JOSLYN

®

 JSP

TM

, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL

 

W A R N I N G !    

THE JSP SERIES WARRANTY IS VOIDED if the unit is damaged as a 

result of improper installation or the installer’s failure to verify the 

following conditions prior to installation.

 

W A R N I N G !    

HAZARDOUS VOLTAGES PRESENT:   Improper installation or 

misapplication may result in serious personal injury or damage to the 

electrical system. Read the complete installation instructions before 

proceeding with installation. Remove all power to the electrical panel 

before installing or servicing the SPD.

 

W A R N I N G ! 

   

IMPORTANT SAFETY INSTRUCTIONS:   All work must be performed 

by licensed and qualified personnel. The electrical system must be 

properly grounded in accordance with the U.S. National Electrical 

Code, state and local codes or other applicable codes for this SPD to 

function properly. This device is suitable for installation where the 

available short circuit current is 200,000 rms symmetrical amperes 

up to 600VAC or less. For countries outside of the US follow applicable 

electrical specifications for the country the unit is being used in.

 

W A R N I N G ! 

   

Check to ensure that a proper bond is installed between neutral and 

ground at the transformer upstream from all 3-Phase Wye, 3-Phase 

High-Leg Delta or Split-Phase JSP Series device (See NEC Article 250).  

If the transformer is not accessible, check the main service 

disconnect/panel for the NG bond. Lack of a proper bond will  

damage JSP Series and void the warranty.

 

W A R N I N G ! 

   

Do not HIPOT the JSP Series units or the electrical system to which 

the JSP Series unit is connected without disconnecting the JSP Series 

units conductors including phases, neutral and ground.

Guide to Installation and Assistance

Thank you for choosing the Joslyn

® 

JSP

TM 

Series Surge Protective Device (SPD) . 

We look forward to fulfilling your facilitywide surge protection needs .

Should you have questions about installing the JSP Series please  

call Joslyn

®

 Technical Support at 800.238.5000 or 804.236.3300  

Monday through Friday, 8:00 a.m. to 5 p.m. (EST). Or, email us at 

[email protected].

This manual provides guidelines for the proper installation of the JSP Series 
of devices . Proper product selection and compliance with these guidelines 
will help your new suppression system provide years of reliable service . If 
installers are unsure about the facility electrical configuration or have other 
installation-related questions, it is recommended they consult with a master 
electrician or other qualified electrical professional .

When shortcuts are taken or installation procedures are not followed, the  
JSP Series may become damaged or may not provide adequate protection . It 
is extremely important to follow these installation procedures carefully . 

 

Содержание JSP series

Страница 1: ...Surge Protective Devices Installation Operation and Maintenance Manual PN 750 0100 001 C00 JSP JSPR S U R G E P R O T E C T I O N S U R G E P R O T E C T I O N Joslyn TM TM ...

Страница 2: ...ice Configurations 5 Conductor Sizing and Routing 6 Upstream Overcurrent Protection Device 7 Mounting 8 Indoor vs Outdoor Installation 8 Conduit Openings 8 Electrical Connections 10 Connecting Form C Dry Contacts 11 Remote Monitoring 11 Verification and Power Up 12 Troubleshooting 13 Installation Assistance 13 Standards and Listings 13 Return and Warranty Procedures 13 Warranty Statement 14 ...

Страница 3: ...elta or Split Phase JSP Series device See NEC Article 250 If the transformer is not accessible check the main service disconnect panel for the NG bond Lack of a proper bond will damage JSP Series and void the warranty W A R N I N G Do not HIPOT the JSP Series units or the electrical system to which the JSP Series unit is connected without disconnecting the JSP Series units conductors including pha...

Страница 4: ...hase 2 Wire Ground JSP R xxx 1P2401 240 216 264 N A 1 Phase 2 Wire Ground JSP R xxx 1S2401 120 240 108 132 216 204 Split Phase 3 Wire Ground JSP R xxx 3Y2081 120 208 108 132 187 229 3 Phase 4 Wire Ground JSP R xxx 3Y3801 220 380 198 242 342 418 3 Phase 4 Wire Ground JSP R xxx 3Y4151 240 415 216 264 374 457 3 Phase 4 Wire Ground JSP R xxx 3Y4801 277 480 249 305 432 528 3 Phase 4 Wire Ground JSP R x...

Страница 5: ...2 Wire Figure 4 3 Phase Delta 3 Wire Figure 3 3 Phase Wye 4 Wire 30 200 AMP 3 POLE 1 CIRCUIT BREAKER JSP SERIES EARTH GROUND Xo BOND B N C A N G N G CONDUCTORS 2 FURNISHED WITH JSP SERIES A B C G N A B C 30 200 AMP 3 POLE 1 CIRCUIT BREAKER B C A N G JSP SERIES CONDUCTORS 2 FURNISHED WITH JSP SERIES A B C G A B C G EARTH GROUND Service Configurations Figures 1 5 show the electrical relationship bet...

