- 8 -
Flexible Sheath Resistance and Thermocouple Temperature Sensors FlexiTEMP
®
60
TC with head MA
BK - black
GN - green
PK - pink
4.1.5 Examples of mounting of the sensors in
operation
Sensors without thermowell, respectively protective tube,
fixing shift pipe union
4.2 Operation and maintenance
The products do not need any operation and maintenance.
It is recommended to check the mounting of the sensor at
preselected intervals.
To ensure metrological parameters of the sensors, periodic
checks of calibration parameters must be performed. Period
of calibrations is set by the user and it is based on operating
conditions and internal metrology regulations. Manufacturer’s
recommended period is 12 months. If there is during the
calibration found calibration difference from the expected
metrological parameters, it is necessary to replace the sensor.
5. Product specifications
5.1 Technical specifications
Resistance sensors type
T1060
Measuring resistor (RTD):
1xPt100, accuracy class A, B according to EN 60751
inside wiring: two-wire, four-wire, outer diameter of stem
3 and 6 mm
2xPt100, accuracy class A, B according to EN 60751,
inside wiring: two-wire, three-wire, four-wire, outer
diameter of stem 3 and 6 mm
Measuring range:
-200 to +700 °C (accuracy class B)
-100 to +450 °C (accuracy class A)
Measuring current:
recommended
0.1 to 1.0 mA
maximal
3 mA
Output signal:
resistance
Electrical insulation resistance:
min. 100 M
Ω
according to EN 60751,
at temperature (20 ±15)°C, max. 80 % relative humidity
Thermocouple sensors type T1560
Thermocouple (TC):
1x / 2x “J“, “K“, “N“,
accuracy class 1 (not for type N with code KV), 2
according to EN 60584-1, EN 60584-3
Measuring range:
-200 to +800 °C (“J“)
-200 to +1300 °C (“K“, “N“)
Output signal:
voltage
RD
RD
RD
RD
RD
+
–
BK
+
–
GN
+
–
PK
+
–
BK
BK
–
+
+
–
GN
GN
–
+
+
–
PK
PK
–
+
RD
RD
RD
RD
RD
+
–
BK
+
–
GN
+
–
PK
+
–
BK
BK
–
+
+
–
GN
GN
–
+
+
–
PK
PK
–
+
1xJ
2xJ
1xK
1xN
2xK
2xN