background image

Unit Positioning

Installation 

Position the HumEvap Mobile 

Plus

close to the electrical and water

supply in such a way that air inlet and outlets are not blocked. 

Do not position the unit directly against a wall.

Do not position the humidifier near sensitive furniture, paintings or

other objects, that might be damaged by excessive humidity.

If possible locate the unit in the middle of the room.

Keep out of reach of children!

Make sure humidifier is in a safe position and cannot fall over or be
pushed and damaged accidentally.

Mechanical Installation:

- Check Water Reservoir for any leaks or damage.
- Check Evaporator Cassette is properly located in the reservoir.

Electrical Installation:

- Before using the unit extend the power cable and inspect for any    

signs of damage.

- Check the plug and socket for any damage. 

- Always use an earthed 230V, 50Hz 13 amp power socket.

- Make sure Fan Switch is in OFF (0-position).

- Make sure the power socket is in the OFF position.

- Plug the humidifier power cable into the power socket. 

- Before filling ensure the unit is disconnected from the power    

supply

-   For additional safety the installation of a high sensitivity circuit 

breaker (RCD) rated at 30mA is recommended.

Running the Unit:

-  To check the unit’s operation turn the Fan Switch to i ii or iii 

and increase the Humidity Control until it runs.
Cool air should discharge from the Supply Grilles.

Please Note: Unit will not run if there is insufficient water in the Water
Reservoir.  The ‘Water Low’ indicators should be lit if this is the case. 

HumEvap Mobile 

Plus

Humidifier

Installation 

Unit Positioning and Installation

2

Warning!  This humidifier must be installed, operated and maintained in

accordance with this manual. Failure to do so could result in

contamination that might cause Legionnaires’ disease, which can be fatal.

Содержание HumEvap Mobile Plus

Страница 1: ...t in contamination that might cause Legionnaires disease which can be fatal WARNING Failure to maintain this humidifier as recommended in this manual will invalidate warranty JS Humidifiers plc Artex...

Страница 2: ...oP in reducing the risk of legionellosis To prevent the growth of legionella users are required to Carry out a risk assessment of the water system by a competent person and implement a monitoring and...

Страница 3: ...tificates iii Technical Specification iv Principle of Operation v Operating Parameters 1 Unit Positioning and Installation 2 Water Supply 3 Routine Maintenance 4 Maintenance Frequency 5 Replacement of...

Страница 4: ...ies Year of Manufacture JS Humidifiers plc Artex Avenue Rustington LITTLEHAMPTON WEST SUSSEX UK BN16 3LN Tel 01903 850200 HumEvap Mobile Plus Humidifier HumEvap Mobile Plus Series 1 00 2006 HumEvap Mo...

Страница 5: ...p Mobile Plus to ensure hygienic trouble free operation This water supply MUST be checked regularly to ensure there is no microbiological build up within the building s water supply This is particular...

Страница 6: ...alised water in the water reservoir is used to moisten the Evaporator Cassette Air drawn from the room through the Air Care filter travels through the wetted evaporator cassette and absorbs water as i...

Страница 7: ...Use to set Fan speed to I II or III To switch the humidifier OFF turn to 0 position The Orange lights will illuminate independantly when the water level in each water tank is low When both lights illu...

Страница 8: ...any damage Always use an earthed 230V 50Hz 13 amp power socket Make sure Fan Switch is in OFF 0 position Make sure the power socket is in the OFF position Plug the humidifier power cable into the powe...

Страница 9: ...ontrol panel of the humidifier Wipe water off with a dry cloth before starting the humidifier It is essential that clean water is supplied to the unit to ensure hygienic trouble free operation The wat...

Страница 10: ...e every 3 months or before if any of the following symptoms occur Odours Heavy soiling or scaling Reduced humidifacation permormance HumEvap Mobile Plus Humidifier Maintenance Routine Maintenance Warn...

Страница 11: ...is 100 biodegradable Always wash hands after handling Do not use solvents or other aggressive liquids for cleaning Do not use scouring materials wire brush or scouring cloth etc for cleaning they lea...

Страница 12: ...n humidity set point turned to maximum and fan switched to i ii and iii 1 As for daily inspections plus 2 Check operation of the Water Tank low level float switch 3 Check cleanliness of air filter 1 A...

Страница 13: ...reduce bacterial contamination of the water This Stick requires replacing every three months to ensure proper bacterial control The Ionic Stick is located in the water reservoir underneath the Evapora...

Страница 14: ...tenance Troubleshooting Spares 8 Flush reservoir and place a Disifin tablet into the reservoir and allow to dissolve Check and switch ON Raise Humidity Control level if necessary Turn Fan switch to Hi...

Страница 15: ...obile Plus Humidifier Installation Instruction Manual Version 1 00 JS Humidifiers plc June 2006 All rights reserved No parts of this publication may be reproduced without the express consent of the pu...

Отзывы: