Technical data
This section includes technical information about the unit, such as weight, dimensions, electrical
data, wiring, and sound data.
Table 3: Typical operational range
Parameter
Allowable ranges
Chilled water in
44.6°F to 77°F (7°C to 25°C)
Chilled water out
39.2°F to 60.8°F (4°C to 16°C)
Cooling water in
68°F to 98.6°F (20°C to 37°C)
Cooling water out
77°F to 107.6°F (25°C to 42°C)
Natural gas inlet pressure
0.3 psig to 4.3 psig (2 kPag to 30 kPag)
The numbers shown in Table 3 are the allowable ranges for each parameter. Not all combinations
are possible. Check with your Johnson Controls Service Center to see if your temperature
differential is possible.
Table 4: Weight for CXR
Weights - CGN
Weights - CGH
YHAU
Maximum
shipping lb (kg) Operating lb (kg) Emergency lb (kg)
Maximum
shipping lb (kg) Operating lb (kg) Emergency lb (kg)
30 CXR
6503.6 (2950)
6922.5 (3140)
9105 (4130)
6503.6 (2950)
6922.5 (3140)
9105 (4130)
40 CXR
6503.6 (2950)
6922.5 (3140)
9105 (4130)
6503.6 (2950)
6922.5 (3140)
9105 (4130)
50 CXR
6503.6 (2950)
6922.5 (3140)
9105 (4130)
6503.6 (2950)
6922.5 (3140)
9105 (4130)
60 CXR
7143.0 (3240)
7650 (3470)
10339.6 (4690)
7143 (3240)
7650 (3470)
10339.6 (4690)
80 CXR
8928.7 (4050)
9546 (4330)
12941.1 (5870)
8928.7 (4050)
9546 (4330)
12941.1 (5870)
100 CXR
9920.8 (4500)
10714.4 (4860)
14682.7 (6660)
9920.8 (4500)
10714.4 (4860)
14682.7 (6660)
Table 5: Weight for CXRM
Weights - CGN
Weights - CGH
YHAU
Maximum
shipping lb (kg)
Operating
lb (kg)
Emergency
lb (kg)
Maximum
shipping
lb (kg) *
Operating
lb (kg)
Emergency
lb (kg)
50 CXRM
6922.5 (3140)
9105 (4130)
6922.5 (3140)
9105 (4130)
100 CXRM
13845 (6280)
18210.1 (8260)
13845 (6280)
18210.1 (8260)
150 CXRM
20767.5 (9420)
27315.2 (12390)
20767.5 (9420)
27315.2 (12390)
200 CXRM
27690 (12560)
36420.3 (16520)
27690 (12560)
36420.3 (16520)
250 CXRM
34612.5 (15700)
45525.4 (20650)
34612.5 (15700)
45525.4 (20650)
300 CXRM
41535 (18840)
54630.5 (24780)
41535 (18840)
54630.5 (24780)
Note: *
CXRM is module-connected split type. The units from 50CXRM to 300CXRM are
assembled with different quantities of the 50CXRM module. The 50CXRM5 is split, so the
maximum shipping weight is for the split unit, according to
the following table
.
Table 6: Split weights
Split weights - CGN
Split weights - CGH
YHAU
Low Temperature
unit lb (kg)
High temperature
unit lb (kg)
Low temperature
unit lb (kg)
High temperature
unit lb (kg)
50 CXRM
2292.8 (1040)
2072.3 (940)
2292.8 (1040)
2072.3 (940)
Model YHAU-CGN/H-CXR(M)Double Effect Direct Fired Small Absorption Chiller-Heater
40