Control  signal  wire  must  use  2-core  shielded 

cable to prevent weak-current signal interference. 

Signal  wire  and  power  supply  cable  must  be 

arranged  in  parallel  and  keep  a  distance  above 

300mm against interference. 

 

All the wires and parts shall be tested. 

 

Each  equipment  (indoor  unit  and  outdoor  unit) 

shall  be  installed  with  breaker  and  leakage 

protector. 

 

The  connecting  line  must  be  firm;  the  wire  or 

other  parts  shall  be  covered  with  hood  against 

looseness.  Looseness  may  cause  overheating, 

short circuit or fire hazard. 

 

 

Figure 

13 

 

13.2.

 

Power line connection 

 

The power supply connection for indoor unit is detailed in electric schematic diagram on electric control box. 

 

Recommended specification and model for power supply is RVV2x2.5+1x1.5. 

 

13.3.

 

Communication wire connection 

 

Figure 14 

 

The recommended model for communication wire is RVSP2X0.75 shield (2-core). 

 

Connect  according  to  the  diagram,  do  not  allow  A  and  B  polarity  connection  error,  if  not,  communication 

failure or controller damage may be caused. 

 

In  order  to  avoid  control  signal  interference,  the  signal  wire  shall  use  shielding  wire,  and  the  shielding  layer 

shall be earthed. 

 

The  signal wire  exceeding  the specific  length  may  cause air conditioner  out  of  service  due to communication 

problem: signal wire length ≤500m and total length ≤1000m. There shall be 16 signal wire branches at most. 

 

13.4.

 

Type setting 

 

Type setting is detailed in the electric schematic diagram on the electric control box. 

 

 

Содержание YORK YDHW022

Страница 1: ...VRF Air Conditioner Installation Manual FORM NO YDHW IOM EN 1212 ...

Страница 2: ...x890x215 295x890x215 Connecting Pipes Liquid Gas φ mm 6 35 9 52 6 35 9 52 6 35 12 7 Drainage Pipe φ mm 16 O D Model YDHW045 YDHW056 YDHW071 Cooling Capacity kW 4 5 5 6 7 1 Heating Capacity kW 5 6 3 7 15 Power supply 220V 50Hz Rated Power W 50 50 70 Rated Current A 0 25 0 25 0 25 Air Flow Rate m3 h 730 730 1050 External Static Pressure Pa 0 Dimension HxWxD mm 295x890x215 302x1070x220 302x1070x220 C...

Страница 3: ...ALLATION POSITION 2 4 MOUNTING PLATE FIXING 2 5 WIRING 2 6 DRAINAGE HOSE INSTALLATION 3 7 INSTALLATION OF INDOOR UNIT 3 8 PIPING CONNECTION 3 9 AIR TIGHTNESS LEAKAGE DETECTION 4 10 THERMAL INSULATION 4 11 DRAINAGE PIPE LAYOUT 5 12 SEALING OF WALL HOLE AND FIXING OF PIPE 5 13 ELECTRIC INSTALLATION 5 ...

Страница 4: ...telephone line Poor earthing may lead to electric shock accident Leakage earthing breaker must be installed If leakage earthing breaker is not installed there will be electric shock hazard or fire hazard Please arrange drainage piping according to this instruction to guarantee smooth drainage and insulate the piping in case of condensed water accumulation Improper piping may lead to water leakage ...

Страница 5: ...t with outdoor unit 4 Mounting Plate Fixing Level with line pulling method or levelling rod and guarantee the indoor unit slightly inclining to water outlet direction of defrosting tray in installation so as to facilitate to remove the condensed water Fix the mounting plate on the wall with screws Pull the suspension plate with hands after installation to confirm whether it is firm The suspension ...

Страница 6: ...6 6 1 Piping trend Cut off 1 part on the indoor unit when the piping comes out from right side Refer to Fig 7 Cut off 2 part on the indoor unit when the piping comes out from left side Refer to Fig 7 Do not overexert when breaking off pipe in order to avoid flat pipe Figure 7 7 Installation of Indoor Unit Let pipeline pass through wall hole and hang the indoor unit on the mounting plate clip the i...

Страница 7: ...for 10min coat soapy water or other foaming agent at the connection position such as weld and thread joint and observe whether there is leakage c If any leakage tighten or repair weld leaking position after pressure relief d Fill into dry compressed nitrogen again and slowly boost the pressure to 4 3MPa e Start to record the reading of pressure gauge after maintaining pressure for 6h and then reco...

Страница 8: ...wire or fuse exceeding the designated class Only use the accessories designated by the company and require the manufacturer or authorized dealer to provide installation and technical service If accessories are controlled improperly controller failure or electric shock consequence may be caused Control mainboard and transformer shielding layer must be installed with earthing wire Do not connect ear...

Страница 9: ... in electric schematic diagram on electric control box Recommended specification and model for power supply is RVV2x2 5 1x1 5 13 3 Communication wire connection Figure 14 The recommended model for communication wire is RVSP2X0 75 shield 2 core Connect according to the diagram do not allow A and B polarity connection error if not communication failure or controller damage may be caused In order to ...

Страница 10: ...7 YDHW IOM EN 1212 NONE YDHW IOM 0812 ...

Отзывы: