Hot insulation and cold insulation procedure
1. The suggested materials and their thickness for hot insulation or cold insulation are shown in
2. Use a bonding agent, iron wire, iron band, and so on, to fix the hot insulation/cold insulation
materials. Never rivet them. Do not use welding pins.
3. Make the outer cover, flanged parts, and evaporator water chamber casing easily removable to
facilitate servicing.
4. The points that require hot insulation or cold insulation are shown in Table 6.
5. The casing of the absorber and the condenser water chamber does not require hot insulation
or cold insulation. If insulation is used, make it easy to remove.
6. Install the generator insulation so that the front, sides, and rear sections can be removed
separately. All parts of the insulation on each side is removable.
Table 5: Insulating material and thickness
Hot insulation
Cold insulation
Material
Rock wool or glass wool
Polyurethane foam, polystyrene foam, or glass wool
Thickness
2 in. (50 mm)
2 in. (50 mm)
Table 6: Points requiring hot or cold insulation
Point requiring hot insulation
Point requiring cold insulation
Point that must not be heat-insulated
Generator shell
Evaporator shell
Sight glass
Drain cooler / drain piping
Evaporator water chamber case
Valve manipulator
Solution return piping
Refrigerant piping
Pressure gauge
Refrigerant blow piping
Thermometer insertion hole
Heat exchanger
Valve for vacuuming
(use a factory only)
Relay insertion hole
YHAU-C Single Effect Steam-Fired Absorption Chiller
36
Содержание York YHAU-C
Страница 2: ......
Страница 26: ...Figure 6 Fitting tir rollers to the machine YHAU C Single Effect Steam Fired Absorption Chiller 24...
Страница 33: ...Figure 11 Location of rupture disk 31 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 85: ...Figure 37 PLC and touch screen communication wiring 83 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 103: ...Figure 49 Cooling start diagram 101 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 104: ...Figure 50 Cooling stop diagram YHAU C Single Effect Steam Fired Absorption Chiller 102...
Страница 166: ...Figure 73 Steam and drain system YHAU C Single Effect Steam Fired Absorption Chiller 164...
Страница 167: ...Figure 74 Duhring diagram PTX chart F 165 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 168: ...Figure 75 Duhring diagram PTX chart C YHAU C Single Effect Steam Fired Absorption Chiller 166...
Страница 169: ...Figure 76 Specific gravity concentration F 167 YHAU C Single Effect Steam Fired Absorption Chiller...
Страница 170: ...Figure 77 Specific gravity concentration C YHAU C Single Effect Steam Fired Absorption Chiller 168...
Страница 178: ...Figure 79 Troubleshooting sequence flow chart YHAU C Single Effect Steam Fired Absorption Chiller 176...