Страница 6: ...s are required they should be sweeping bends Do not make sharp 90 bends for appearance purposes because they will severely decrease the effectiveness of JSP Series unit Binding or twisting conductors together using tie wraps or electrical tape increases the protection performance of the device The conductor length should be as short as possible to ensure the maximum level of protection Wires are m...

Страница 7: ...switch or connected directly to the bus of the panelboard or switchboard it is protecting If direct bus connection is used Joslyn recommends installing the JSP Series unit behind a disconnect switch or other disconnecting means for ease of serviceability If the SPD is connected to a dedicated OCPD a 60A breaker is recommended 30A minimum 200A maximum JSP Models Conductor size JSP 120 6AWG JSP 160 ...

Страница 8: ...adjacent studs After the drywall has been installed install Flush Mounting Plate FMP by first removing the JSPR enclosure lid Place the FMP over enclosed body Attached the FMP to the wall using the enclosed hardware kit Screw the lid back on to the enclosure body JSPR 120 160 Weight 30 lbs 13 6 kg NEMA 4 enclosures are suitable for indoor or outdoor use NEMA 4X stainless steel enclosures are suita...

Страница 9: ...gs continued Figure 6A Conduit Openings and Enclosure Mounting Dimensions JSP Dim JSP 60 80 100 JSP 120 160 JSP 200 240 300 400 H1 6 00 152 4 10 00 254 0 14 00 355 6 H2 6 75 171 5 10 75 273 1 14 75 374 7 H3 7 50 190 5 11 50 292 1 15 50 393 7 W1 6 00 152 4 8 00 203 2 12 00 304 8 W2 4 00 101 6 6 00 152 4 10 00 254 0 D 6 20 157 5 6 20 157 5 D1 4 16 105 7 D2 2 00 50 8 All measurements in inches mm W1 ...

Страница 10: ...ors Each phase conductor is labeled Phase A B or C Ensure that the conductor lengths are kept as short and straight as possible On all high leg delta systems the high leg 208V LN must be connected to the Phase B of the SPD Color coded orange according to NEC The 3 Wire Ground Delta JSP Series units do not have a neutral conductor All measurements in inches mm and pounds kg Figure 6B Enclosure Moun...

Страница 11: ...ition Models JSP120kA to JSP400kA For these models the Form C contacts must be wired by the installer See Figure 8 for the Form C contact configuration and terminal location on the monitor board The annotations on the diagram match the markings on the terminal block The installer must route the monitoring conductors to the terminal blocks on the door mounted main monitoring board Route the wires t...

Страница 12: ...on For Standard JSP units 120 160 200 240 300 and 400 or M 60 80 and 100kA and JSPR Units Verify that all Protection Available indicating lights are illuminated The Protection Available lights extinguish only upon failure of one or more phases indicating an alarm condition Audible alarm should not operate under normal conditions The audible alarm can be muted by pressing the ALARM SILENCE button w...

Страница 13: ...of Failure Service Required indicating light illuminated Desired Action from Joslyn Replace tnbpowersolutions com joslynsurge UL Listed 1449 4th Edition for Type 1 and Type 2 SPD application cUL and UL 1283 Meets Requirements for UL 96A Compliant to IEEE C62 41 1 2002 C62 41 2 2002 and C62 45 2002 NFPA 70 NEC Article 285 RoHS Compliant Standards and Listings The following standards and listings ap...

Страница 14: ...uct alteration of the Product including removal of any warning labels accidents or improper installation application operation or repair of the Product THIS WARRANTY REPRESENTS THE ENTIRE WARRANTY OF SELLER ALL OTHER WARRANTIES EXPRESS OR IMPLIED ORAL OR WRITTEN INCLUDING BUT NOT LIMITED TO THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED The liability o...

Страница 15: ...15 JOSLYN JSP TM JSPR INSTALLATION OPERATION AND MAINTENANCE MANUAL Notes ...

Страница 16: ...ation JoslynTM is a trademark of Thomas Betts International Inc Specifications are subject to change without notice Visit our website for latest revisions Thomas Betts Power Solutions 5900 Eastport Blvd Richmond VA 23231 4453 USA Tel 804 236 3300 Toll free 800 238 5000 Fax 804 236 4841 tnbpowersolutions com joslynsurge 750 0100 001 C00 081418 Model Date of Purchase Date Installed Installer ...

Отзывы: