VRF Air-Conditioner IOM

 

 

1

1.

 

Safety Cautions 

Please  carefully  read  this  "Safety  Cautions"  before 
installing  air  conditioner  so  as  to  ensure  correct 
installation. 
The following cautions are divided into two categories, 
related  to  safety  and  of  great  importance,  please 
carefully read. 

  Warning

…Inattention  will  lead  to  death  or 

serious injury. 

  Caution

…Inattention  will  lead  to  injury  or 

machine  damage,  and  may  also  cause  serious  injury 
according to different conditions. 

 

 

Installation  operation  must  be  conducted  by 
professional  personnel.  Do  not  conduct  without 
approval. 

 

Please  install  the  air  conditioner  in  a  solid  place 
sufficient to bear the weight. 

Instable  base  may  lead  to  air  conditioner  falling 
and cause damage. 

 

Please  use  separate  circuit  for  power  supply.  The 
operation  of  all  the  electric  parts  must  be  in 
accordance  with  the  local  laws  and  specifications 
as well as this instruction. 

 

The  operation  shall  be  conducted  by  the 
electrician with professional qualification. 

Insufficient 

capacity 

or 

improper 

electric 

operation may cause electric shock or fire hazard. 

 

Use  the  specification  designated  wires;  all  the 
wires shall be connected well to make connecting 
terminal  and  wire  free  from  external  force 
drawing. 

Poor  connection  and  improper  installation  may 
cause fire hazard. 

 

Straighten out and lay flat when connecting power 
line,  remote  controller  and  wire  controller  line  so 
as  to  make  electric  parts  and  wire  slot  box  cover 
fastened down. 

 

If  any  refrigerant  gas  leakage  in  installation, 
immediately  open 

door  and  window  for 

ventilation. 

The  refrigerant  gas  will  generate  toxic  gas  when 
meeting  combustion  sources  such  as  air  heater, 
furnace and stove. 

 

Please  power  off  first  before  touching  electronic 
parts. 

 

Do not touch the switch with wet hand. 

Touching switch with wet hand may cause electric 
shock. 

 

Air conditioner must be earthed. 

Earthing  wire  shall  not  be  connected  to  gas  pipe, 
tap water pipe, lightening rod and telephone line. 
Poor earthing may lead to electric shock accident. 

 

Leakage  earthing  leakage  breaker  must  be 
installed. 

If  leakage  earthing  breaker  is  not  installed,  there 
will be electric shock hazard or fire hazard. 

 

Please  arrange  drainage  piping  according  to  this 
instruction  to  guarantee  smooth  drainage,  and 
insulate  the  piping  in  case  of  condensed  water 
accumulation. 

Improper  piping  may  lead  to  water  leakage  and 
soak household items. 

 

Air  conditioner,  power  line  and  connecting  line 
shall be far away from more than 1m at least from 
such  electrical  equipment  as  television  set  and 
radio 

to 

prevent 

from 

interference 

of 

electromagnetic wave and noise. 

 

In  the  room  equipped  with  fluorescent  lamp 
(inverter  or  quick  start  type),  the  signal 
transmission distance of the remote controller may 
not reach the preset value. 

The  indoor  machine  shall  be  away  from 
fluorescent lamp as far as possible. 

 

Installation  should  not  be  conducted  in  the 
following places: 

(a)

 

Place  where  mineral  oil  smoke  or  mist  or  steam 
is diffused, for example, kitchen. 

Plastic parts may be deteriorated and damaged. 

(b)

 

Place where there is corrosive  gas such as sulfur 
dioxide. 

Copper  pipe  or  welding  part  may  be  corroded  to 
cause refrigerant leakage. 

(c)

 

Place  which  is  close  to  the  machine  generating 
electromagnetic wave. 

Electromagnetic  wave  may  influence  the  control 
system  to  make  the  air  conditioner  incapable  of 
normally operating. 

(d)

 

Place  where  there  is  combustible  gas  leakage, 
carbon  fiber  or  combustible  dust  floating,  or 
volatile  combustible  placing  such  as  gasoline  or 
diluent. 

The  use  of  air  conditioner  in  such  places  may 
cause fire hazard. 

 

Please do not touch the fin of the heat exchanger. 

Improper  touch  may  cause  machine  damage  and 
personal injury. 

 

Please  pay  special  attention  to  product  handling. 
Do  not  handle  by  lifting  PP  strap  in  case  of  PP 
strap rupture to damage unit and harm person. 

2.

 

Before Installation 

 

Air  conditioner  shall  not  be  unsealed  before 
moved to the installation site. If it is necessary to 
unseal,  measures  shall be taken  after  unsealing to 
avoid damaging or scratching air conditioner. 

 

When  moving  the  air  conditioner  during  or  after 
unsealing, do not apply force to refrigerant piping, 
drainage  pipe  or  other  plastic  parts  in  order  to 
avoid damaging air conditioner. 

 

Before air conditioner installation, please confirm 
whether the refrigerant used for the unit is R22 or 

Warning 

Содержание York YDEC028

Страница 1: ...VRF Air Conditioner Installation Manual FORM NO YDEC IOM EN 1212 ...

Страница 2: ...cting Pipes Liquid Gas φ mm 6 35 9 52 6 35 12 7 6 35 12 7 6 35 12 7 9 52 15 88 Drainage Pipe φ mm 16 O D Model YDEC080 YDEC090 YDEC112 YDEC140 YDEC160 Cooling Capacity kW 8 0 9 0 11 2 14 0 16 0 Heating Capacity kW 9 0 10 0 12 5 16 0 18 0 Power supply 220V 50Hz Rated Power W 210 210 210 250 250 Rated Current A 0 97 0 97 0 97 1 20 1 20 Air Flow Rate m3 h 1550 1550 1550 1950 1950 External Static Pres...

Страница 3: ... Contents 1 SAFETY CAUTIONS 1 2 BEFORE INSTALLATION 1 3 SELECTION OF INSTALLATION POSITION 2 4 INSTALLATION OF INDOOR UNIT 2 5 INSTALLATION OF REFRIGERANT PIPING 4 6 INSTALLATION OF DRAINAGE PIPING 5 7 ELECTRIC CONNECTION 6 ...

Страница 4: ...ge earthing breaker is not installed there will be electric shock hazard or fire hazard Please arrange drainage piping according to this instruction to guarantee smooth drainage and insulate the piping in case of condensed water accumulation Improper piping may lead to water leakage and soak household items Air conditioner power line and connecting line shall be far away from more than 1m at least...

Страница 5: ...nd the superhard walls as much as possible in holing the hole inside shall be 0 5cm 1cm higher than outside considering drainage wall hole passing through outlet pipe of indoor unit side shall be slightly lower than the indoor unit downside for holing with diamond plastic cloth shall be sticked to wall or other method may be adopted to prevent water flow to wall for holing with electric hammer dus...

Страница 6: ... must be opened on the ceiling before installation with the specification as follows 1170 610 for 028 112 type and 1600 610 for 140 160 type take down the right and left cover plates of indoor unit and then embed one half of main body into the ceiling and only expose rear cover plate and head cover For seat installation use gradienter to install Hoisting bolt Hoisting bolt Hoisting support Hoistin...

Страница 7: ... designated refrigerant anything for example air shall not mix into refrigerating circuit Before welding refrigerant piping please conduct nitrogen replacement or fill nitrogen into piping in welding and finally connect with indoor unit by horn mouth When filling nitrogen into piping in welding guarantee to control the pressure with reducing valve as 0 02MPa 0 2kgf cm2 like the feel of breeze blow...

Страница 8: ... good thermal insulation Field piping must be connected to the piping connecting part all the time If poor thermal insulation for piping there will be dew outside and scald if any touch 6 Installation of Drainage Piping 6 1 Drainage piping installation In delivery the drainage outlet is PVC pipe in connecting water pipe please use auxiliary sealing material and sleeve Conduct thermal insulation fo...

Страница 9: ...ional electrician Line breaker or leakage breaker must be arranged at power supply Earthing resistance must below 4Ω Air conditioner must be earthed reliably Earthing wire shall not be connected to gas pipe tap water pipe lightening rod or telephone line Do not power on before the end of all the electric operation The terminal of the same power supply shall not be connected with two wires with dif...

Страница 10: ...on wire of TB3 outlet connects to the communication port of the next indoor unit TB2 inlet Inlet and outlet lines TB2 inlet and TB3 outlet of indoor unit shall not be reversed otherwise there will be fault and the unit can t be started Connect according to the diagram do not allow A and B polarity connection error otherwise communication failure or controller damage may be caused In order to avoid...

Страница 11: ...roller can connect to max 4 indoor units The indoor units in one group should be connected in one and same power supply to guarantee normal initialization of wire controller when power on Connection sketch of indoor unit and wire controller a When one wire controller connecting only one indoor unit refer to Fig 13 b When one wire controller connecting multi indoor units refer to Fig 14 Fig 13 One ...

Страница 12: ...9 YDEC IOM EN 1212 NONE YDEC IOM 0812 ...

Отзывы: