3 Functions
20
3.4
Data acceptance after writing
Since a maximum of 6 words can be written to the instrument in one
protocol, it is conceivable that inconsistent configuration data are
written to the instrument.
In order to achieve consistent data sets in the instrument, the received
data are initially just stored, but not applied.
The stored data will only be completely accepted and thus effective
after the acceptance flag has been set at the end of a transmission.
The data acceptance flag is set at the end of a transmission by writing
any value to the address 0x0050 = 80dec.
Example
After writing any data...
Instruction:
Response (as instruction):
01
06
00
50
00 1
481B
01
06
00
50
00 1
481B