JOVYATLAS
UPS-division
Operating manual
POWERMASTER
M
MIL BAX 3330E page 6
4.
Technical data
POWERMASTER
S 1000-7-115
Input Voltage
115V (80V ... 138V)
Input power factor
cos
φ
: 0,98
Frequency
50Hz / 60Hz ±5%
Current at 115V
12,4A
Required fuse
C20A
C-Automatic
Battery voltage
36V
Output power
1000VA
Affective power
700W
Efficency INV
85%
Output voltage
115V (sinuswave)
Output power factor
cos
φ
: 0,7
Frequency
50Hz / 60Hz ±0.5%
Distorsion
< 3% (at linear Load)
Overload capability
>105% for 10s /> 130% for 300ms
Crest Factor
3 : 1
Operation mode
Online
Signalisation
Data processing interface
Radio interferance
degree
Acc. EN 50091-2 : 1994 Klasse B
According to the rules
of
CE, EN, IEC, VDE
Loudness
< 45 dBA
Temperature
0°C ... 55°C
If temperature is exceeding 55°C the ups will switch to bypass, the load is now not
buffered by battery
Humidity
Max. 95% non condensing
Dimension (mm)
Width
Height
Depth
483 (19-Inch)
131
404
Weight (kg)
(incl. Battery)
22