31
Installation and Maintenance
2. Capacity charging malfunction (outdoor unit malfunction) (AP1 below is control board of outdoor unit)
Main detection point:
Ɣ'HWHFWLIWKHYROWDJHRI/DQG1WHUPLQDORIZLULQJERDUGLVEHWZHHQ$&$&E\DOWHUQDWLQJYROWDJHPHWHU
Ɣ,VUHDFWRU/ZHOOFRQQHFWHG",VFRQQHFWLRQZLUHORRVHQHGRUSXOORXW",VUHDFWRU/GDPDJHG"
0DOIXQFWLRQGLDJQRVLVSURFHVV
N
Y
N
Y
N
Y
N
Y
N
Y
Turn on the unit
and wait 1 minute
Use DC voltmeter
to measure the
voltage on the two
ends of electrolytic
capacitor
Voltage higher than 200V?
Fault with the voltage
testing circuit on
control panel AP1
Replace the control
panel AP1
Measure the AC voltage between
terminal L and N on wiring board
XT(power supply)
Voltage within
210VAC~250VAC?
Shut down the power
and repair the power
supply to restore the
range
210VAC~250VAC
power on and
restart the unit
If the fault is
eliminated?
Shut down the power and wait 20 mi
nutes; or
use DC voltmeter to measure the voltage
on the two ends of capacitor (test3), until
the voltage is lower than 20V
Check the
connection of reactor
(L in the Electrical
Wiring Diagram)
If the wiring of
reactor L is normal?
Connect the reactor
Laccording to Elec-
trical Wiring Diagr-
am correctly
Re-energize and
turn on the unit
If the fault is
eliminated?
End
Replace the control
panel AP1
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
Содержание Z Series
Страница 56: ...48 ...