WARNING
IMPROPER ADjUSTMENT OF DASh
POT WILL RESULT IN FAILURE OF
FIRE CURTAIN TO CLOSE PROPERLy.
n
CLOSINg DASh POT vALvE TOO FAR may cause
curtain to stop before reaching floor and will
impose greater shock loads to system and
building structure.
n
LEAvINg vALvE TOO FAR OPEN will allow curtain
to crash into floor or travel final distance faster
than local codes allow.
Refer to instructions on reverse side for proper
adjustment procedure.
See reverse side for installation instructions.
Fire Safety Curtain Dash Pot
016-410L/016-411L