dialog box Parameters Parameter Selection settings Description Function Inactive Control loop monitoring is generally not permitted Ac...

Страница 92: ...ent actual value at the start of monitoring within the response time If it does not an alarm is triggered On leaving the monitoring band the actual value at the time is used as a reference value for a...

Страница 93: ...and the actual value is within the monitoring band An alarm may be caused by Partial or total failure of heating elements or other parts in the control loop Reversal of the control direction for examp...

Страница 94: ...Parameters Parameter Selection settings Description Locking Inactive Output level monitoring generally not permitted Active Output level monitoring generally permitted Determination time 0 s to 350 s...

Страница 95: ...ntrol differential band The mean output level is then deter mined again Application examples Monitoring of signs of aging and faults on heating elements Reporting of faults during operation Functional...

Страница 96: ...er if there is a temporary deviation from the control differential band when determining the output level or if the setpoint value is changed by more than 0 5 control differential band x A mean output...

Страница 97: ...log box Parameters NOTE The active setpoint value is not automatically used as a setpoint value for the control channel it must first be assigned in the controller configuration see Chapter 12 6 2 Con...

Страница 98: ...ogram setpoint value 2 Setpoint value 1 to 4 start 99999 to 99999 Setpoint limit start Setpoint value 1 to 4 end 99999 to 99999 Setpoint limit end Boost function No function Boost function switched of...

Страница 99: ...n Ramp off Ramp in minutes Ramp in hours Ramp in days Ramp function switched off Ramp function switched on Positive gradient 0 00 to 999 00 In the event of a setpoint value step the ramp rises dependi...

Страница 100: ...he case of a ris ing edge as the current controller set point value in the form of a step without a ramp If the ramp end value is changed again this behavior is no longer active and the ramp end value...

Страница 101: ...escription Description Relay OUT 1 15 characters editable text For example for the signal that is issued via the digital output Signal source Digital selector controller This signal is issued at the d...

Страница 102: ...1 Accessories page 186 12 7 2 Switching digital outputs to manual mode If it should be possible to switch digital outputs on the device using manual mode this must be enabled using the setup program...

Страница 103: ...three analog outputs can be configured as current or voltage outputs standard signal and are freely scalable Setup dialog box Parameters Parameter Selection settings Description Description Analog Out...

Страница 104: ...mit is issued NAMUR Low See table limits according to NAMUR NAMUR High See table limits according to NAMUR Frozen Retains the last valid value Safety value Issues the set replacement value Safety valu...

Страница 105: ...handling The behavior in the event of deviation above or below the measuring range out of range can be configured The settings made there also apply for probe conductor breaks or probe con ductor shor...

Страница 106: ...signal that can be linked to or issued at a dig ital output Setup dialog box Parameters Parameter Selection settings Description Function No function AF1 to AF8 Alarm function AF 1 to 8 can be select...

Страница 107: ...output is only re activated to the maximum level via the set pulse time after repeated devia tion above or below the alarm values The lock takes priority over the pulse function Response at error Off...

Страница 108: ...t value entered Shown with the associated hysteresis functions non standard left symmetrically non standard right Limit value in relation to the setpoint value Non standard left Symmetrically Non stan...

Страница 109: ...eresis page 108 Non standard left Symmetrically Non standard right AF5 AF6 w 1 x 0 2 w 1 x 0 2 w 1 x 0 2 w 1 x 0 2 w 1 2 x 0 w 1 2 x 0 1 Output signal active 0 Output signal not active x Actual value...

Страница 110: ...ssion The following example shows monitoring of the actual value x with the alarm function AF4 without hysteresis for a specified limit value 1 The setpoint value is changed from w1 to w2 Initial stat...

Страница 111: ...larm text Setup program Selection of text from a list Clicking on the button opens a list with text numbers and the associated texts The texts are editable Parameter Selection settings Description Ala...

Страница 112: ...recorded data is shown Yes Simulated data is displayed within the mea suring range Alarm text header Yes Alarms are inserted cyclically in the header No Alarms are not inserted Lock touchscreen No se...

Страница 113: ...s on Waiting period Screen is switched off following a waiting period Control signal Screen is switched off with a signal Waiting period 10 to 300 to 32767 s If the screen is not touched it will turn...

Страница 114: ...box Parameters only setup Parameter Selection settings Description Controller screen 1 to 4 Display do not display Controller overview Display do not display Program controller Display do not display...

Страница 115: ...tup dialog box Parameters Parameter Selection settings Description Analog channel 1 to 4 The color for the recording data can be selected in the RGB color selector Digital channel 1 to 3 Background co...

