V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
111
9 What to do, if ...
What is happening?
Cause / remedy
Info
Green Power LED is
flashing
- Display switch-off active
h
Press any key
v
Power controller is not
producing any output
power
even though the green
Power LED
is lit and a setpoint value
has been set.
- Parameters have been changed in the
configuration level but not completed.
h
Leave the configuration level by pressing
EXIT and wait for a restart.
-
- Wire break at the analog input or incor-
rect analog input wiring
v
Chapter 3.3 "Con-
nection diagram"
- Setpoint value configuration incorrectly
configured, e.g. set via interface.
v
Chapter 5.1.4
"Setpoint value
configuration"
- Input for firing pulse inhibit active
A padlock symbol is shown as the operating
mode in the info line.
Undo connection between screw terminal 7
and 8 at terminal X2_2.
v
Chapter 4.1.2 "Ap-
pearance of mea-
sured values"
- Load break
h
Check load and load connections
v
Chapter 8 "Error
messages and
alarms"
Fuse LED is lit
- Semiconductor fuse defective due to
short circuit in power section
h
Remedy short circuit in the load or load
circuit
h
Fit a new semiconductor fuse
v
Chapter 8.2 "Re-
placing a defective
semiconductor
fuse"
Power controller is pro-
ducing power even
though no setpoint value
(output level) is specified
by the controller.
- Configuration problem:
Controller output signal set to 4 to
20 mA and current set to 0 to 20 mA at
analog input of power controller.
h
Check configuration and select same
standard signals for the controller and
power controller.
v
Chapter 5.1.3 "An-
alog inputs"
v
Chapter 5.1.4
"Setpoint value
configuration"
- Power controller in manual mode
h
Exit manual mode by pressing EXIT
v
- Base load settings selected
h
Check settings for base load settings
v
- Thyristor short circuit
v
Содержание 709061/8-01-020
Страница 16: ...1 Introduction 14 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Страница 22: ...2 Mounting 20 V1 04 EN 00561071 Thyristor Power Switch TYA 201 TYA201 100A TYA201 150 200A ...
Страница 23: ...V1 04 EN 00561071 Thyristor Power Switch TYA 201 21 2 Mounting TYA201 250A ...
Страница 46: ...3 Electrical connection 44 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Страница 56: ...4 Operation 54 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Страница 78: ...5 Configuration 76 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Страница 96: ...6 Special device functions 94 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Страница 112: ...8 Error messages and alarms 110 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Страница 120: ...10 Technical data 118 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Страница 124: ...11 Certificates 122 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...