9
2 Safety requirements and installation instructions
2.6
Safety data according to ATEX
Repeater power supply amplifier operation
Input isolating amplifier operation
2.7
UL note
The safety requirements resulting from the UL approval are included in the "Control Drawing". The "Con-
trol Drawing" is part of the package leaflet.
Max. output voltage U
o
25.2 V
Max. output current I
o
93 mA
Max. output power P
o
587 mW
Max. external inductance L
o,
max. external capacitance C
o
Simple electrical circuit IIB: 4 mH/820 nF
Simple electrical circuit IIC: 2 mH/107 nF
Safety-related maximum voltage
U
m
Supply terminals
AC/DC 253 V
Output terminals
AC 253 V, DC 125 V
Max. voltage U
i
≤
30 V
Max. current I
i
≤
150 mA
Max. internal inductance L
i
Negligible
Max. internal capacitance C
i
Negligible
Safety-related maximum voltage
U
m
:
Supply terminals
AC/DC 253 V
Output terminals
AC 253 V