20
Electric wiring and the application
Indoor power source and communication wiring
Control type and the switchover
Communication wire for wired controller
Indoor total
current (A)
Item
Power
cable
section
(mm
2
)
<
10
≥
10 and
<
15
≥
15 and
<
22
≥
22 and
<
27
〈100
≥ 100 and <200
≥ 200 and <300
≥ 300 and <400
≥ 400 and <600
0.3mm
2
×(3-core) shielded wire
0.5mm
2
× (3-core) shielded wire
0.75mm
2
× (3-core) shielded wire
1.25mm
2
×(3-core) shielded wire
2mm
2
× (3-core) shielded wire
2
3.5
5.5
10
23
24
27
42
20
30
40
50
20A, 30mA, below 0.1s
30A, 30mA, below 0.1s
40A, 30mA, below 0.1s
50A, 30mA, below 0.1s
Outdoor/indoor
(mm
2
)
2-core × (0.75-2.0mm
2
)
shielded wire
Indoor/indoor
(mm
2
)
Wire
length
(m)
Rated current
of overcurrent
breaker(A)
Rated current of residual
circuit breaker(A)
Ground fault interruptor(mA)
response time(S)
Communication wire section
a. Power cable and communication wire must be fixed firmly.
b. Each indoor must be grounded well.
c. When power cable exceeds the range, increase the gauge appropriately.
d. Shielded layer of communication wires must be connected together and be earthed at single
point.
e. Communication wire total length cannot exceed 1000m.
a. Shielded layer of communication wire must be grounded at one end.
b. The total length cannot exceed 600m.
a) Indoor unit can be controlled by wired controller or remote controller.
b) When installation, the installer must set the unit due to the control type and wiring type.
Switchover between wired control master/slave unit /remote control unit, set when installation:
Note:
1. In the above figure, the state in the frame is set when out of factory.
2. The indoor controlled by master/slave wired controller and the indoor controlled by
individual wired controller are all wired controlled master indoor.
3. The remote receiver is equipped with a wire which can be inserted in CN21.
wire length(m)
wire spec
wire length(m)
wire spec
Control type
SW08-[6]
signal terminal
block
A,B,C to wired
controller
Short connected
Disconnected
Disconnected
Short connected
Short connected
Disconnected
Blank
Blank
To remote receiver
ON
ON
OFF
B,C to wired
controller
A,B,C not to wired
controller
CN23
CN30
CN21
Socket
/Dip switch
Wired control
Master unit
Wired control
Slave unit
Remote control