Carefully remove the protective cover from the control unit of the JUDO JUDOMAT DX water
softening system.
Undo the 4 screws and take the operating front panel off from the housing.
Carefully break out the cable lead-through on the rear of the housing, fit a suitable cable gland and
insert the connection cable.
Using a suitable plug type cable terminal, connect the free connector of the bottom microswitch (NC)
(see Fig. 10).
Using a suitable wire splice connector, splice the 12VAC power supply to the brown connecting wire
of the input lead (rear side of the PCB, 4th connection from the left) (see Fig. 11).
Correctly refit the operating front panel and attach the protective cover.
5
Description of the control unit
5.1
Display and control elements
Fig. 12: Display and control elements
Element
Function
Power LED (green)
Illuminates if the control unit is supplied with power and switched on
RUN LED (yellow)
Illuminates if input IN1/IN2 is connected
Active alarm LED (yellow) Illuminates if programmed time is exceeded (fault indication)
Toggle switch
Switch on/off of the control unit, acknowledgment of the fault indication
Tab. 4: Display and control elements