Страница 116: ...n of actual value 15 characters Default setting X actual value of control ler 1 Signal source of actual value Signal from the analog selector Designation of setpoint value 15 characters Default settin...

Страница 117: ...esignation time value Proglaufzeit Signal source No selection Analog selector integer Colour time value R0 G0 B0 RGB color selector Parameter Selection settings Description Description Sollwert1 Text...

Страница 118: ...for analog value 1 to 3 in light blue box Signal source No selection Any analog value can be displayed here Analog selector Color RGB color selector Color for analog values and text Bar graph Yes Bar...

Страница 119: ...iguration 12 10 9 Controller overview screen 1 2 Setup dialog box Parameters Parameter Selection settings Description Heading for Controller overview 1 27 characters of text can be entered Controller...

Страница 120: ...and a maximum of 3 digital signals are displayed in the form of a recorder screen Activation is required for the recorded data to also be saved or extracted and processed Chapter 15 6 Approval of extr...

Страница 121: ...before removing an inserted USB flash drive Please follow the instructions on the device s display Registry data update Measurement data that has not yet been retrieved is transferred to the flash dr...

Страница 122: ...ction settings Description Analog signal 1 to 4 Description Channel 1 Signal source No selection Any analog value can be recorded here Analog selector Line width Fine Bold Parameter Selection settings...

Страница 123: ...controller With the fixed setpoint controller all additional program functions are grayed out and therefore inactive Setup dialog for program controller Parameters Parameter Selection settings Descri...

Страница 124: ...elvin hour Kelvin day Actual value input for tolerance band monitoring IN8 analog input 1 This value is monitored by the toler ance band Analog selector Chapter 12 6 8 Ramp function page 99 Signal for...

Страница 125: ...ut specific time Program start after lead time Start with day of the week Program start on a day of the week and with a start time Start with date Program start on a specific date and at a specific ti...

Страница 126: ...signal switches to the next pro gram section No selection Signal Fast Forward Digital selector This signal fast forwards through the programs The longer the signal appears for the faster the process N...

Страница 127: ...ction settings Description Additional functions Not selected empty No function Reserved functions for service Fast forward etc Input interlock Not selected empty Setpoint value 1 The ticked program co...

Страница 128: ...ntered here is active in the basic status Program setpoint value 2 0 00 to 99999 Control contacts Not selected empty Contact 1 to 8 Ticked operating contacts are active in the basic status Parameter s...

Страница 129: ...Program setpoint value 1 0 00 to 99999 The value entered here is active in manual operating mode Program setpoint value 2 0 00 to 99999 Control contacts Not selected empty Contact 1 to 8 Ticked operat...

Страница 130: ...ters Parameter Selection settings Description Program setpoint value 1 0 00 to 99999 The value entered here is active for out of range parameters Program setpoint value 2 0 00 to 99999 Control contact...

Страница 131: ...pty Weekly program 1 to 10 Ticked weekly programs start auto matically Weekly program 1 Program number 0 Inactive Program number 1 Number of program to be started Start day Sunday Program starts on th...

Страница 132: ...time 00 00 00 to 99 59 59 The timer works for this time period Timer end time 0 to 9999 Downstream timer that is also available in the digital selector timer end signal Chapter 12 2 Digital selector...

Страница 133: ...is set here This signal is available in the digital selector for further use Low Additional timer func tions Not selected empty Extension 1 Reserved functions for service Parameter Selection settings...

Страница 134: ...12 Configuration 134 Monday to Saturday Hours 0 to 24 Same settings possible as for Sunday Switch on time 1 to 4 Switch off time 1 to 4 Parameter Selection settings Description...

Страница 135: ...ector Setup dialog box Parameters Parameter Selection settings Description Description Digit contr 01 15 characters of editable text Signal source No selection Any digital value that should be linked...

Страница 136: ...n switch between 16 different programs BCD Signal 2 No selection 2nd BCD digital value Digital selector BCD Signal 3 No selection 3rd BCD digital value Digital selector BCD Signal 4 No selection 4th B...

Страница 137: ...ion settings Description Alarm type Off Alarm switched off Alarm A message will be entered in the alarm list depending on the signal level that has been set Event A message will be entered in the even...

Страница 138: ...or example the measured values of analog input 1 and 2 are linked to each other The dry bulb temperature and the wet bulb temperature are required for calculating the relative humidity and should be d...

Страница 139: ...with standard mathe matical rules Any number of spaces may be used within the formula symbol string Spaces are not admissible in function designations names of variables or constants Linearization Th...

Страница 140: ...00 to 100 Can be set within the limits to any value with 4 decimal places Temperature None Relative Absolute Unit Unit with up to 5 characters can be entered Decimal place Auto Automatic switching XXX...

