background image

12

3. TRANSPORTATION, INSTALLATION AND STARTUP

3.1. Transportation

It is forbidden to transport the equipment in any position other than vertical. During transportation, the equipment must be properly 

secured and packed to prevent any movement or impact inside the vehicle, protected from the weather (direct sunlight, rain, snow, etc.). 

Manufacturer supplies upright cabinets protected by cardboard corners and film.

ATTENTION! It is forbidden to connect upright cabinets to the power supply within at least 2 hours after it has been transported 

and installed.

3.2. Storage of the Equipment

Upright cabinets should be stored vertically. It is forbidden to store units under direct sunlight or influence any other atmospheric 

phenomena.

3.3. Requirements to the Place of Operation

It is necessary to install the upright cabinet in a dry, ventilated room at the distance no less than 10 cm away from the nearest wall. There 

should be good airflow around the compressor unit. It is also necessary to install an upright cabinet away from any equipment source of heat 

and conditioners/ventilators.

The upright cabinet should be installed away from direct sunlight or any other atmospheric phenomena. Make sure that voltage and 

frequency in the electricity grid correspond to those recommended by the manufacturer. 

3.4. Installation

• Unpack the unit, remove the protective film and cardboard corners;

• Install the unit on a solid surface and adjust the horizontal position of the cabinet with the levelling supports.

ATTENTION! Make sure to install the upright cabinet with the inclination of min. 20° degrees to the rear side.

The cabinet is supplied to the buyer partially disassembled. After transportation and installation of the unit, please follow the next steps:

• I. Fix shelf holders in perforated rack straps. 

• II. Place the grid shelves on the fixed holders. 

The first cleaning of the unit should be done after unpacking and/or its first launching. For cleaning use only warm water (no more than 

40°C) with neutral detergents. Do not use any cleaning agents that contain chlorine and sodium of different types as they can damage the 

protective layer and components of the unit. Any residue of adhesive or silicone on metal elements of the equipment should be removed only 

with extraction gasoline (it is not applied to plastic elements!). Do not use any other organic solvents!

ATTENTION! Upright cabinet shall not be cleaned with a water jet, use only a damp cloth. After transporting and installation 

of the equipment, wait for about 2 hours before its launching.

ATTENTION! Make sure not to damage the refrigerant circulation circuit!

Содержание ND140M

Страница 1: ......

Страница 2: ...the Electronic Controller s Display 16 4 4 2 Setting of the Temperature 16 4 4 3 Warning Signals 16 4 5 Electronic controller Dixell 17 4 5 1 Display 17 4 5 2 Checking the set temperature 17 4 5 3 Ch...

Страница 3: ...ose air inlets on the body frame of the equipment Disconnect equipment from voltage before any maintenance operation Any kind of works connected with refrigeration or electric systems shall be carried...

Страница 4: ...22 C at ambient temperature 16 C 25 C and relative humidity up to 60 Upright cabinets are equipped with a built in compressor which is located at the top SD70M VD70M ND70M NG60G and in the bottom VD7...

Страница 5: ...3 Cabinet door 4 Shelf support 5 Grid shelf 6 Levelling supports 7 Compressor department Picture 1 Upright Cabinet VD75G ND75G 1 Electronic controller temperature control 2 Cabinet control panel swit...

Страница 6: ...t control panel switches 3 Cabinet door 4 Shelf support 5 Grid shelf 6 Levelling supports 7 Compressor department Picture 3 Upright Cabinet NG60G 1 Cabinet control panel temperature control switches 2...

Страница 7: ...el switches 3 Cabinet door 4 Shelf support 5 Grid shelf 6 Levelling supports 7 Compressor department Picture 5 Upright Cabinet VG60G 1 Electronic controller temperature control 2 Cabinet control panel...

Страница 8: ...witches 2 Cabinet door 3 Shelf support 4 Grid shelf 5 Levelling supports 6 Compressor department Picture 8 Upright Cabinet VD140M ND140M 1 Cabinet control panel switches 2 Cabinet door 3 Shelf support...

Страница 9: ...0 27 0 27 0 27 0 27 0 55 0 55 0 5 0 5 CO2 EQ t 0 58 1 06 0 58 1 06 0 58 1 06 1 18 2 16 1 07 1 96 Current consumption 3 2 2 5 3 3 4 3 3 4 Electric power consumption kW 24h 6 0 3 0 8 5 4 8 13 9 Climate...

Страница 10: ...27 0 27 0 12 0 05 CO2 EQ t 0 58 1 06 0 58 1 06 0 00 0 00 Current consumption 2 5 3 6 3 3 2 3 Electric power consumption kW 24h 6 0 10 0 11 0 3 52 Climate class 7 4 Ambient temperature range 16 35 16...

Страница 11: ...2 0 59 0 00 Current consumption 0 7 0 8 1 1 94 1 94 1 6 Electric power consumption kW 24h 1 6 2 2 4 0 6 0 6 0 4 9 Climate class 3 4 Ambient temperature range 16 25 16 30 Operating temperature range 2...

Страница 12: ...age and frequency in the electricity grid correspond to those recommended by the manufacturer 3 4 Installation Unpack the unit remove the protective film and cardboard corners Install the unit on a so...

Страница 13: ...ghting switch 3 Main switch turns on off the unit 3 5 Connecting Electricity and Startup The device should be connected to a separate properly mounted electrical circuit with a grounding socket The sy...

Страница 14: ...inside the upright cabinet Do not store beverages in bottles and cans especially carbonated beverages in the freezer chamber The cans and the bottles may explode Do not store explosive substances such...

Страница 15: ...when the defrosting function is turned on It is blinking when defrosting start is delayed by external disengagement or when another procedure is in progress Diode d Alarm the symbol is visible when t...

Страница 16: ...the last pressure of the button the Loc code is displayed for 1 second To unlock press any button while holding it for 4 seconds UnL code will be displayed for 4 seconds Turning on off of the equipme...

Страница 17: ...e door is opened the controller starts counting down the time blocking the operation of the air cooler fan After this time expires the alarm is started and the dA signal is blinking on the display dur...

Страница 18: ...dirty condenser leads to reduced cooling capacity overheating of the refrigeration unit and even damage to the compressor ATTENTION The condenser needs to be cleaned at least once a month Clean the c...

Страница 19: ...ATION AND REPAIR In case of any problems during the startup of the equipment or its operation it is necessary to return to those sections of the service manual that explain their operations This aims...

Страница 20: ...vice do not vibrate when the compressor is working Internal elements have been properly mounted Dirty condenser alarms cht CHt cht pre alarm indicating that condenser is dirt cht is shown on the displ...

Страница 21: ...a high relative humidity more than 60 is a natural phenomenon and does not require a call to the service centre If after verifying the items described in this section the equipment does not work prope...

Страница 22: ...ctions if there has been any disaster or in other standard insurance cases which led to an inability to use the equipment flood fire accident etc and in any other circumstances which are not under sel...

Страница 23: ...Warranty card Product and model Date of sale Serial number Warranty period Seller s signature Buyer s signature The buyer confirms the technical serviceability of the product...

Страница 24: ......

Отзывы: