Variable speed drive screen
Figure 23: Variable speed drive screen
This screen displays information pertaining to the variable speed drive.
Table 35: Display only fields
Field/LED name
Description
Motor Run (LED)
Indicates whether the digital output from the controls is commanding the motor to RUN.
VSD Fault (LED)
Indicates that the variable speed drive is reporting a fault over the communications link or
by logic low at the hardwired digital input.
Input % Full Load Amps
Displays the input current as a percentage of the job FLA value, based on the highest phase.
Input Current Limit Setpoint Displays the input current limit value in use. This value could come from a 0-20 mA, 4-20 mA,
0-10 VDC, or 2-10 VDC input in Analog Remote mode, from a PWM signal in Digital Remote
mode, from SC-Equip Gateway interface in BAS (ISN) mode, or from a locally programmed
value.
Pulldown Demand Time Left Displays the time remaining in the programmed pulldown period if the value is nonzero.
VSD Output Voltage
Displays the output voltage measured to the motor.
VSD Output Frequency
Displays the present output frequency to the motor.
Max Chiller Frequency
Displays the maximum value that the output frequency is limited to for the chiller, based on
configuration.
Input Power
Displays the total input Kilowatts measured by the variable speed drive.
Input kW Hours
Displays the cumulative amount of kilowatts used over time as the drive motor controller
operates.
Motor Harmonics
Displays the harmonics.
Output Current (RMS) - Phase
A, B, C
Displays the RMS current measured to the motor, for each phase.
VGD Position
Displays the variable geometry diffuser position as a value between 0% and 100%.
Input kVA
Displays the supply kVA measured by the VSD.
Input Power Factor
Displays the relationship between the Input Power and the Supply kVA.
Rated Motor Voltage
Displays the motor voltage rating, based on configuration.
Maximum Motor Current
Displays the maximum motor current, based on configuration.
Motor % Full Load Amps
Displays the percentage of maximum motor current presently delivered, based on highest
phase.
53
YVAM Control Center
Содержание YORK YVAM 0350
Страница 2: ...2 YVAM Control Center...
Страница 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Страница 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Страница 118: ...Figure 47 Drive logic board Callout Component Callout Component A U35 B U38 C U37 D U36 YVAM Control Center 118...
Страница 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Страница 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Страница 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Страница 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Страница 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Страница 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Страница 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...