ALARM RELAY CIRCUIT: (Optional for both MusterWire LHD and LOP systems)
This circuit connects to voltage free relay terminals inside the Alarm Panel. This relay is energised when a fire is detected
and the contacts can be used for connecting to other systems such as telemetry or external fire alarms. This circuit can be
set to Normally Open or Normally Closed (see SETUP).
SHUTDOWN RELAY CIRCUIT: (Optional for both MusterWire LHD and LOP systems)
This circuit connects to voltage free relay terminals inside the Alarm Panel. This relay is energised after the required delay
on detection of a fire and can be used in conjunction with a suitable contactor to shut down the machine or vehicle. This
circuit can be set to Normally Open or Normally Closed (see SETUP).
(For reliable operation especially on normally open circuits it is advisable to test that these limits are not exceeded)
FUSES
There are five fuses located on the mezzanine board in the base of the Alarm Panel. These fuses are all rated 2 Amps and
serve to protect the Alarm Panel from incorrect wiring or overloading of the relay circuits. It is advisable to test all circuits
connected to the relays after installation to ensure they are correctly wired and do not exceed the ratings of the contacts
or fuses. The relay circuits are not monitored for faults.
PURPLE
&
GREY
no polarity
max 1 Amp, 30V DC
ORANGE
&
RED
no polarity
max 1 Amp, 30V DC
Fuse Pack of 10 (M2FP01)
Use of proper safety wear and tools is highly recommended
to help prevent injury to self and damage to the equipment.