3 Technical data
3
Technical data
Temperature range
902454/10
0 to 120 °C
902454/11
0 to 120 °C
902464/10
0 to 120 °C
The maximum operating temperature of the thermowells must be observed.
Protection type
IP65 (as delivered condition)
Temperature difference
Minimum
3 K
Maximum
120 K
Maximum pressure
902454/10
PS25 for a water flow velocity of 2 m/s
902454/11
PS25 for a water flow velocity of 2 m/s
902464/10
With thermowells basic type 902440/47, 902440/48 and 902440/49
PS40 for a water flow velocity of 2 m/s
Electrical connection
2-wire circuit, 4-wire circuit
Maximum measuring current
The maximum measuring current is calculated using the maximum admissible
power loss of 5 mW.
Depending on the nominal values, this results in the following effective current
values:
Pt100: 1783 µA
Pt500: 797 µA
Pt1000: 564 µA
Response times
902454/10
t
0.5
= 5 s; t
0.63
= 7 s; t
0.9
= 12 s;
902454/11
t
0.5
= 5 s; t
0.63
= 7 s; t
0.9
= 12 s;
902464/10 without thermowell
t
0.5
= 5 s; t
0.63
= 7 s; t
0.9
= 12 s;
902464/10 with thermowell
902440/47
t
0.5
= 10 s; t
0.63
= 14 s; t
0.9
= 27 s;
902464/10 with thermowell
902440/48
t
0.5
= 11 s; t
0.63
= 15 s; t
0.9
= 28 s;
902464/10 with thermowell
902440/49
t
0.5
= 12 s; t
0.63
= 16 s; t
0.9
= 32 s;
Minimum immersion depth
30 mm
Nominal value
Pt100, Pt500, Pt1000 (see identification marking for temperature probes)
Tolerance
Class B according to DIN EN 60751:2009 / IEC 60751:2008; restricted toler-
ances optional
When using two-wire technology, the display will be systematically higher due
to the line resistance (see maximum connection length according to
DIN EN 1434).
Содержание 902454/10
Страница 2: ......
Страница 4: ...Contents...
Страница 6: ...1 Safety information 6...
Страница 8: ...2 General information 8...
Страница 10: ...3 Technical data 10...
Страница 16: ...4 Installation 16...
Страница 18: ...5 Maintenance 18...
Страница 19: ...19 6 Declaration of conformity 6 Declaration of conformity...
Страница 20: ...6 Declaration of conformity 20...
Страница 23: ......