V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
69
5 Configuration
Ext. current limiting
Note:
This function can only be selected with the following
presettings:
Option 1:
Power controller
r
Operating mode
r
Phase angle control
and
Power controller
r
Current limiting
r
Yes
Option 2:
Power controller
r
Operating mode
r
Pulse groups
Power controller
r
Soft start
r
Yes
Power controller
r
Current limiting
r
Yes
If, for example, "Digital input 1" is selected here, the "External
current limit value" (further down in the table) takes effect
when the digital input is closed instead of the current limit val-
ue selected under "Power controller rCurrent limit value".
Switched off
No ext. current limiting
Digital input1
Ext. current limiting is controlled by digital input1
Digital input2
Ext. current limiting is controlled by digital input2
Ext. digital input1
Ext. current limiting is controlled via an interface
Ext. digital input2
Ext. current limiting is controlled via an interface
Ext. current limit
value
10 % to max. load
current of the
device +10 %
Note:
This parameter is only available if a digital input is selected for
ext. current limiting.
The max. load current varies depending on the device type.
For 20 A power controllers, 2 to 22 A can be selected.
v
Key lock
Switched off
No key lock
Digital input1
Key lock is controlled by digital input1
Digital input2
Key lock is controlled by digital input2
Ext. digital input1
Key lock is controlled via an interface
Ext. digital input2
Key lock is controlled via an interface
External switch-off
of display lighting
Switched off
No external switch-off, i.e. the background lighting
behaves according to the configuration in Chapter 5.1.1
Digital input1
Switch-off is controlled by digital input1
Digital input2
Switch-off is controlled by digital input2
Ext. digital input1
Switch-off is controlled via an interface
Ext. digital input2
Switch-off is controlled via an interface
Inhibit input con-
trol direction
The firing pulse inhibit can be triggered when the switching
contact is closed or open.
v
Chapter 3.3 "Connection diagram"
Value / settings
Description
k
/ bold = default setting
Содержание 709061/8-01-020
Страница 16: ...1 Introduction 14 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Страница 22: ...2 Mounting 20 V1 04 EN 00561071 Thyristor Power Switch TYA 201 TYA201 100A TYA201 150 200A ...
Страница 23: ...V1 04 EN 00561071 Thyristor Power Switch TYA 201 21 2 Mounting TYA201 250A ...
Страница 46: ...3 Electrical connection 44 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Страница 56: ...4 Operation 54 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Страница 78: ...5 Configuration 76 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Страница 96: ...6 Special device functions 94 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Страница 112: ...8 Error messages and alarms 110 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Страница 120: ...10 Technical data 118 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...
Страница 124: ...11 Certificates 122 V1 04 EN 00561071 Thyristor Power Switch TYA 201 ...