3.2.5
Audible alarms
Battery discharging:
One short tone sounds every 5 seconds
When battery close to depletion:
Two short tones sounds every 5 seconds
Fault:
Continuous tone
During battery test:
No tone
4 Transport and storage
Only transport the equipment in its original packaging. Always use the appropriate transport gear.
Do not remove the original packaging until the equipment has reached its final operating destination.
Protect against falling when storing!
Store the equipment in a dry place; see also the technical data.
4.1
Storing the battery
If the UPS includes a battery or there is a separate battery unit, observe the following:
Recharging is required if the battery is stored as follows.
At approx. 20°C, every 6 months
At approx. 30°C, every 3 months
At approx. 35°C, every 2 months
More information can be found in the battery manufacturer's operating instructions.
4.2
Unpacking and setup
Keep packaging for return transports. Store it in a dry place. Set up the equipment, making sure that it cannot fall
over. Alternatively, slide it carefully into a slot designed for UPS systems.
Note that you must insert it into a slot as far as it will go.
Refer to the technical data for conditions concerning the setup location.
5 Installation
This model of UPS either comes with a battery integrated into the housing or with an external battery case.
Use the cables included in delivery to connect it.
CAUTION:
UPSs from this model series are designed for different DC-voltages (battery voltages). Always
check that the battery voltage matches the specifications before connecting an external battery
to the UPS. There is otherwise a risk of destroying individual assemblies and/or the battery. The
battery sockets and connectors have been mechanically coded to aid you in avoiding incorrect
connection.
CAUTION:
Do not connect an external battery until the UPS is being fed an input voltage. There is
otherwise a risk of overloading the battery connection.
NOTE:
PME-1000VA has its air outlet on its front side.
All other models have their air outlet on their rear.
Connect the UPS to the supply grid.
Make sure that the UPS is receiving input voltage.
If required: Connect an external battery to the UPS.
Connect consumers to the output sockets.
NOTE:
Refer to the list of electrical connections for the connection assignments; see the section on
technical data for the corresponding technical specifications.