Страница 141: ...ns are counted Time in hours The hours in which the signal was High logic level 1 are counted Time in days The days in which the signal was High logic level 1 are counted Monitoring signal No selectio...

Страница 142: ...input using the COPY button The settings can be copied to another external input using the COPY button Setup dialog box Parameters Parameter Selection settings Description Channel descrip tion ext DE...

Страница 143: ...arameters Parameter Selection settings Description Description Ext AI 01 Temperature None Relative Absolute Comma format Auto Automatic switching XXXXX No decimal place XXXX X 1 decimal place XXX XX 2...

Страница 144: ...9 In the event of deviation below the limit values an alarm event will be entered Minimum alarm text Underrange Ext AI 01 20 characters of editable text Maximum alarm Off Alarm switched off Alarm A me...

Страница 145: ...they will appear here Setup dialog box Parameters Parameter Selection settings Description Protocol Modbus slave ER8 Modbus master Baud rate 9600 19200 38400 Data format 8 1 no parity Min response tim...

Страница 146: ...thernet This dialog only appears if an Ethernet interface is installed in the device and it determines how the IP address is to be assigned and what the DNS server is called Chapter 15 2 Ethernet opti...

Страница 147: ...Parameters for Modbus slave Parameters for Modbus master Parameter Selection settings Description Port 0 to 502 to 1024 Parameter Selection settings Description Timeout 4000 to 5000 to 10000 Scan cyc...

Страница 148: ...ctive per default Setup dialog box Parameters Parameter Selection settings Description Activation Inactive Not activated active COM1 The external relay module is connected and activated at this interf...

Страница 149: ...e Setup dialog box Parameters Parameter Selection settings Description Function Inactive PROFIBUS inactive bus error message suppressed Active PROFIBUS active Device address 0 to 127 Device address 1...

Страница 150: ...12 Configuration 150...

Страница 151: ...er to use the full range of functions Follow the instructions on the screen 13 1 1 Hardware 500 MB hard disk space 512 MB RAM 13 1 2 Software requirements Microsoft Windows XP Microsoft Windows 7 32 o...

Страница 152: ...not yet been connected The following possibilities are available for connecting the device Via USB device interface USB connection established Step Activity 1 Connect USB interfaces between the devic...

Страница 153: ...ram The USB host socket is used for this purpose This means that devices with identical firmware versions can be easily duplicated Step Activity 1 Connect Ethernet socket on the device with LAN socket...

Страница 154: ...13 Configuration in setup program only 154 13 3 Connection diagram The rear side of the device is shown here with all the fitted hardware components that the setup program has detected...

Страница 155: ...3 4 Country settings Additional device languages can be created or edited here For example French can be se lected as a 2nd language from the current library and transferred to the device 13 5 User li...

Страница 156: ...setup program These documents can contain texts graphics and JavaScript code Analog and digital values for the device can be displayed with JavaScript The result is a website which can be retrieved o...

Страница 157: ...alues analog integer and digital values and text are written to the selected variables from the received Mod bus telegram and are available for use in the system Each frame can be used to configure up...

Страница 158: ...ite end The process values analog in teger and digital signals and text are written to the frames by the system and are available to external devices Each frame can be used to configure up to 64 entri...

Страница 159: ...3 Configuration in setup program only 13 11 PROFINET RT If the device is equipped with a PROFINET RT interface class B up to ten slots can be config ured See PROFINET interface description Setup dialo...

Страница 160: ...the linearized value temperature in C for example Setup dialog box Parameters The definition range of linearization measured values x axis is monitored in the module and delimited as follows Lower li...

Страница 161: ...se this button to calculate a polynomial that describes the pro gression of the linearization characteristic line The calculated coefficients are incorporated into the formula The characteristic lines...

Страница 162: ...termined by the measuring range start and measuring range end values y values it can be temporarily changed in the display by en tering different x values Example of 3rd order polynomial Meas range en...

Страница 163: ...objects at the bottom of the list are covered by those at the top If a particular object is problematic it can first be set to VISIBLE NO Preview In the list on the right hand side the position for s...

Страница 164: ...me of the process screen 7 Select background color 8 Navigation and editing functions 9 10 Exit process screen editor settings are not adopted 11 Exit process screen editor settings are adopted 12 Pre...

Страница 165: ...the background image must not cov er the entire area of the process screen or it must be transparent option when replacing a screen Example A furnace whose temperature is regulated via an thyristor p...

Страница 166: ...3 Configuration in setup program only 166 Select the new furnace screen click Transparent and it will appear in the list of screens Once Active is ticked the background image will appear in the previe...

Страница 167: ...Integer signal from the integer selector Digital signal from the digital selector Text Text from the process or configuration selector Frame Transparent border Rectangle Rectangle with color fill and...

Страница 168: ...coordinate of the upper left corner of the object in the process screen Y position 0 to 20 to 402 Y coordinate of the upper left corner of the object in the process screen Width 1 to 50 to 635 Width...

Страница 169: ...Preview screen Transparent Yes No If Yes the background color of the object is not active Instead the font will be displayed in front of the background color of the process screen Frame form Select f...

Страница 170: ...s screen 13 13 6 Transferring the process screen to the device As soon as the setup file has been transferred to the device it can be retrieved in the operating loop Button Function Select foreground...

Страница 171: ...contact on the adhe sive touchscreen cover In this case the touchscreen must be calibrated DEVICE MENU CALIBRATE TOUCHSCREEN To do this 4 points on the screen with an x must alternately be tapped as a...

Страница 172: ...14 Special functions 172...

Страница 173: ...easurement de viates from the displayed value The amount of deviation is different at the upper and lower measuring points meaning that measured value offset is not suitable Actual zero point 15 C low...

Страница 174: ...e temperature to 80 C 4 Enter the display value as the actual end value and the reference value as the set end val ue Example Enter 70 and 80 Characteristic line The following diagram shows the change...

Страница 175: ...ually here if necessary it should be requested from the administrator responsible Subnet mask 0 0 0 0 to 255 255 255 0 to 255 255 255 255 Manual setting of the subnet mask Standardgateway 0 0 0 0 to 2...

Страница 176: ...he connected PC or entered manually Setup dialog box 15 4 Screenshot A screenshot of the current device can be created here and saved as a bitmap Setup dialog box 15 5 Deleting the measurement data me...

Страница 177: ...ctivity 1 Connect device to the PC using the USB or LAN 2 Click on ENABLING OF EXTRA CODES 3 Generate code number and click Next 4 Select the required extra codes and click Next 5 Code number appears...

Страница 178: ...ing calibration This area shows the dialogs for calibration and testing of analog and digital outputs as well as other device functions Setup dialog box 15 8 Different process values Values can be rea...

Страница 179: ...software tool per default The program s essential tasks include Monitoring and documenting the optimization or autotuning phase Triggering of a setpoint value step change for recording and determining...

Страница 180: ...15 Online parameters 180...

Страница 181: ...ower limit for a bar graph display The numeric representation is independent of the display start end and is produced over the entire measuring range In the recording measured values small er than the...

Страница 182: ...16 Error and alarm messages 182...

Страница 183: ...uirements regarding changes to an electrical device must be observed 1 Identify the module from the part number on the sticker attached to the packaging 2 Check which slot the optional board may be in...

Страница 184: ...this example a universal analog input is inserted in slot In10 Step Activity 1 Disconnect screw terminals connected at the rear and connected interface cables 2 Loosen 2 screws at bottom do not remove...

Страница 185: ...th the associated toothed lock washers and screw in the side screw again to ensure a conductive connection between the back panel and the side panel secure grounding 6 Switch on the device again and c...

Страница 186: ...V max 30 mA 00581165 Two logic outputs DC 0 12 V max 20 mA 00581168 One solid state relay AC 230 V 1 A 00581164 Two solid state relays AC 230 V 1 A for motor actuator 00621574 Two PhotoMOS relays1 DC...

Страница 187: ...187 18 Approvals approval marks 18 1 GL...

Страница 188: ...18 Approvals approval marks 188...

Страница 189: ...189 18 Approvals approval marks...

Страница 190: ...18 Approvals approval marks 190...

Страница 191: ...191 18 Approvals approval marks...

Страница 192: ...18 Approvals approval marks 192...

Страница 193: ...193 18 Approvals approval marks 18 2 DIN...

Страница 194: ...18 Approvals approval marks 194...

Страница 195: ...195 19 China RoHS 3URGXFW JURXS D DUGRXV VXEVWDQFHV 3E J G U 9 3 3 RXVLQJ HKlXVH 3URFHVV FRQQHFWLRQ 3UR HVVDQVFKOXVV 1XW 0XWWHU 6FUHZ 6FKUDXEH d d d K d K d y d y d...

Страница 196: ...Q HOLYHU DGGUHVV 0DFNHQURGWVWUD H XOGD HUPDQ 3RVWDO DGGUHVV XOGD HUPDQ 3KRQH D PDLO PDLO MXPR QHW QWHUQHW ZZZ MXPR QHW 802 RXVH 7HPSOH DQN 5LYHUZD DUORZ VVH 0 8 3KRQH D PDLO VDOHV MXPR FR XN QWHUQHW Z...

Отзывы: